Technical data
3.1
Features of the 2141 fieldbus module
•
Attachable additional module for the following devices:
– 82XX
– 8200 vector
– Drive PLC
– 93XX
– 9300 Servo PLC
•
LON connection module with the LONMARK
®
Functional Profile “ Variable Speed Motor
Drive”
•
Access to all Lenze parameters
•
Internal and external 24-V-DC voltage supply possible with devices listed above
(exception 820X: only external supply)
3.2
General data / application conditions
Field
Values
Order name
EMF2141IB
Network topology
Free topology (line, tree, star, ring)
Possible number of nodes
64
Max. cable length
2700 m with bus topology
500 m if the topology is mixed
Baud rate
78 kBit/s
Ambient temperature
during
operation:
during
transport:
during storage:
0° C ... 55° C
-25° C ... 70° C
-25° C ... 60 °C
Permissible humidity
Class 3K3 to EN 50178 (without condensation, average relative humidity 85%)