PROFINET
Leuze electronic
DDLS 548i
54
7.4.4
Module 2 – Link Loss Counter (LLC)
NOTICE
Module ID: 1002 with submodule ID: 1
The module makes available the current value of the Link Loss Counter
The value of the Link Loss Counter is only updated if the function was activated via module M1
(see chapter 7.4.3 "Module 1 – Communication status and control"). Upon activation of the func-
tion, the LLC value is set to 0.
• Input data length: 4 bytes consistently
Input data
Address
Data type
Value range
Default
Unit
Explanation
Link Loss
Counter
(LLC)
0 … 3
UNSIGNED
32 bit
0 …
0xffffffff
0
---
Current value of the LLC
7.4.5
Module 3 – reception quality
NOTICE
Module ID: 1003 with submodule ID: 1
The module transmits the current reception quality.
• Input data length: 1 byte consistently
Input data
Address
Data type
Value range
Default
Unit
Explanation
Reception
quality
0
UNSIGNED
8 bit
0 … 100%
0
%
This value is a mea-
sure of the reception
quality (RSSI received
signal level).
7.4.6
Module 60 – Device status
NOTICE
Module ID: 1060 with submodule ID: 1
This module contains the display of the device status as well as the control bits for resetting the
internal error logs.
• Input data length: 1 byte
• Output data length: 1 byte
Input data
Address
Data type
Value range
Default
Unit
Explanation
Device sta-
tus
0
UNSIGNED
8 bit
1: Initialization
10: Standby
15: Device is
ready
0x80: Error
0x80: Warning
0
This byte represents the
device status.
Output
data
Address
Data type
Value range
Default
Unit
Explanation
ClearError-
Log
0.0
Bit
0: No action
1: Clears log
---
---
0 -> 1 clears the error,
warning and info entires
of the device.