Lennox XC21-024 Installation Instructions Manual Download Page 11

Page 11

SL18XC1 SERIES

STEP 6 -- INSTALLING INDOOR EXPANSION VALVE 

A.

ATTACH THE SUCTION LINE SENSING BULB IN THE PROPER
ORIENTATION AS ILLUSTRATED TO THE RIGHT USING THE
CLAMP AND SCREWS PROVIDED.

NOTE

 -

 CONFIRM PROPER THERMAL CONTACT BETWEEN

SUCTION LINE AND CHECK EXPANSION BULB BEFORE IN­
SULATING THE SENSING BULB ONCE INSTALLED.

B.

CONNECT THE EQUALIZER LINE
FROM THE EXPANSION VALVE TO
THE EQUALIZER VAPOR PORT ON
THE SUCTION LINE. FINGER
TIGHTEN THE FLARE NUT PLUS
1/8 TURN (7 FT-LBS) AS ILLUS­
TRATED BELOW.

THE EXPANSION VALVE UNIT CAN BE INSTALLED INTERNAL OR
EXTERNAL TO THE INDOOR COIL. IN APPLICATIONS WHERE AN
UNCASED COIL IS BEING INSTALLED IN A FIELD-PROVIDED
PLENUM, INSTALL THE CHECK EXPANSION VALVE IN A MANNER
WHICH PROVIDES ACCESS FOR FIELD SERVICING OF THE
EXPANSION VALVE. REFER TO BELOW ILLUSTRATION FOR
REFERENCE DURING INSTALLATION OF EXPANSION VALVE
UNIT.

TWO PIECE

PATCH PLATE

(UNCASED

COIL ONLY)

VAPOR

LINE

LIQUID LINE

ORIFICE

HOUSING

DISTRIBUTOR

TUBES

LIQUID LINE

MALE EQUALIZER LINE

FITTING (SEE

EQUALIZER LINE

INSTALLATION FOR
FURTHER DETAILS)

SENSING

LINE

EQUALIZER
LINE

EXPANSION

VALVE

TEFLON

®

RING

(Uncased Coil Shown)

SENSING BULB INSULATION IS REQUIRED
IF MOUNTED EXTERNAL TO THE COIL
CASING. SEE SENSING BULB
INSTALLATION FOR BULB POSITIONING.

STUB

END

TEFLON

®

RING

LIQUID LINE

ASSEMBLY WITH

BRASS NUT

DISTRIBUTOR

ASSEMBLY

THIS OUTDOOR UNIT IS DESIGNED FOR USE IN SYSTEMS THAT USE A CHECK EXPANSION VALVE METERING DEVICE. SEE THE

 LENNOX SL18XC1

PRODUCT SPECIFICATION BULLETIN (EHB)

 FOR APPROVED EXPANSION VALVE KIT MATCH-UPS AND APPLICATION INFORMATION.

1. REMOVE THE FIELD-PROVIDED FITTING THAT TEMPORARILY RECON­

NECTED THE LIQUID LINE TO THE INDOOR UNIT'S DISTRIBUTOR ASSEM­
BLY.

2. INSTALL ONE OF THE PROVIDED TEFLON

®

 RINGS AROUND THE

STUBBED END OF THE EXPANSION VALVE AND LIGHTLY LUBRICATE THE
CONNECTOR THREADS AND EXPOSE SURFACE OF THE TEFLON

®

 RING

WITH REFRIGERANT OIL.

3. ATTACH THE STUBBED END OF THE EXPANSION VALVE TO THE LIQUID

LINE ORIFICE HOUSING. FINGER TIGHTEN AND USE AN APPROPRIATE­
LY SIZED WRENCH TO TURN AN ADDITIONAL 1/2 TURN CLOCKWISE AS
ILLUSTRATED IN THE FIGURE ABOVE, OR 20 FT-LB.

4. PLACE THE REMAINING TEFLON

®

 WASHER AROUND THE OTHER END

OF THE EXPANSION VALVE. LIGHTLY LUBRICATE CONNECTOR
THREADS AND EXPOSE SURFACE OF THE TEFLON

®

 RING WITH REFRIG­

ERANT OIL.

5. ATTACH THE LIQUID LINE ASSEMBLY TO THE EXPANSION VALVE. FIN­

GER TIGHTEN AND USE AN APPROPRIATELY SIZED WRENCH TO TURN
AN ADDITIONAL 1/2 TURN CLOCKWISE AS ILLUSTRATED IN THE FIGURE
ABOVE OR 20 FT-LB.

SUCTION LINE

FLARE NUT

COPPER FLARE
SEAL BONNET

MALE BRASS EQUALIZER
LINE FITTING

FLARE SEAL CAP

OR

1

2

3

4

5

6

7

8

9

10

11 12

1/2 TURN

SENSING BULB INSTALLATION

EQUALIZER LINE INSTALLATION

REMOVE AND DISCARD EITHER THE FLARE SEAL CAP OR FLARE
NUT WITH COPPER FLARE SEAL BONNET FROM THE EQUALIZER
LINE PORT ON THE SUCTION LINE AS ILLUSTRATED IN THE FIGURE
TO THE RIGHT.

ON 7/8” AND LARGER LINES,
MOUNT SENSING BULB AT
EITHER THE 4 OR 8 O'CLOCK
POSITION. NEVER MOUNT
THE SENSING BULB ON
BOTTOM OF LINE.

12

ON LINES SMALLER THAN
7/8”, MOUNT SENSING
BULB BETWEEN THE 9 AND
3 O'CLOCK POSITIONS.

12

BULB

VAPOR LINE

NOTE - NEVER MOUNT

THE SENSING BULB ON

BOTTOM OF LINE.

BULB

BULB

BULB

9 O'CLOCK TO

3 O'CLOCK

1

2

3

4

5

6

7

8

9

10

11

12

1/8 TURN

FIGURE 14

Summary of Contents for XC21-024

Page 1: ...RUCTIONS Dave Lennox Signature Collection SL18XC1 System AIR CONDITIONERS 507353 01 7 2018 WARNING Improper installation adjustment alteration service or maintenance can cause property damage personal...

Page 2: ...subject to damage e g being bent or scratched While handling or stowing the panels consider any weather conditions especially wind that may cause panels to be blown around and damaged CAUTION As with...

Page 3: ...e and uneven surfaces Concrete slab use two plastic anchors hole drill 1 4 COIL BASE PAN CORNER POST STABILIZING BRACKET 18 GAUGE METAL 2 WIDTH HEIGHT AS REQUIRED 10 X 1 2 LONG SELF DRILLING SHEET MET...

Page 4: ...erforming any service procedure to neutralize electrostatic charge NOTE For proper voltages select control wires gauge per table below WIRE RUN LENGTH AWG INSULATION TYPE LESS THAN 100 30 METERS 18 TE...

Page 5: ...ontinued Outdoor Control A175 Jumpers and Terminals 55 50 DEGREE TARGET 45 DEGREE TARGET 40 DEGREE TARGET DEFAULT 55 50 45 40 55 50 45 40 55 50 45 40 55 50 45 40 DEGREE TARGET 30 0 30 SECOND DELAY SEC...

Page 6: ...o stage electric heat cut factory installed metal link between W1 and W2 Then connect thermostat wire between the air handler control s W2 and the thermostat s W2 terminal 5 Cut on board link clippabl...

Page 7: ...existing traps Polyol es ter POE oils are used in Lennox units charged with HFC 410A refrigerant Residual mineral oil can act as an insulator preventing proper heat transfer It can also clog the expa...

Page 8: ...line orifice housing LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD CYLINDER CONTAINING CLEAN HCFC 22 TO BE USED FOR FLUSHING Positioned to deliver liquid refrigerant LIQUID LINE SERVICE VALVE INLET DIS...

Page 9: ...ort nitrogen flow will have an exit point NITROGEN HIGH LOW B A C PIPING PANEL REMOVAL PREPARING LINE SET CAP AND CORE REMOVAL Remove piping panel to access service valves Cut ends of the refrigerant...

Page 10: ...ter saturated cloths under the valve body to protect the base paint 4FLOW NITROGEN Flow regulated nitrogen at 1 to 2 psig through the refrigeration gauge set into the valve stem port connection on the...

Page 11: ...SION VALVE KIT MATCH UPS AND APPLICATION INFORMATION 1 REMOVE THE FIELD PROVIDED FITTING THAT TEMPORARILY RECON NECTED THE LIQUID LINE TO THE INDOOR UNIT S DISTRIBUTOR ASSEM BLY 2 INSTALL ONE OF THE P...

Page 12: ...linder of HFC 410A refrigerant to the center port of the manifold gauge set Open the valve on the HFC 410A cylinder vapor only B Open the high pressure side of the manifold to allow HFC 410A into the...

Page 13: ...IGH LOW NITROGEN CONNECT GAUGE SET A B C D LINE SET AND INDOOR COIL NOTE Remove cores from service valves if not already done FIGURE 16 EVACUATE LINE SET AND INDOOR COIL The unit is shipped with a fac...

Page 14: ...rigerant Open the mani fold gauge valve 1 to 2 psig in order to release the vac uum in the line set and indoor unit 9 Perform the following S Close manifold gauge valves S Shut off HFC 410A cylinder S...

Page 15: ...and clean as neces sary 4 Inspect the condition of refrigerant piping and confirm that pipes are not rubbing copper to copper Also check the condition of the insulation on the refrigerant lines Repair...

Page 16: ...Up and Performance Checklist Customer Address Indoor Unit Model Serial Outdoor Unit Model Serial Solar Module Mfg and Model Serial Notes START UP CHECKS Refrigerant Type Rated Load Amps Actual Amps Ra...