3-phase mains connection 480 V
Connetion for single drive according to UL 61800-5-1
L1
L1
L2
L3
N
PE
F1 … F3
L2 L3
SELV/PELV
DC 24 V
(+19.2 … +28.8 V)
5.6k
5.6k
R
b
M
3~
Rb1
Rb2
V
U
W
+
+
X3
X4
+
1
2
3
BD1
BD2
X2
1
2
3
4
X1
1
2
3
4
X5
max. 50 mA
X6
GND
-I
DI1
DI2
n. c.
5.6k
GND
-O
DO1
DI3
24V
1
2
3
4
1
2
3
4
DC
AC
Q
400
Rb1
Rb2
X4
R
b
Rb1 Rb2
390
Fuse data (F1 ... F3)
Motor
MSEMA
☐☐
063-42
MSEMA
☐☐
080-32
Cable installation in compliance
with
UL 61800-5-1
Fuse
Standard
UL 248
Typ. rated current
A
3
6
Max. rated current
A
3
10
Semiconductor fuse
Standard
UL 248
Typ. rated current
A
3
6
Max. rated current
A
3
10
Circuit breaker
Standard
UL 489
Typ. rated current
15
15
Max. rated current
A
15
15
•
Use UL-approved cables:
•
Conductor temperature < 75 °C, ambient temperature < 40 °C
•
Operation from mains supply 5 kA rms SCCR:
•
Use current-limited UL-approved fuses (UL 248) or automatic circuit breakers (UL 489),
voltage ≥480 V.
•
Operation from mains supply 200 kA rms SCCR:
•
Use current-limiting UL-approved fuses (UL 248), current limiting rating von 200 kA rms to
max. 5 kA rms, e.g. 15 A class CC.
Mounting/ installation
Electrical installation
Mains connection
62