77
5.5. Syslog Messages: Severity Level Definitions
The Emergency level is the most severe type of message generated by ePowerSwitch 8M+
R2
and the
Debug severity level is the least severe one.
Severity Level 0, Emergency:
The following messages appear at severity 0:
- Continuous error!
Severity Level 1, Alert:
The following messages appear at severity 1:
- Settings have been reinitialized through the serial connection
- ePowerSwitch 8M+
R2
does not respond
- Satellite "number" does not respond
- Sensor "number" does not respond
- Failure on Power Input A of Master M0
- Failure on Power Input B of Master M0
- Failure on Power Input A of Satellite (number)
- Failure on Power Input B of Satellite (number)
Severity Level 2, Critical:
The following messages appear at severity 2:
- "file" config corrupted : restoring default values
Severity Level 3, Error:
ePowerSwitch 8M+
R2
doesn't generate Severity Level 3.
Severity Level 4, Warning:
The following messages appear at severity 4:
- Settings have been changed through the serial connection
- Settings have been changed through the network by User "name"
Severity Level 5, Notice:
The following messages appear at severity 5:
- Master M0 has been connected
- Satellite (number) has been connected
- Sensor (number) has been connected
- System has been restarted through the serial connection
- Power Supply A of Master restored
- Power Supply B of Master restored
- Power Supply A of Satellite (number) restored
- Power Supply B of Satellite (number) restored
- Rule (number) : Outlet (number) of Master has been switched ON
- Rule (number) : Group (number) has been switched ON
- Rule (number) : Dry Contact Output (number) has been open
Severity Level 6, Informational:
The following messages appear at severity 6:
- System has been started
- Date & Time have been synchronized to a Network Time Server
- User "name" : Outlet (number) of Master M0 has been switched ON
- User "name" : Group (number) has been switched ON
- Dry Contact Input (number) has been opened
- Dry Contact Input (number) has been closed
- Dry Contact Output (number) has been opened
- Dry Contact Output (number) has been closed
- Session opened by user "name"
Severity Level 7, Debug:
ePowerSwitch 8M+
R2
doesn't generate Severity Level 7.