Commissioning
6.4
Setting the IP configuration
30
Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.4.1
Setting via the PROFINET configurator of the »Engineer«
How to set the IP parameters via the PROFINET configurator:
1. Execute the menu command
Online
Profinet configurator addresses...
.
The
Assign IP addresses
dialog window is opened, and all Lenze PROFINET devices
connected are listed.
Note!
• The IP address must only be allocated manually in the »Engineer« if the PROFINET
network is not operated on the IO controller yet (IP address has not been allocated by
the IO controller yet).
• While setting the IP parameters in the »Engineer«, PROFINET communication with the
IO controller must not take place at the same time.
• Changes will be effective immediately and are saved with mains failure protection.