Terminal data
Rated power
P
rated
kW
0.37 ... 1.5
2.2 ... 4
Connection description
Mains connection
Connection
X100
Connection type
Pluggable
Max. cable cross-section
mm²
4
6
Max. cable cross-section
AWG
10
10
Stripping length
mm
8
8
Stripping length
in
0.3
0.3
Tightening torque
Nm
0.6
0.7
Tightening torque
lb-in
5.3
6.2
Required tool
Screwdriver 0.5 x 3.0
Screwdriver 0.6 x 3.5
Rated power
P
rated
kW
0.37 ... 4
Connection description
PE connection
Connection
PE
Max. cable cross-section
mm²
6
Max. cable cross-section
AWG
10
Stripping length
mm
10
Stripping length
in
0.4
Tightening torque
Nm
2
Tightening torque
lb-in
18
Required tool
Torx key 20
Rated power
P
rated
kW
0.37 ... 1.5
2.2 ... 4
Connection description
Motor connection
Connection
X105
Connection type
Pluggable
Max. cable cross-section
mm²
4
6
Max. cable cross-section
AWG
10
10
Stripping length
mm
8
8
Stripping length
in
0.3
0.3
Tightening torque
Nm
0.6
0.7
Tightening torque
lb-in
5.3
6.2
Required tool
Screwdriver 0.5 x 3.0
Screwdriver 0.6 x 3.5
Fusing data
A residual current device (RCD) is optional.
Fusing data for UL/NEC compliant installations:
Inverter
Fuse
Circuit breaker
RCD
Characteristic
Max. rated
current
Characteristic
Max. rated
current
Type
A
A
mA
I51AP137D
gG/gL, gRL
40
B
32
≥30
Typ B
I51AP175D
gG/gL, gRL
40
B
32
≥30
Typ B
I51AP211D
gG/gL, gRL
40
B
32
≥30
Typ B
I51AP215D
gG/gL, gRL
40
B
32
≥30
Typ B
I51AP222D
gG/gL, gRL
40
B
32
≥30
Typ B
I51AP230C
gG/gL, gRL
80
B
32
≥30
Typ B
I51AP240C
gG/gL, gRL
80
B
32
≥30
Typ B
Electrical installation
Mains connection
3-phase mains connection 230/240 V
31
Summary of Contents for i510 protec
Page 2: ......