background image

Page 17

507111-02     2/2015

C - Refrigerant Charge and Check

WARNING-Do not exceed nameplate charge under
any condition.

This unit is factory charged and should require no further
adjustment. If the system requires additional refrigerant,

reclaim the charge,

 

evacuate the system,

 and 

add

required nameplate charge.

NOTE - System charging is not recommended below
60

°

F (15

°

C). In temperatures below 60

°

F (15

°

C),

 

the

charge

 must 

be weighed into the system.

If weighing facilities are not available, or to check the
charge, use the following procedure:

IMPORTANT - Charge unit in standard cooling mode
high stage only.

1- Make sure outdoor coil is clean. Attach gauge

manifolds and operate unit at full CFM in cooling mode
with economizer disabled until system stabilizes
(approximately five minutes). Make sure all outdoor air
dampers are closed.

2- Compare the normal operating pressures (see tables

4 - 9) to the pressures obtained from the gauges.
Check unit components if there are significant
differences.

3- Measure the outdoor ambient temperature and the

suction pressure. Refer to the appropriate circuit
charging curve to determine a target liquid
temperature.

Note - Pressures are listed for sea level applications.

4- Use the same thermometer to accurately measure the

liquid temperature (in the outdoor section).

If measured liquid temperature is higher than

the target liquid temperature, add refrigerant to
the system.

If measured liquid temperature is lower than

the target liquid temperature, recover some
refrigerant from the system.

5- Add or remove charge in increments. Allow the

system to stabilize each time refrigerant is added or
removed.

6- Continue the process until measured liquid

temperature agrees with the target liquid
temperature. Do not go below the target liquid
temperature when adjusting charge. Note that
suction pressure can change as charge is adjusted.

7- Example ZHA036: At 95°F outdoor ambient and a

measured suction pressure of 130psig, the target
liquid temperature is 105.5°F. For a measured liquid
temperature of 106°F, add charge in increments until
measured liquid temperature agrees with the target
liquid temperature.

D - Compressor Controls

See unit wiring diagram to determine which controls are
used in each unit. Optional controls are identified on
wiring diagrams by arrows at junction points.

1- Defrost Switch (S6)

Defrost switch closes to initiate defrost when liquid
line temperature falls to 42

F (5.6

C). Defrost switch

opens when liquid line temperature reaches 70

F

(21

C) to terminate defrost. If the liquid line

temperature does not rise above 70

F (21

C), the

CMC1 will terminate defrost after 14 minutes. The
defrost switch is located on the liquid line between the
outdoor expansion valve and the distributor

2- Defrost Control (CMC1)

Defrost is liquid line temperature initiated and
operates for 14 minutes unless terminated by liquid
line temperature.

When the liquid line temperature drops below 42°F
(5.6

C), the defrost switch closes and signals the

defrost control

 that a defrost cycle is needed. If

the defrost switch is still closed after 90 minutes
(default), a defrost cycle begins and operates for
up to 14 minutes. The defrost switch can terminate
the defrost cycle before the 14 minutes elapses if
liquid line temperature reaches 70

F (21

C)

Electric heat is energized during defrost to maintain
discharge air temperature.

TABLE 4

ZHA036 NORMAL OPERATING PRESSURES

Outdoor Coil Entering Air Temperature

65 

F

75 

F

85 

F

95 

F

105 

F

115 

F

Suct

(psig)

Disc

(psig)

Suct

(psig)

Disc

(psig)

Suct

(psig)

Disc

(psig)

Suct

(psig)

Disc

(psig)

Suct

(psig)

Disc

(psig)

Suct

(psig)

Disc

(psig)

119

235

122

272

124

314

126

359

129

409

132

461

128

241

130

279

132

319

136

364

146

421

140

470

139

245

146

285

151

331

155

377

155

428

159

482

145

248

154

290

163

335

170

384

174

438

179

498

Summary of Contents for ZHA036

Page 1: ...ng and Packing List Page 3 General Page 3 Requirements Page 3 Unit Support Page 4 Duct Connection Page 4 INSTALLATION INSTRUCTIONS ZHA036 3 TON ZHB036 3 TON ZHA048 4 TON ZHB048 4 TON ZHA060 5 TON ZHB0...

Page 2: ...937 ZHA036 046 44 7 8 1140 ZH 060 ZHB036 048 10 7 8 276 25 5 8 651 5 1 8 130 75 7 8 1927 TOP VIEW Base 24 9 16 624 12 1 8 308 5 1 8 130 BOTTOM SUPPLY AIR OPENING BOTTOM RETURN AIR OPENING 17 3 4 451...

Page 3: ...contains both refrigerant and oil Some rubber roofing material may absorb oil causing the rubber to swell Bubbles in the rubber roofing material can cause leaks Protect the roof surface to avoid expo...

Page 4: ...ny form of moisture from entering unit Recommended minimum frame height is 14 356mm 4 Duct must be attached to the roof mounting frame and not to the unit Supply and return plenums must be installed b...

Page 5: ...CONE SEALANT BETWEEN DUCT COVER FLANGE AND UNIT INSULATION NOT TO SCALE 4 Install return air duct on the intake air side of the horizontal economizer See figure 5 5 Horizontal economizer and return ai...

Page 6: ...thermostat where it might be affected by drafts or dead spots behind doors and in corners hot or cold air from ducts radiant heat from sun or appliances concealed pipes and chimneys IMPORTANT Unless f...

Page 7: ...gure 9 Note Static pressure readings can vary if not taken where shown 3 Measure the indoor blower wheel RPM 4 Referring to pages 9 14 use static pressure and RPM readings to determine unit CFM Use op...

Page 8: ...ten four bolts securing motor base to the mounting frame D Check Belt Tension Overtensioning belts shortens belt and bearing life Check belt tension as follows 1 Measure span length X See figure 12 2...

Page 9: ...47 0 56 1287 0 6 1326 0 64 1364 0 68 1402 0 72 1300 1139 0 51 1182 0 55 1224 0 58 1265 0 62 1304 0 66 1342 0 71 1379 0 75 1416 0 79 1400 1160 0 57 1202 0 61 1243 0 65 1283 0 69 1322 0 73 1359 0 78 139...

Page 10: ...5 0 92 1382 0 97 1417 1 02 1452 1 07 1486 1 11 1800 1253 0 85 1292 0 91 1331 0 96 1368 1 01 1404 1 06 1439 1 11 1473 1 16 1506 1 21 1900 1279 0 94 1317 1 00 1355 1 05 1392 1 10 1427 1 16 1461 1 21 149...

Page 11: ...422 1 28 1456 1 34 1489 1 40 1521 1 45 1554 1 50 2200 1341 1 22 1378 1 28 1414 1 34 1448 1 41 1481 1 46 1513 1 52 1546 1 57 1578 1 62 2300 1371 1 34 1407 1 41 1442 1 47 1475 1 54 1507 1 59 1539 1 65 1...

Page 12: ...1231 0 54 1271 0 58 1310 0 62 1347 0 66 1385 0 69 1300 1115 0 50 1161 0 53 1204 0 56 1246 0 60 1286 0 64 1325 0 68 1362 0 72 1399 0 76 1400 1135 0 56 1179 0 59 1222 0 62 1264 0 66 1303 0 70 1341 0 75...

Page 13: ...1335 0 94 1375 0 98 1413 1 02 1449 1 07 1485 1 12 1800 1233 0 91 1276 0 94 1318 0 98 1358 1 02 1397 1 06 1434 1 11 1469 1 16 1504 1 21 1900 1261 0 98 1303 1 02 1343 1 06 1382 1 11 1420 1 16 1455 1 21...

Page 14: ...944 1 15 971 1 22 997 1 28 1022 1 34 1046 1 40 1070 1 46 2200 902 1 13 931 1 19 959 1 24 986 1 31 1012 1 37 1036 1 43 1060 1 50 1084 1 56 2300 920 1 23 948 1 29 975 1 35 1001 1 41 1027 1 47 1051 1 53...

Page 15: ...15 1 5 1 7 ZA03 906 1383 2 ZA06 1262 1634 ZHB060 1 1 1 1 15 1 5 1 7 ZAA01 522 784 ZAA02 632 875 2 ZAA03 798 1105 NOTE Using total air volume and system static pressure requirements determine from blow...

Page 16: ...tional Electric Heat An increased heating demand W2 will energize electric heat Electric heat is also energized during the defrost cycle W1 to maintain discharge air temperature Cooling 1 Set thermost...

Page 17: ...charge Note that suction pressure can change as charge is adjusted 7 Example ZHA036 At 95 F outdoor ambient and a measured suction pressure of 130psig the target liquid temperature is 105 5 F For a m...

Page 18: ...105 F 115 F Suct psig Disc psig Suct psig Disc psig Suct psig Disc psig Suct psig Disc psig Suct psig Disc psig Suct psig Disc psig 119 236 122 274 125 315 128 361 130 410 133 464 126 239 128 278 132...

Page 19: ...100 110 120 130 110 120 130 140 150 160 170 Outdoor Temperature F Suction Pressure psig 105 95 115 85 75 65 180 ZHA048 CHARGING CURVE 70 80 90 100 110 120 130 110 120 130 140 150 160 170 Suction Pres...

Page 20: ...0 110 120 130 110 120 130 140 150 160 170 Outdoor Temperature F Suction Pressure psig 105 95 115 85 75 65 180 ZHB 036 CHARGING CURVE 70 80 90 100 110 120 130 110 120 130 140 150 160 170 Outdoor Temper...

Page 21: ...100 110 120 130 110 120 130 140 150 160 170 Suction Pressure psig 105 95 115 85 75 65 180 Outdoor Temperature F 60 ZHB060 CHARGING CURVE 70 80 90 100 110 120 130 110 120 130 140 150 160 170 Suction P...

Page 22: ...ting The TEST mode may be started any time the unit is in the heating mode and the defrost thermostat is closed or jumpered If the timing jumper is in the TEST position at power up the defrost control...

Page 23: ...psig DO NOT REPLACE COMPRESSOR C Filters Units are equipped with temporary filters which must be replaced prior to building occupation See table 11 for correct filter size Refer to local codes or app...

Page 24: ...rmed slabs On units with two slabs dirt and debris may become trapped between the slabs To clean between slabs carefully separate coil slabs and wash them thoroughly See figure 16 Flush coils with wat...

Reviews: