Terminal data
Rated power
P
rated
kW
0.37 ... 0.75
Connection description
Mains connection
Connection
X100
Connection type
Pluggable
Max. cable cross-section
mm²
4
Max. cable cross-section
AWG
10
Stripping length
mm
8
Stripping length
in
0.3
Tightening torque
Nm
0.6
Tightening torque
lb-in
5.3
Required tool
Screwdriver 0.5 x 3.0
Rated power
P
rated
kW
0.37 ... 0.75
Connection description
PE connection
Connection
PE
Max. cable cross-section
mm²
6
Max. cable cross-section
AWG
10
Stripping length
mm
10
Stripping length
in
0.4
Tightening torque
Nm
2
Tightening torque
lb-in
18
Required tool
Torx key 20
Rated power
P
rated
kW
0.37 ... 0.75
Connection description
Motor connection
Connection
X105
Connection type
Pluggable
Max. cable cross-section
mm²
4
Max. cable cross-section
AWG
10
Stripping length
mm
8
Stripping length
in
0.3
Tightening torque
Nm
0.6
Tightening torque
lb-in
5.3
Required tool
Screwdriver 0.5 x 3.0
Fusing data
A residual current device (RCD) is optional.
Fusing data for UL/NEC compliant installations:
Inverter
Fuse
Circuit breaker
RCD
Characteristic
Max. rated
current
Characteristic
Max. rated
current
Type
A
A
mA
I51AP137A
gG/gL, gRL
32
B
32
≥30
Typ B
I51AP175A
gG/gL, gRL
32
B
32
≥30
Typ B
Electrical installation
Mains connection
1-phase mains connection 120 V
26
Summary of Contents for i510 protec