PROFINET
Leuze electronic
DDLS 548i
52
Module
Module name
Module contents
M3
see chapter 7.4.5 "Module 3 –
reception quality"
Reception quality
Transmit the current reception quality
M60
see chapter 7.4.6 "Mod-
ule 60 – Device status"
Device status
Display the device status and the con-
trol bits for error log reset
7.4.2
DAP module
NOTICE
Each PROFINET device must have a DAP module (DAP=Device Access Point). The DAP mod-
ule contains the specific characteristic values and limits of the DDLS 548i.
Device-specific parameters:
• VendorID: 338
• Vendor Name: Leuze electronic GmbH + Co. KG
• MainFamily: Network Systems
• ProductFamily: DDLS548i
• MaxInputLength: 1024
• MaxOutputLength: 1024
Additional persistent parameters are managed by the parameter manager and preset to default values:
• NameOfStation: ""
• IP Address: 0.0.0.0
• Gateway Address: 0.0.0.0
7.4.3
Module 1 – Communication status and control
NOTICE
Module ID: 1001 with submodule ID: 1
The module makes available status and control information for the monitoring and control of the
communication.
• Input data length: 2 bytes consistently
• Output data length: 1 byte consistently
Input data
Address
Data type
Value range
Default
Unit
Explanation
Transmitter
diode status
0.0
Bit
0: On
1: Off
0
---
The signal indicates
the current state of the
transmitter diode.
Alignment
laser status
0.1
Bit
0: Off
1: On
0
---
The signal indicates
the current state of the
alignment laser.
Link Loss
Counter
(LLC)
0.2
Bit
0: Off
1: On
0
---
The signal indicates
the current state of the
Link Loss Counter.
Link Fault
Pass-
Through
(LFP)
0.3
Bit
0: Off
1: On
0
---
The signal indicates
whether the LFP mech-
anism is switched on or
off.