Motor holding brake connection
The inverter is designed for 24 V brakes. The motor holding brake is connected to X106.
The operation of a motor holding brake requires a separate voltage supply at X107.
n
EYF
GB
24B
DC 24 V SELV/PELV
(+19.2 V ... +28.8 V)
BD2
BD1
Fig. 9: Connection diagram - motor holding brake
Motor holding brake connection
Terminal
X106: BD1, BD2
Controlling a motor holding brake with or
without brake voltage reduction
Level
V
LOW: < +5, HIGH: > +15
Max. output current
0.55 ... 15 kW A
2.5
22 ... 110 kW
5.0
Cycle time
ms 1
Short-circuit-proof
Unlimited period
Suppressor circuit
Freewheeling diode and spark
suppressor are integrated
Max. breaking energy
0.55 ... 15 kW Ws 5
22 ... 110 kW Ws 20
Max. operating frequency
6/min at max. output current
Depending on the output current:
Doubling the operating frequency while
halving the output current
Insulation
Basic insulation
Electrical installation
Motor holding brake connection
126
Summary of Contents for i950-Cabinet
Page 2: ......
Page 4: ...4...
Page 29: ...22 kW Die Abmessungen in mm gelten f r 22 kW I95AE322F Mechanische Installation Abmessungen 29...
Page 49: ...I95AE322F 3 3 Elektrische Installation Anschluss an das IT Netz 49...
Page 51: ...I95AE390F I95AE411F 3 3 Elektrische Installation Anschluss an das IT Netz 51...
Page 103: ...22 kW The dimensions in mm apply to 22 kW I95AE322F Mechanical installation Dimensions 103...
Page 104: ...30 hp The dimensions in inch apply to 30 hp I95AE322F Mechanical installation Dimensions 104...
Page 123: ...I95AE322F 3 3 Electrical installation Connection to the IT system 123...
Page 125: ...I95AE390F I95AE411F 3 3 Electrical installation Connection to the IT system 125...
Page 153: ......