Troubleshooting
Leuze electronic
CSL 710
77
Table 12.2:
LED displays - causes and measures
12.3 Error codes in the display
The following error messages can be output in the form of status codes in the device display.
Table 12.3:
Normal mode
Error
Possible cause
Measure
Teach error
Soiling of the lens covers
Poor alignment of transmitter and
receiver
Clean the lens cover on the receiver
and on the transmitter.
Check alignment.
Function reserve too low
Poor alignment of transmitter and
receiver
Soiling of the lens covers
Adjust alignment.
Test with shorter distance between
transmitter and receiver.
Clean the lens cover on the receiver
and on the transmitter.
Alignment signal too low
Poor alignment of transmitter and
receiver
Soiling of the lens covers
Adjust alignment.
Test with shorter distance between
transmitter and receiver.
Clean the lens cover on the receiver
and on the transmitter.
Outputs are not active or
change their state without a
contour change in the mea
-
surement field
Configuration data is read or writ
-
ten
End configuration communication.
During teaching, the system checks whether the signals of all beams are within a certain corridor.
If there are considerable deviations in the signal strength, this results in a teaching error and is
indicated on the LEDs. The cause may be partial soiling of the lens cover.
Measure: clean the lens covers on the transmitter and receiver!
Status code
Description
RxS 0x0100 CxL in normal mode, start-up phase still running
RxS 0x0180 CxL reconfigures itself after a configuration. Process data is invalid.
RxS 0x0190 The measurement system is not active (after a stop command or if the first trigger pulse
is missing).
RxS 0x0200 The “Leuze AutoControl ACON function” has detected soiling.
RxS 0x0300 Teach parameters have been changed (teaching must be done) or default values are
active.
RxS 0x0FFF CxL shuts down. Process data is invalid.