Parameter setting
Parameter setting using the keypad
10
L
EDK82EVXXX EN 2.0
2.1.4
Menu structure
For easy operation the codes are divided in two groups:
z
The menu
user
– is active after every mains switching or keypad attachment during operation.
– contains all codes for a standard application with linear V/f characteristic control (Lenze
setting).
– can be modified as required under C0517.
z
The menu
all
– contains all codes.
– shows a list of all codes in ascending order.
2.2
The menu
uuuusssseeeerrrr
- The 10 most important drive parameters
After mains switching or plugging in the keypad during operation, the 10 codes defined in code
C0517 are immediately available.
In default setting the menu
user
contains all codes required for a standard application with linear V/f
characteristic control.
Code
Name
Lenze setting
C0050 Output frequency
Display: Output frequency without slip compensation
C0034 Setpoint selection range
0
Standard I/O
X3/8:
0 ... 5 V / 0 ... 10 V / 0 ... 20 mA
C0034 Setpoint selection range
0
Application I/O
X3/1U: 0 ... 5 V / 0 ... 10 V
X3/2U: 0 ... 5 V / 0 ... 10 V
C0007 Fixed configuration of digital inputs
0
E4
E3
E2
E1
C0007 Fixed configuration of digital inputs
0
CW/CCW
DCB
JOG2/3
JOG1/3
CW/CCW rotation
DC injection brake
Selection of fixed setpoints
C0010 Minimum output frequency
0.00 Hz
C0011 Maximum output frequency
50.00 Hz
C0012 Acceleration time main setpoint
5.00 sec
C0013 Deceleration time main setpoint
5.00 sec
C0015 V/f rated frequency
50.00 Hz
C0016 V
min
boost
Depending on the controller
C0002 Parameter set management
Restore default setting; Transfer parameter sets with keypad; save, load or copy own
basic settings
Note!
Use C0002 ” Parameter set transfer/restorage of default setting” to transfer
configurations from one controller to the other with keypad or restore the default
setting by loading the Lenze setting (e.g. if you lost track during parameter setting).