Technical data
Rated data
42
EDK94AZMP DE/EN/FR/ES/IT 8.0
4.2
Rated data
Mains
Voltage
Voltage range
Frequency range
U
Lrated
[V]
U
Lrated
[V]
f [Hz]
3/PE AC
230
180 − 0 % ... 264 + 0 %
45 − 0 % ... 65 + 0 %
3/PE AC
400
320 − 0 % ... 440 + 0 %
45 − 0 % ... 65 + 0 %
3/PE AC
500
400 − 0 % ... 550 + 0 %
45 − 0 % ... 65 + 0 %
Voltage
Freq.
Current [A]
Current [A]
Number
of phases
[V]
[Hz]
max. +45° C
max. +55° C
E94AZMP0084
230/400/500
50/60
8/8/8
6/6/6
3
E94AZMP0294
230/400/500
50/60
29/29/29
21.8/21.8/21.8
3
E94AZMP0294
2)
400/480
50/60
24.5/24.5
15.3/15.3
3
Temperature in the control cabinet
2)
For i700 mounting: mains connection at the bottom, output at the top
Power loss
Inductance
Voltage drop
P
loss
[W]
L [mH]
D
U [V]
E94AZMP0084
50
3.9
9.8
E94AZMP0294
110
0.7
6.4
Thermal contact
Design
max. switching voltage
max. switching current
U
Th
[V AC]
I
Th
[A]
E94AZMP0084
NC contact, 150 °C
250
2.5
E94AZMP0294