INSTALLATION
INSTRUCTION 

VRF SYSTEMS -- Indoor Units
507462-02
10/2015

THIS MANUAL MUST BE LEFT WITH THE OWNER FOR 
FUTURE REFERENCE

Shipping and Packing List 

General

Check the components for shipping damage. If you fi nd any 
damage, immediately contact the last carrier.

Package 1 of 2 contains the following:

1 - Assembled indoor unit with mounting bracket

8 - Mounting bracket securing screws

8 - Plastic screw anchors

1 - Roll tape

1 - Flexible condensate drain pipe

1 - Wall sleeve

1 - Plastic cover for wall sleeve

1 - Resistor

1 - Brass fl are nut

1 - Installation manual

The VWMA wall-mounted indoor units are matched with an 
outdoor heat recovery or heat pump unit to create a VRF 
(variable refrigerant fl ow) system that uses HFC-410A 
refrigerant.

Refer to the Product Specifi cation bulletin (EHB) for the 
proper use of these indoor units with specifi c heat pumps, 
heat recovery units, mode switching devices, branch

pipes, line sets and controls.

These instructions are intended as a general guide and do 
not supersede local or national codes in any way. 

Authorities having jurisdiction should be consulted before 
installation.

WARNING

!

Improper installation, adjustment, alteration, ser vice 
or maintenance can cause property damage, personal 
injury or loss of life.
Installation and service must be performed by a li-
censed professional HVAC installer, service agency 
or the gas supplier.
Failure to follow safety warnings and these instruc-
tions exactly could result in property damage, dan-
gerous operation, serious injury, or death.
Any additions, changes, or conversions required in 
order for the appliance to satisfactorily meet the ap-
plication needs must be made by a licensed profes-
sional HVAC installer (or equivalent) using factory-
specifi ed parts.
Do not use this system if any part has been under 
water. A fl ood-damaged appliance is extremely dan-
gerous. Immediately call a licensed professional 
HVAC service technician (or equivalent) to inspect 
the system and to replace all controls and electrical 
parts that have been wet, or to replace the system, if 
deemed necessary.
The State of California has determined that this 
product may contain or produce a chemical or 
chemicals, in very low doses, which may cause 
serious illness or death. It may also cause cancer, 
birth defects, or reproductive harm.

CAUTION

!

As with any mechanical equipment, personal injury 
can result from contact with sharp sheet metal edges. 
Be careful when you handle this equipment.

VWMA Wall-Mounted Units

These instructions are intended as a general guide and do 
not supersede local codes in any way. Consult authorities 
having jurisdiction before installation.

IMPORTANT!

The Clean Air Act of 1990 bans the intentional 
venting of refrigerant (CFCs, HCFCs and HFCs) 
as of July 1, 1992. Approved methods of recovery, 
recycling or reclaiming must be followed. Fines and/
or incarceration may be levied for noncompliance. 
These units must be installed as a part of a matched 
system as specifi ed in the Product Specifi cations 
(EHB) bulletin.

Not for use with V0CTRL90 Auxiliary Heat Relay. 
See Service and Application Note VRF-15-01.

Summary of Contents for VWMA007S4

Page 1: ...struc tions exactly could result in property damage dan gerous operation serious injury or death Any additions changes or conversions required in order for the appliance to satisfactorily meet the ap...

Page 2: ...15 000 Btuh 018 18 000 Btuh 024 24 000 Btuh 030 30 000 Btuh Voltage P 208 230V 1 phase 60hz Model Number Identification Safety Requirements ELECTRICAL SHOCK FIRE OR EXPLOSION HAZARD Do not touch the u...

Page 3: ...8 733 27 1 4 692 015 018 42 1 4 1073 12 3 8 314 35 1 8 892 33 1 8 841 FRONT VIEW TOP VIEW SIDE VIEW SIDE VIEW 9 229 C A B D 3 1 4 83 4 1 2 114 VWMA007S4 VWMA009S4 VWMA012S4 VWMA015S4 VWMA018S4 FRONT...

Page 4: ...et away from any antenna power cord line radio telephone security system or intercom Electrical interference and radio frequencies from any of these sources may affect operation WARNING Do not install...

Page 5: ...w proper condensate drainage 1 Use a carpenter s level or measuring tape to verify the wall mounting plate is horizontally level 2 Secure the wall mounting plate to the wall using the provided screws...

Page 6: ...r pipes and wiring from the effects of these construction materials by using a sleeve made of a suitable material The integrity of copper pipe and wiring can deteriorate when exposed to these construc...

Page 7: ...Remove the flare nuts from the connections on the unit and discard the seal from each of the piping connections 5 Slide the flare nuts onto the ends of the field provided refrigerant piping before usi...

Page 8: ...om the indoor unit 3 Drain should be as short as possible and should not have any droops or kinks that would restrict condensate flow and shall be approved resistant pipe There must be a 2 inch space...

Page 9: ...r The ground wire for the unit must not be connected to a gas or water pipe a lightning conductor or a telephone ground wire Do not connect power wires to the outdoor unit until all other wiring and p...

Page 10: ...communication wiring FM WHITE WHITE GRAY C TR Y G EEV CN10 WHITE CN15 CN5 CN3 CN24 CN7 CN1 CN21 GM GM CN4 DM HEAT ANION Y G BLUE RED HEAT_L HEAT_N XS2 XP2 CN1 CN2 CN2 T1 WHITE T2B T2 BLACK SW1 SW2 SW...

Page 11: ...communication wiring CS T2B T2 TR FM XS1 7 XP1 7 T1 C KEY XT1 2 EEV COMPONENT GM DM INDOOR FAN ELECTRONIC EXPANSION VALVE INLET AIR TEMP EVAP OUTLET TEMP COOLING MODE COIL TEMP PLUG JACK TRANSFORMER...

Page 12: ...utdoor unit sub2 unit PQE H1 H2 E H1 H2 E H1 H2 E PQE MS Box PQE Ground cable shield DO NOT connect to E PQE MS Box PQE Install a terminating resistor at the last indoor unit terminals P and Q of the...