Parameter data transfer
Parameter set transfer
l
84
EDS82ZAFPC201 EN 4.0
8.3
Parameter set transfer
Lenze parameter sets
The 8200 vector and 8200 motec controllers have 2/4 parameter sets, whose parameters
can directly be addressed with the PROFIBUS.
)
Note!
ƒ
Parameter set 1 can be accessed via ...
– DRIVECOM parameter data channel
– PROFIdrive parameter data channel (DP−V0)
– PROFIdrive parameter data channel (DP−V1)
ƒ
Parameter sets 2 ... 4 can be accessed via ...
– DRIVECOM parameter data channel
– PROFIdrive parameter data channel (DP−V1)
Addressing of Lenze parameter sets
The parameter sets are addressed by means of a code offset:
ƒ
Offset 0 addresses parameter set 1 (C0000 ... C1999).
ƒ
Offset 2000 addresses parameter set 2 (C2000 ... C3999).
ƒ
Offset 4000 addresses parameter set 3 (C4000 ... C5999).
ƒ
Offset 6000 addresses parameter set 4 (C6000 ... C7999).
If a parameter is only available once (see documentation for 8200 vector), use the code
offset 0.
Example for C0011 (maximum rotating−field frequency):
ƒ
C0011 in parameter set 1: Lenze code number = 11
ƒ
C0011 in parameter set 2: Lenze code number = 2011
ƒ
C0011 in parameter set 3: Lenze code number = 4011
ƒ
C0011 in parameter set 4: Lenze code number = 6011
Parameter set transfer with keypad
)
Note!
Always switch the mains after you have transferred the parameter sets with
the keypad!
Observe the options for parameter set transfer with keypad marked with
"Keypad
ð
" under code
C0002
.
If an address is assigned via
C1509
, the address must be reassigned via the parameter data
channel after a parameter set transfer. Afterwards mains switching is required. The
address modified via keypad becomes effective immediately.