Technical data
Rated data
Operation at rated mains voltage 500 V
4
35
EDS84ABD302 EN 4.0
Fuses and cable cross-sections
Operation without external mains choke/mains filter
Type
Installation according to EN 60204-1
1)
Installation according
to UL
2)
FI
3)
c
d
L1, L2, L3 - Laying system
e
L1, L2, L3
B2
C
F
[A]
[A]
[mm
2
]
[mm
2
]
[mm
2
]
[A]
[AWG]
[mA]
E84AVBxx3714
C6
6
1.5
-
-
10
14
≥
30
E84AVBxx5514
C6
6
1.5
-
-
10
14
E84AVBxx7514
C6
6
1.5
-
-
10
14
E84AVBxx1124
C10
10
1.5
-
-
10
14
E84AVBxx1524
C10
10
1.5
-
-
10
14
E84AVBxx2224
C10
10
1.5
-
-
10
14
E84AVBxx3024
C16
16
1.5
-
-
12
14
1)
These values are recommendations only. Other dimensioning values/laying systems are possible (e.g. according to
VDE 0298-4). The cable cross-sections apply under the following conditions: Use of PVC-insulated copper cables,
conductor temperature < 70 °C, ambient temperature < 45°C, no bundling of cables or cores, three loaded cores.
2)
Use UL-approved cables, fuses and fuse holders only.
UL fuse: voltage
≥
500 V, tripping characteristic ”H”, ”K5” or ”CC”. The cable cross-sections apply under the following
conditions: conductor temperature < 75 °C, ambient temperature < 45°C.
3)
Universal-current sensitive earth-leakage circuit breaker, short-time delay
If cables are longer than 50 m, the protective circuit-breaker may respond, depending on the cable type and
switching frequency.
c
Circuit breaker
d
Fuse
e
Fuse
Observe national and regional regulations
Operation with external mains choke/mains filter
Type
Installation according to EN 60204-1
1)
Installation according
to UL
2)
FI
3)
c
d
L1, L2, L3 - Laying system
e
L1, L2, L3
B2
C
F
[A]
[A]
[mm
2
]
[mm
2
]
[mm
2
]
[A]
[AWG]
[mA]
E84AVBxx3714
C6
6
1.5
-
-
10
14
≥
30
E84AVBxx5514
C6
6
1.5
-
-
10
14
E84AVBxx7514
C6
6
1.5
-
-
10
14
E84AVBxx1124
C6
6
1.5
-
-
10
14
E84AVBxx1524
C10
10
1.5
-
-
10
14
E84AVBxx2224
C10
10
1.5
-
-
10
14
E84AVBxx3024
C16
16
1.5
-
-
12
14
1)
These values are recommendations only. Other dimensioning values/laying systems are possible (e.g. according to
VDE 0298-4). The cable cross-sections apply under the following conditions: Use of PVC-insulated copper cables,
conductor temperature < 70 °C, ambient temperature < 45°C, no bundling of cables or cores, three loaded cores.
2)
Use UL-approved cables, fuses and fuse holders only.
UL fuse: voltage
≥
500 V, tripping characteristic ”H”, ”K5” or ”CC”. The cable cross-sections apply under the following
conditions: conductor temperature < 75 °C, ambient temperature < 45°C.
3)
Universal-current sensitive earth-leakage circuit breaker, short-time delay
If cables are longer than 50 m, the protective circuit-breaker may respond, depending on the cable type and
switching frequency.
c
Circuit breaker
d
Fuse
e
Fuse
Observe national and regional regulations
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]