LEROY-SOMER
2013.01 / k
Installation and maintenance
LSA 43.2/44.2 - 4 POLES
ALTERNATORS
3434 en -
4.7 - Installation and maintenance of
the PMG
For the LSA 43.2 and LSA 44.2, the PMG
reference is PMG 1.
See the PMG maintenance manual, ref:
4211.
Mounting is impossible with the
«regreasable bearings» option with the
LSA 44.2.
4.8 - Table of characteristics
Table of average values:
Alternator - 2 and 4 poles - 50 Hz/60 Hz -
Winding n° 6 and M or M1 connected in
dedicated single-phase. (400 V for the
excitation values).
The voltage and current values are given for
no-load operation and operation at rated
load with separate field excitation. All values
are given at ± 10% (for exact values, consult
the test report) and are subject to change
without prior warning. For 60 Hz machines,
the resistance values are the same and the
excitation current «i exc» is approximately 5
to 10% weaker.
• 3-phase LSA 43.2 4 P, SHUNT
excitation
Resistances at 20 °C (
Ω
)
LSA 43.2
Stator L/N Rotor Field Armature
S1
0.155
1.35 18.4
0.23
S15
0.155
1.35 18.4
0.23
S25
0.155
1.35 18.4
0.23
S35
0.128
1.41 18.4
0.23
M45
0.105
1.57 18.4
0.23
L65
0.083
1.76 18.4
0.23
L8
0.063
1.96 18.4
0.23
Field excitation current i exc (A) - 400 V - 50 Hz
«i exc»: excitation current of the exciter field
LSA 43.2
no load
at load
S1
0.5
1.3
S15
0.5
1.5
S25
0.5
1.6
S35
0.5
1.8
M45
0.4
1.6
L65
0.4
1.6
L8
0.4
1.6
• 3-phase LSA 43.2 4 P, AREP excitation
Resistances at 20 °C (
Ω
)
LSA
43.2
Stator
L/N Rotor
Wind.
X1,X2
Wind.
Z1,Z2 Field Armat.
S1
0,155 1,35 0,32
0,52 4,6
0,23
S15
0,155 1,35 0,32
0,52 4,6
0,23
S25
0,155 1,35 0,32
0,52 4,6
0,23
S35
0,128 1,41 0,29
0,5
4,6
0,23
M45
0,105 1,57 0,26
0,51 4,6
0,23
L65
0,083 1,76 0,26
0,44 4,6
0,23
L8
0,063 1,96 0,21
0,4
4,6
0,23
Field excitation current i exc (A) - 400 V - 50 Hz
«i exc»: excitation current of the exciter field
LSA 43.2
no load
at load
S1
1
2,6
S15
1
3
S25
1
3,2
S35
1
3,6
M45
0,8
3,2
L65
0,8
3,2
L8
0,8
3,2
• Dedicated single-phase LSA 43.2:
4-pole, SHUNT excitation (60 Hz only)
Resistances at 20 °C (
Ω
)
LSA 43.2
Stator L/N Rotor Field Armature
S1
0,058
1,35
13,9
0,23
S25
0,058
1,35
13,9
0,23
S35
0,046
1,41
13,9
0,23
M45
0,037
1,57
13,9
0,23
L65
0,027
1,76
13,9
0,23
L8
0,019
1,96
13,9
0,23
Field excitation current i exc (A) - 240 V - 60 Hz
«i exc»: excitation current of the exciter field
LSA 43.2
no load
at load
S1
0,59
1,44
S25
0,59
1,68
S35
0,66
1,65
M45
0,61
1,48
L65
0,62
1,48
L8
0,74
1,46
WARNING