Parameter setting

Parameter setting using the keypad

8

L

EDK82EVXXX EN 2.0

2.1.2

Display elements and function keys

z
y

w x

v

t

u

s

88888

8888

888

8

a

b

c

d

e

j g f k i h

PS



‚

m n o

p

q r

Hi

Hz

%sh

rpm

°C

m

A

V

Lo

8

0

3

1

2

4
6

5
7

E82ZBC002

Status displays

Meaning

Explanation

-

Ready for operation

,

Pulse inhibt active

Power outputs inhibited

+

Adjusted current limitation is exceeded in motor-mode or
generator-mode

C0022 (motor mode) or C0023 (generator mode)

.

Warning active

*

Active fault

Function bar 1

Meaning

Explanation

3

Setpoint selection via

AB

Not possible when password protection is active (display =

”loc”

)

0

Display function:

User menu, memory location 1 (C0517/1), display

Display active parameter set

Active after every mains connection

/

Code selection

Four-digit display of the active code number

4

Select subcodes

Three-digit display of the active subcode number

2

Change the parameter value of a (sub) code

Five-digit display of the current value

1

Display of values longer than 5 digits

1

H:

high-order positions

Display

”HI”

L:

low-order positions

Display

”lo”

Function bar 2

Meaning

Explanation

5

Select parameter set 1 ... 4 for changing

Display, e.g. PS

2

(

)

The parameter sets can only be activated via digital signals
(configuration with C0410)

6

Select system bus (CAN) devices

The selected device can be parameterised by the current drive

:

= function active

7

Select menu

user

List of codes in the user menu (C0517)

7

The user menu is active after mains switching

all

List of all codes

funci

Only specific codes for bus function modules, e.g.
INTERBUS, PROFIBUS-DP, LECOM-B, ...

Bargraph display

Value set under C0004 in %
(Lenze setting: Controller load C0056)

Display range: - 180 % ... + 180 % (every bar = 20 %)

Display of parameter set

In the mode

0

:

Display of the parameter set activated via digital signal
Otherwise:
Display of the parameter set active for changing

Select the single parameter sets in the mode

5

in the function

bar 2

Summary of Contents for Global Drive 8200 vector

Page 1: ...L Information for the operator of the machine system EDK82EVXXX P2F Global Drive 8200 vector frequency inverter 0 25 90 kW P2F...

Page 2: ...kW Inverter Input Output 8200 vector Type _ K For detailed information refer to the manual EDK82EV222 Id No Made in Germany 1D74 Industrial Control Equipment D 31855 Aerzen Hans Lenze Str 1 Prod No Se...

Page 3: ...Drive controllers are components which are designed for installation in electrical systems or machinery They are not to be used as household appliances They are intended exclusively for professional a...

Page 4: ...ry adapt the controllers to your application Please observe the corresponding information given in the Instructions After the controller has been disconnected from the supply voltage live components a...

Page 5: ...be used as safety brakes It cannot be guaranteed that factors which cannot be influenced such as oil ingression because of a defective A side shaft seal do not cause a torque reduction Transport stora...

Page 6: ...and the box itself must be sealed against dust and water For the trial run without output elements lock the key Check brakeoperation before commissioning of low voltage machines with brakes Operation...

Page 7: ...heatsink of the controller has an operating temperature of 80 C Direct skin contact with the heatsink results in burnings Controller protection z All pluggable connection terminals must only be conne...

Page 8: ...graph Signal word Possible consequences if the safety information are Signal word Meaning safety information are disregarded Danger Impending danger for persons Death or most severe injuries Dangerous...

Page 9: ...f k i h PS m n op q r Hi Hz sh rpm C m A V Lo z y w x v t u s 88800 0050000 1 a b c d e j g f k i h PS m n op q r Hi Hz sh rpm C m A V Lo 88888 8888888 8 a b c d e j g f k i h PS m n op q r Hi Hz sh r...

Page 10: ...bcode number 2 Change the parameter value of a sub code Five digit display of the current value 1 Display of values longer than 5 digits 1 H high order positions Display HI L low order positions Displ...

Page 11: ...igital signals must be used to activate a parameter set for operation configuration with C0410 z In the function 0 the display shows the parameter set which is just active during operation Step Keys R...

Page 12: ...quency Display Output frequency without slip compensation C0034 Setpoint selection range 0 Standard I O X3 8 0 5 V 0 10 V 0 20 mA C0034 Setpoint selection range 0 Application I O X3 1U 0 5 V 0 10 V X3...

Page 13: ...Lo 1 j g f k i h PS 001 0 000 000 a b c d e m n op q r Hi Hz Lo 1 j g f k i h PS 0007 000 000 a b c d e m n op q r Hi Hz Lo 1 j g f k i h PS 0034 z y w x v t u s 000 000 a b c d e m n op q r Hi Hz Lo...

Page 14: ...ect configuration in C0410 Use internal voltage source X3 20 for function modules Standard I O INTERBUS PROFIBUS DP or LECOM B RS485 Bridge between X3 7 and X3 39 is missing Bridge terminals Motor doe...

Page 15: ...r active check under C0161 OFF 20 28 X3 880Hr 01 61 000 1 a b c d e j g f k i h PS m n op q r Hi Hz sh rpm C m A V Lo 3 1 4 5 2 6 ON z y w x v t u s 88888 8888888 8 a b c d e j g f k i h PS m n op q r...

Page 16: ...us configuration For operation with application I O Faulty parameter setting of parameter set changeover In all parameter sets the signal parameter set changeover C0410 13 C0410 14 must be combined wi...

Page 17: ...re 80 C Impermissibly high currents or too frequent and too long acceleration Check drive selection Check load if necessary replace defective bearings OH3 53 PTC monitoring TRIP is displayed if C0119...

Page 18: ...to TRIP reset More than 8 fault messages in 10 minutes Depends on the error message sd5 85 Wire breakage analog input 1 Current at analog input 4 mA at setpoint range 4 20 mA Close circuit at analog i...

Reviews: