6
Commissioning
6.3
Setting the station name
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.3
Setting the station name
The station name currently used is shown in code
.
The station name ...
• is required for unambiguous addressing of the Servo Drive 9400 by the I/O controller.
• can either be assigned by the I/O controller via PROFINET or set manually in the »Engineer«.
• has to be allocated in accordance with the PROFINET specification:
• 1 or several labels separated by ".".
• Max. length per label: 63 characters
• Max. total length: 240 characters
• Permissible characters: [a ... z], [0 ... 9], [.], [-]
• Labels must not begin or end with [-].
• Prohibited syntax:
• "n.n.n.n" (n = 0 ... 999)
• "port-xyz" (x, y, z = 0 ... 9)
• "port-xyz-abcde" (a, b, c, d, e, x, y, z = 0 ... 9)
Note!
• The "node blinking" PROFINET function by means of which an accessible field service
can be identified is supported. While the function is being executed, the red LED
ME
(
) is blinking.
• Operation of PROFINET requires a valid station name.
• In case of impermissible settings, the red LED
BE
) is
blinking and the error message
PROFINET: Invalid station name [0x00c86532]
is output. The communication module then continues to work internally with the
deleted name.
• If the station name is assigned by the IO controller via PROFINET or via the PROFINET
configurator of the »Engineer«, changes will become effective immediately.