Table 1. Specifications, Type 7D2F, 7D2G, and 7D2H (continued)
Heat output
Approximate heat output:
• Minimum configuration: 447 BTU, 131 W (in BTU per hour and watts)
• Maximum configuration: 5265 BTU, 1543 W (in BTU per hour and watts)
Environment
ThinkSystem SR850P complies with ASHRAE Class A2 specifications. Depending on
the hardware configuration, some models comply with ASHRAE Class A3 and Class A4
specifications. System performance may be impacted when operating temperature is
outside AHSARE A2 specification.
• Air temperature:
– Operating
– ASHARE Class A2: 10°C to 35°C (50°F to 95°F); the maximum ambient
temperature decreases by 1°C for every 300 m (984 ft) increase in altitude
above 900 m (2,953 ft).
– ASHARE Class A3: 5°C to 40°C (41°F to 104°F); the maximum ambient
temperature decreases by 1°C for every 175 m (574 ft) increase in altitude
above 900 m (2,953 ft).
– ASHARE Class A4: 5°C to 45°C (41°F to 113°F); the maximum ambient
temperature decreases by 1°C for every 125 m (410 ft) increase in altitude
above 900 m (2,953 ft).
– Server off: 5°C to 45°C (41°F to 113°F)
– Shipment/storage: -40°C to 60°C (-40°F to 140°F)
• Maximum altitude: 3,050 m (10,000 ft)
• Relative Humidity (non-condensing):
– Operating
– ASHRAE Class A2: 8% to 80%; maximum dew point: 21°C (70°F)
– ASHRAE Class A3: 8% to 85%; maximum dew point: 24°C (75°F)
– ASHRAE Class A4: 8% to 90%; maximum dew point: 24°C (75°F)
– Shipment/storage: 8% to 90%
• Particulate contamination
Attention:
Airborne particulates and reactive gases acting alone or in combination
with other environmental factors such as humidity or temperature might pose a risk to
the server. For information about the limits for particulates and gases, see
“Particulate contamination” on page 5
.
Note:
To maintain component reliability, system performance might vary at ambient temperature higher than
35°C while all the fans are functioning. With one fan failing, system performance might vary at ambient
temperature higher than 27°C.
Particulate contamination
Attention:
Airborne particulates (including metal flakes or particles) and reactive gases acting alone or in
combination with other environmental factors such as humidity or temperature might pose a risk to the
device that is described in this document.
Risks that are posed by the presence of excessive particulate levels or concentrations of harmful gases
include damage that might cause the device to malfunction or cease functioning altogether. This
specification sets forth limits for particulates and gases that are intended to avoid such damage. The limits
must not be viewed or used as definitive limits, because numerous other factors, such as temperature or
moisture content of the air, can influence the impact of particulates or environmental corrosives and gaseous
contaminant transfer. In the absence of specific limits that are set forth in this document, you must
implement practices that maintain particulate and gas levels that are consistent with the protection of human
health and safety. If Lenovo determines that the levels of particulates or gases in your environment have
caused damage to the device, Lenovo may condition provision of repair or replacement of devices or parts
on implementation of appropriate remedial measures to mitigate such environmental contamination.
Implementation of such remedial measures is a customer responsibility.
5
Summary of Contents for 7D2F
Page 1: ...ThinkSystem SR850P Maintenance Manual Machine Types 7D2F 7D2G and 7D2H ...
Page 8: ...vi ThinkSystem SR850P Maintenance Manual ...
Page 20: ...12 ThinkSystem SR850P Maintenance Manual ...
Page 172: ...164 ThinkSystem SR850P Maintenance Manual ...
Page 176: ...168 ThinkSystem SR850P Maintenance Manual ...
Page 186: ...178 ThinkSystem SR850P Maintenance Manual ...
Page 187: ......
Page 188: ...Part Number SP47A58972 Printed in China 1P P N SP47A58972 1PSP47A58972 ...