Commissioning
Test commissioning
Test commissioning with keypad control
7
89
EDS84ABD302 EN 4.0
4. Set keypad control
-0-
_
-1-
PASS
2 sec.
2 sec.
_
_ `
_
_
....
_
C...
C007
-2-
_
`
_ `
....
C002
0020
-3-
0000
0000
`
`
`
`
`
_ `
....
84BLMEN001
z
Select menu -3- (quick commissioning with integrated keypad)
z
Press ”Enter” key
z
Set C007 code
z
Press ”Enter” key
z
Set value ”20”
z
Press ”Enter” key
5. Enable controller:
Set terminal X4/RFR to HIGH-Potential (reference: X4/12I).
6. Vary the motor speed with the integrated keypad or by defining different fixed
setpoints:
Internal Keypad
Code
Subcode
Motor speed
_
`
C...
C728
c003
_ `
.....
-199.9
_ `
199.9
C00728
3
Counter-clockwise rotation:
-199.9 % .... 0 (from C00011)
Clockwise rotation
0 ... +199.9 % (from C00011)
C00051
-
Observe
z
the actual speed value:
C00051
z
appearing messages
92
7. Save the settings with mains failure protection by entering the value ”1” in code
C002, subcode 7.