Branch Circuit Protection (BCP) with Short Circuit Current Ratings (SCCR) with Standard Fuses and Circuit
Breaker. (Tested per UL61800-5-1, reference UL file E132659)
These devices are suitable for motor group installation when used with Standard Fuses and Circuit Breaker.
For single motor installation, if the fuse value indicated is higher than 400% of the motor current (FLA), the
fuse value has to be calculated. If the value of the fuse is below two standard ratings, the nearest standard
ratings less than the calculated value shall apply.
Inverter
Standard Fuses (UL248)
Circuit Breaker (UL489)
Mains
Rated
power
Rated
power
SCCR Max. rated
current
Class
SCCR Max. rated
current
Min. cabinet
dimensions
Min. cabinet
dimensions
kW
hp
kA
A
kA
A
m³
ft³
480 V, 3-ph
0.55
0.75
65
35
CC,CF,J,T
65
25
0.042
1.48
480 V, 3-ph
0.75
1
65
35
CC,CF,J,T
65
25
0.042
1.48
480 V, 3-ph
2.2
3
65
35
CC,CF,J,T
65
25
0.042
1.48
480 V, 3-ph
4
5
65
35
CC,CF,J,T
65
25
0.042
1.48
480 V, 3-ph
7.5
10
65
60
CC,CF,J,T
65
60
0.042
1.48
480 V, 3-ph
11
15
65
60
CC,CF,J,T
65
60
0.042
1.48
480 V, 3-ph
15
20
65
60
CC,CF,J,T
65
60
0.042
1.48
480 V, 3-ph
22
30
65
70
CC,CF,J,T
65
70
0.17
6
480 V, 3-ph
30
40
22
125
CC,CF,J,T
35
125
0.57
20
480 V, 3-ph
45
60
22
125
CC,CF,J,T
35
125
0.57
20
480 V, 3-ph
55
75
22
200
CC,CF,J,T
35
200
0.57
20
480 V, 3-ph
75
100
22
200
CC,CF,J,T
35
200
0.57
20
480 V, 3-ph
90
125
22
300
CC,CF,J,T
10
300
0.57
20
480 V, 3-ph
110
150
22
300
CC,CF,J,T
10
300
0.57
20
Branch Circuit Protection (BCP) with Short Circuit Current Rating (SCCR) for Semiconductor Fuses. (Tested
per UL61800-5-1, reference UL file E132659)
These devices are suitable for standard installation when used with Semiconductor Fuses. For single motor
installation, if the fuse value indicated is higher than 400% of the motor current (FLA), the fuse value has to
be calculated. If the value of the fuse is below two standard ratings, the nearest standard ratings less than
the calculated value shall apply.
Inverter
Alternate Fuse (Semiconductor Fuse)
Mains
Rated power
Rated power
SCCR
Max. rated current
kW
hp
kA
A
480 V, 3-ph
0.55
0.75
100
6
480 V, 3-ph
0.75
1
100
6
480 V, 3-ph
2.2
3
100
20
480 V, 3-ph
4
5
100
50
480 V, 3-ph
7.5
10
100
63
480 V, 3-ph
11
15
100
80
480 V, 3-ph
15
20
100
80
480 V, 3-ph
22
30
100
100
480 V, 3-ph
30
40
100
125
480 V, 3-ph
45
60
100
125
480 V, 3-ph
55
75
100
200
480 V, 3-ph
75
100
100
200
480 V, 3-ph
90
125
100
350
480 V, 3-ph
110
150
100
350
Elektrische Installation
Anschluss nach UL
41
Summary of Contents for i950-Cabinet
Page 2: ......
Page 4: ...4...
Page 29: ...22 kW Die Abmessungen in mm gelten f r 22 kW I95AE322F Mechanische Installation Abmessungen 29...
Page 49: ...I95AE322F 3 3 Elektrische Installation Anschluss an das IT Netz 49...
Page 51: ...I95AE390F I95AE411F 3 3 Elektrische Installation Anschluss an das IT Netz 51...
Page 103: ...22 kW The dimensions in mm apply to 22 kW I95AE322F Mechanical installation Dimensions 103...
Page 104: ...30 hp The dimensions in inch apply to 30 hp I95AE322F Mechanical installation Dimensions 104...
Page 123: ...I95AE322F 3 3 Electrical installation Connection to the IT system 123...
Page 125: ...I95AE390F I95AE411F 3 3 Electrical installation Connection to the IT system 125...
Page 153: ......