Electrical installation
Control connections
l
63
EDKLCMZ3024−SPS DE/EN 4.0
4.6
Control connections
)
Note!
The sums of all inputs currents
and
output currents on X41, X42, X45, X60 and
X72 may be max. 1.3 A.
If the total current is higher, the device switches off!
lcu12x_000e
Digital inputs
X41 − digital inputs E1, E2
Pin
Signal
Description
Data
Connector: socket, 4−pole, M12
1
+24 V
Supply
2
Signal 2
E2
HIGH
+13 .... 26.5 V DC
3
GND
Reference potential
LOW
0 ... +4 V
4
Signal 1
E1
8 mA at 24 V DC
X42 − digital inputs E3, E4
Pin
Signal
Description
Data
Connector: socket, 4−pole, M12
1
+24 V
Supply
2
Signal 2
E4
HIGH
+13 .... 26.5 V DC
3
GND
Reference potential
LOW
0 ... +4 V
4
Signal 1
E3
8 mA at 24 V DC
Summary of Contents for L-force