DMU318-400.W…-M12 - 01

2017/02

DMU318-1600.W…-M12 - 01

Multiplex operation

In this operating mode the mutual interference of adjacent sensors can be reliably avoided. For this purpose, up to 4 sensors of the same 
type are wired together in a network according to the following diagram. 

The devices operate in multiplex operation with a 

cyclically time-delayed transmission pulse

 and are switched to a passive state 

outside of the active phase, whereby the states of the outputs are frozen until the next active phase. The response time of the individual 
sensor in the network is therefore extended with respect to the response time of a single sensor as follows: 

Response time in the network = (Response time of sensor * n) + 25ms

 (n = number of sensors in the network)

Multiplex operation wiring schematic

Resetting to factory settings

The sensor can be reset to the factory setting (1 switching point at 400mm or 1600mm, rising characteristic curve with spread over the 
entire scanning range). 

Resetting to factory settings 

1. When switching on the supply voltage (during power-on),

 press the 

teach button

 for 

> 5s

.

2. Release the button

. The 

green, yellow and blue LEDs

 flash 

alternately and very quickly 

for a brief time. 

The sensor was reset to the factory setting:

switching output

: 1 

switching point at 400mm or 1600mm (1-point teach, static), 

analog output

: 4 … 20mA or 0 … 10V corresponds to an object distance of 50 … 400 mm or 150 … 1600 mm, respectively.

Sensor 2

Sensor 1

Sensor n

GND

NOTE

Please make certain that the wiring is performed according to the connection diagram.

Sync/MUX

 pin 5 on all sensors in the network must be connected to one another. 

To activate multiplex operation, the 

Sync/MUX cable must be connected to GND for 5 s 

when applying the operating voltage

.

Generation of the multiplex signal for all sensors in the network occurs automatically. 

Activating multiplex operation: 

to GND for 5s during power-on

.

DMU318…W

Summary of Contents for DMU318 W Series

Page 1: ...PN NO NC function reversible NEW Both outputs can easily be taught using a button NEW Stable plastic design NEW Temperature compensated scanning range 50 400mm 150 1600mm 10 30 V DC 4 20mA 0 10V Acces...

Page 2: ...utton 12s Indicators Yellow LED OUT2 object detected Blue LED Analog OUT object detected Yellow green or blue green LED flashing Teach in teaching error Green LED Object within the scanning range Mech...

Page 3: ...contact preset C Analog output 4 20mA V Analog output 0 10V Pin assignment of connector pin 5 gray cable wire Sync MUX K Synchronization multiplex input Connection technology M12 M12 connector 5 pin...

Page 4: ...rmally closed Close Far Far Close Dead zone Sensor OUT1 active Yellow LED ON Green LED OFF OUT1 not active Yellow LED OFF Green LED ON Distance Hysteresis Switching point Scanning range OUT1 not activ...

Page 5: ...th 2 point window teach as a function of the switching function 1 Place object at desired switching distance 1 First place object at desired switching distance for switching point 1 2 To adjust the ou...

Page 6: ...output is changed to the opposite state toggled First activate the previously described teach mode for output OUT 1 Changeover of the switching function 1 To change the switching function of output O...

Page 7: ...that is to be taught OUT1 or Analog OUT 1 Press the teach button for 2s to activate teach mode The yellow LED OUT 1 flashes at 1Hz While in this state output OUT 1 can be taught 2 To teach output Ana...

Page 8: ...ning range of 400mm 90mm scanning range of 1600mm 310mm 2 To adjust analog output Analog OUT press the teach button for 2 7s until the blue and green LEDs flash simultaneously at 3Hz 3 Release the but...

Page 9: ...of the same type are wired together in a network according to the following diagram The devices work in synchronous operation with a simultaneous transmission pulse The response time of the individual...

Page 10: ...factory setting 1 switching point at 400mm or 1600mm rising characteristic curve with spread over the entire scanning range Resetting to factory settings 1 When switching on the supply voltage during...