Electrical installation
Important notes
51
EDK94AZMP DE/EN/FR/ES/IT 8.0
Danger!
Hazardous electrical voltage
The leakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences:
ƒ
Death or severe injuries when touching the device in the event of
an error.
Protective measures:
Implement the measures required in EN 61800−5−1. Especially:
ƒ
Fixed installation
– Implement PE connection in compliance with standards.
– Connect PE conductor twice or PE conductor cross−section
³
10 mm
2
.
ƒ
Connection with a connector for industrial applications according
to IEC 60309 (CEE):
– PE conductor cross−section
³
2.5 mm
2
as part of a multi−core
supply cable.
– Provide for suitable strain relief.