Technical data
3-2
L
BA2141 EN 1.0
3.3
Rated data
Field
Values
Voltage supply
24 V DC
ñ
10 %; max. 120 mA
Communication profile
LONMARK
®
Functional Profile “Variable Speed Motor Drive”
Communication medium
FTT - 10 A (Free Topology Transceiver)
Insulation voltage between bus and ...
Rated insulation voltage
Insulation type
•
Earth reference / PE
50 V AC
Mains isolation
•
External supply (terminal 39/59)
50 V AC
Mains isolation
•
Power stage
– 820X / 821X
270 V AC
Basic insulation
– 822X / 8200 vector
270 V AC
Double insulation
– 93XX
270 V AC
Double insulation
•
Control terminals
– 820X / 8200 vector (with internal supply)
0 V AC
No mains isolation
– 8200 vector (with external supply
100 V AC
Basic insulation
– 821X
50 V AC
Mains isolation
– 822X
270 V AC
Basic insulation
– 93XX
270 V AC
Basic insulation
Degree of pollution
VDE0110, part 2, pollution degree 2
3.4
Dimensions
Service
LON
L
24V DC
FTT
2141
62
75
18
23
Fig. 3-1
Dimensions of the 2141 fieldbus module (all dimensions in mm)