Electrical installation
Important notes
DANGER!
Dangerous electrical voltage
The product's power connections can still be carrying voltage when the mains supply has been
switched off.
Possible consequences: Death or severe injuries when touching the power terminals.
▶
Do not touch the power connections immediately. Take note of the corresponding warning
plates on the product.
▶
Check to make sure that all power connections are deenergised.
DANGER!
Dangerous electrical voltage
The leakage current against earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences: Death or severe injuries when touching the device in the event of an
error.
▶
Implement the measures required in EN 61800-5-1, especially:
▶
Fixed installation
▶
The PE connection must comply with the standards (PE conductor diameter ≥ 10 mm
2
or
use a double PE conductor)
NOTICE
No protection against excessively high mains voltage
The mains input is not fused internally.
Possible consequences: Destruction of the product in the event of excessively high mains volt-
age.
▶
Take note of the maximum permissible mains voltage.
▶
On the mains supply side, use fuses to adequately protect the product against mains fluctu-
ations and voltage peaks.
Mounting/ installation
Electrical installation
Important notes
58