background image

9

Wiring Connections

WARNING

!

Isolate the power supply before accessing unit 
electrical terminals.
Install unit so that unit disconnect is accessible.
Follow all local and national codes, as well as this 
installation instruction, during installation. Do NOT 
overload electrical circuit, as this may lead to failure 
and possible fi re.
Use specifi ed wiring and cable to make electrical 
connections. Clamp cables securely and make sure 
that connections are tight to avoid strain on wiring. 
Insecure wiring connections may result in equipment 
failure and risk of fi re. 
Wiring must be installed so that all cover plates can 
be securely closed.

In the U.S.A., wiring must conform with current local codes 
and the current National Electric Code (NEC). In Canada, 
wiring must conform with current local codes and the current 
Canadian Electrical Code (CEC). 

Refer to unit nameplate for minimum circuit ampacity and 
maximum overcurrent protection size. 

NOTE - Three-conductor shielded cable must be used for 
the communication wiring. This is necessary to 

ensure 

proper system communication and operation.

CAUTION

!

This unit must be properly grounded and protected 
by a circuit breaker. The ground wire for the unit must 
not be connected to a gas or water pipe, a lightning 
conductor or a telephone ground wire. 
Do not connect power wires to the outdoor unit until 
all other wiring and piping connections have been 
completed.
Install all wiring at least 3 feet away from televisions,  
radios or other electronic devices in order to avoid 
the possibility of interference with the unit operation.
Do not install the unit near a lighting appliance that 
includes a ballast. The ballast may affect remote 
control operation.

1.  Lift indoor unit front panel to access the control box 

over. Remove the screw(s) securing the cover. Remove 
the plate.

2.  Locate the terminal strip in the control box. Connect the 

power wiring (sized per NEC/CEC and local codes) and 
communications cable 

(three-conductor, shielded 

cable).

 Refer to unit nameplate for rated voltage.

3.  If the indoor unit is the fi nal unit in a group that is wired 

in series, install the provided resistor across terminals 
P and Q. 

4.  Remove spacer. Secure bottom of unit to wall mounting 

bracket. Continue with installation of outdoor unit and 
system commissioning.

CONTROL BOX

COVER

POWER WIRING

COMMUNICATIONS

WIRING

Figure 11. Accessing Control Box

Network Address and Commissioning

After the system has been installed, each indoor unit must 
be assigned an address as part of the commissioning 
procedure.

Summary of Contents for VWMA007S4

Page 1: ...struc tions exactly could result in property damage dan gerous operation serious injury or death Any additions changes or conversions required in order for the appliance to satisfactorily meet the ap...

Page 2: ...15 000 Btuh 018 18 000 Btuh 024 24 000 Btuh 030 30 000 Btuh Voltage P 208 230V 1 phase 60hz Model Number Identification Safety Requirements ELECTRICAL SHOCK FIRE OR EXPLOSION HAZARD Do not touch the u...

Page 3: ...8 733 27 1 4 692 015 018 42 1 4 1073 12 3 8 314 35 1 8 892 33 1 8 841 FRONT VIEW TOP VIEW SIDE VIEW SIDE VIEW 9 229 C A B D 3 1 4 83 4 1 2 114 VWMA007S4 VWMA009S4 VWMA012S4 VWMA015S4 VWMA018S4 FRONT...

Page 4: ...et away from any antenna power cord line radio telephone security system or intercom Electrical interference and radio frequencies from any of these sources may affect operation WARNING Do not install...

Page 5: ...w proper condensate drainage 1 Use a carpenter s level or measuring tape to verify the wall mounting plate is horizontally level 2 Secure the wall mounting plate to the wall using the provided screws...

Page 6: ...r pipes and wiring from the effects of these construction materials by using a sleeve made of a suitable material The integrity of copper pipe and wiring can deteriorate when exposed to these construc...

Page 7: ...Remove the flare nuts from the connections on the unit and discard the seal from each of the piping connections 5 Slide the flare nuts onto the ends of the field provided refrigerant piping before usi...

Page 8: ...om the indoor unit 3 Drain should be as short as possible and should not have any droops or kinks that would restrict condensate flow and shall be approved resistant pipe There must be a 2 inch space...

Page 9: ...r The ground wire for the unit must not be connected to a gas or water pipe a lightning conductor or a telephone ground wire Do not connect power wires to the outdoor unit until all other wiring and p...

Page 10: ...communication wiring FM WHITE WHITE GRAY C TR Y G EEV CN10 WHITE CN15 CN5 CN3 CN24 CN7 CN1 CN21 GM GM CN4 DM HEAT ANION Y G BLUE RED HEAT_L HEAT_N XS2 XP2 CN1 CN2 CN2 T1 WHITE T2B T2 BLACK SW1 SW2 SW...

Page 11: ...communication wiring CS T2B T2 TR FM XS1 7 XP1 7 T1 C KEY XT1 2 EEV COMPONENT GM DM INDOOR FAN ELECTRONIC EXPANSION VALVE INLET AIR TEMP EVAP OUTLET TEMP COOLING MODE COIL TEMP PLUG JACK TRANSFORMER...

Page 12: ...utdoor unit sub2 unit PQE H1 H2 E H1 H2 E H1 H2 E PQE MS Box PQE Ground cable shield DO NOT connect to E PQE MS Box PQE Install a terminating resistor at the last indoor unit terminals P and Q of the...

Reviews: