Indoor Unit Placement

AVOID

Do not install the unit in the following locations:
•  Areas exposed to petrochemicals or petrochemical 

products

•  Areas exposed to salt or other corrosive materials or 

caustic gasses

•  Areas exposed to extreme voltage variations (such as 

factories

•  Tightly enclosed areas that may impede service of the 

unit

•  Areas exposed to fossil fuels (such as oil or gas in 

kitchens)

•  Areas exposed to strong electromagnetic forces
•  Areas exposed to acids or alkaline detergents (laundry 

rooms)

DO:

•  Locate the unit so that it is not exposed to direct 

sunlight

• 

Ensure the structural wall, floor, or ceiling can support 

the weight of the unit.

•  Select a location where condensate line will have the 

shortest run to a suitable drain per local codes.

• 

Allow sufficient space around unit for proper operation 

and maintenance

•  Install unit a minimum of 3 feet away from any antenna, 

power cord (line) radio, telephone, security system, or 

intercom. Electrical interference and radio frequencies 

from any of these sources may affect operation

•  Be sure to instruct customers how to properly 

operate the unit (especially maintenance of air filter, 

and operation procedure) by having them carry out 

operations themselves while looking at the manual 

provided with the controller.

 WARNING

Excessive  Weight  Hazard  -  Use  tow  or  more  people 

when moving and installing the unit. Failure to do so can 

result in back or other type of injury.

 WARNING

Danger of explosion. 

Keep flammable materials and vapors, such 

as gasoline, away form air handler. 

Place air handler so that heating elements 

are at least 18 inches (46 cm) above the 

floor for a garage installation. 

Failure to follow these instructions can result 

in death, explosion, or fire.

 

CAUTION

Make  sure  the  blower  motor  support  is  tight  (3-motor 

mount bolts) then check to see if wheel is secured to 

motor shaft before operating unit.

Motor mounting bolt

 IMPORTANT

This unit is approved for installation clearance to 

combustible material as stated on the unit rating plate. 

Accessibility and service clearances must take 

precedence over combustible material clearances.

Excessive condensation may occur if the unit is installed 

in a warm, humid place. When the unit is installed in an 

unconditioned space, apply sealant around 

electrical wires, refrigerant piping and condensate lines 

at the point where they enter the cabinet.
Apply sealant on the inside of the cabinet at the point 

where the electrical wires exit through the conduit 

opening.

Sealing the cabinet in this way prevents warm, moist, 

unconditioned air from entering the cabinet. Warm, 

moist air in the cabinet forms condensate on the cooler 

control box and electrical controls.
The air handler must be installed so that free access is 

allowed to the coil/filter compartment and blower/control 

compartment.

 WARNING

Use  the  provided  and  specified  components  when 

installing equipment. Failure to do so may result in 

unit falling, water leaking or electrical shocks, caus ing 

personal injury or equipment or property dam age.
Check suitability of structure to which the unit support 

mechanism will be fixed to. If structure is not capable 

of carrying the weight of the unit, unit may fall causing 

personal injury or equipment damage.

Consider the possibility of earthquakes in your area 

when installing the equipment. If the unit is not correctly 

secured, it may fall, causing personal injury or equipment 

damage.

Safely dispose of packing materials, which include 

nails, wood and other sharp objects, as well as plastic 

wrapping. Children playing with plastic wrap or bags risk 

the danger of suffocation.

 CAUTION

Do not place items which may be damaged by water 

under or around the indoor unit.

Summary of Contents for VVCB

Page 1: ...h flanges for connecting the supply plenum VRF VRF SYSTEMS Air Handler 507895 02 01 2019 WARNING Improper installation adjustment alteration ser vice or maintenance can cause property damage personal...

Page 2: ...voided Note Only Lennox VRF indoor units will work with Lennox VRF outdoor units and associated mechanical equipment Lennox Mini Split indoor units are similar in appearance but must not be connected...

Page 3: ...8 549 10 1 4 260 SUPPLY AIR 17 7 8 454 SUPPLY AIR 1 1 4 32 SUCTION LINE LIQUID LINE RETURN AIR RETURN AIR RETURN AIR SUPPLY AIR 20 3 4 527 18 1 2 470 19 3 4 502 45 3 4 1162 3 4 19 3 76 13 3 4 349 1 5...

Page 4: ...365 B 22 560 C 19 1 2 495 D 24 610 E 19 1 2 495 F 20 3 8 518 G 22 3 4 578 F A G E LINE VOLTAGE INLETS Top and Either Side LOW VOLTAGE INLETS Top and Either Side 10 1 4 260 SUPPLY AIR 1 1 4 32 SUCTION...

Page 5: ...RTICAL INSTALLATION 39 3 8 39 3 8 39 3 8 7 7 8 7 7 8 7 7 8 NOTE All dimensions shown in inches 1000 mm 1000 mm 200 mm 200 mm 1000 mm 200 mm Model No 012 030 036 060 Cabinet 0 inch 0 mm 0 inch 0 mm To...

Page 6: ...ine Connection Liquid Line Connection Electronic Expansion Valve EEV Strainer Primary Drain Connection Vertical Drain Pan Auxiliary Horizontal Auxiliary Upflow Straps Drip Shield Baffle Drain Connecti...

Page 7: ...blower motor support is tight 3 motor mount bolts then check to see if wheel is secured to motor shaft before operating unit Motor mounting bolt IMPORTANT This unit is approved for installation cleara...

Page 8: ...rty damage injury or death Install the unit in a location that meets the following requirements Allow adequate space for installation service clearance piping and electrical connections and necessary...

Page 9: ...is shown in Figure 5 5 If the unit is suspended the entire length of the cabinet must be supported If you use threaded rod use a piece of angle iron or Unistrut channel attached to the unit either abo...

Page 10: ...rtical Upflow and Horizontal Right Configuration Shown T 1 T 2B T 2 Sensor Description T1 Return Air room Sensor T2 Middle of Coil Sensor T2A Entering Coil inlet Sensor T2B Leaving Coil outlet Sensor...

Page 11: ...r temperature 16 Secure T 1 sensor to top of coil See Figure 10 17 Re secure the wiring harness using clips and wire ties Do not pinch or bind wires 18 Reconnect the T2 and T2B sensors 19 Reconnect th...

Page 12: ...l with any other type of refrigerant oil Refrigerant leaks are unlikely however if a refrigerant leak occurs open a door or windows to dilute the refrigerant in the room Turn off the unit and all othe...

Page 13: ...n pressurization of the low side shell and suction tubing Application of a brazing torch to a pressurized system may result in ignition of the refrigerant and oil mixture Check the high and low pressu...

Page 14: ...ry drain The condensate drain is on the negative pressure side of the blower therefore air being pulled through the condensate line will not allow positive drainage without a proper trap 6 Route the d...

Page 15: ...ect supply air duct to the flange on top of the air handler If an isolation connector is used it must be nonflammable When sizing the return air filter grille a minimum surface area of 200 sq in per t...

Page 16: ...R84 IMPORTANT DO NOT adjust DIP switch settings Settings may only be adjusted by a trained technician as part of the com missioning procedures CAUTION This unit must be properly grounded and protected...

Page 17: ...from the outdoor unit Always follow NEC CEC and Local Codes Outdoor unit main unit L1 L2 L3 Outdoor unit sub1 unit L1 L2 L3 Outdoor unit sub2 unit L1 L2 L3 L2 L3 L1 L2 L1 208 230V 3Ph 60Hz or 460V 3Ph...

Page 18: ...wire polarity sensitive Typical Wiring Diagram NEC CEC and Local Codes apply Outdoor unit Outdoor unit sub1 unit Outdoor unit sub2 unit PQ main unit PQ MS Box PQ PQ MS Box PQ PQ H1 H2 H1 H2 H1 H2 Out...

Page 19: ...eat Pump System Tightening torque for the terminal screws Use the correct screwdriver for fighting the terminal screws If the screwdriver blade is too small the head of the screw might be damaged and...

Page 20: ...XP2 XP3 1 S X 2 S X 3 S X T2 Middle of evaporator Sensor YELLOW GRAY WHITE BLUE RED BLACK CN17 CN30 To wired controller comm bus To outdoor indoor MS units comm bus XT2 HA HB 12V COM Q P To wired cont...

Page 21: ...0 28 8 30 240 5 0 17 100 3 0 29 8 30 7 5 kW V8EH0080P 1P 13P63 208 5 6 19 200 3 0 37 8 4 40 5 220 6 3 21 500 3 0 39 8 4 40 5 230 6 9 23 500 3 0 41 8 45 5 240 7 5 25 600 3 0 42 8 45 5 VVCB024H4 Descri...

Page 22: ...50 3 60 6 220 8 4 28 700 4 2 53 3 60 6 230 9 2 31 400 4 2 55 3 60 6 240 10 0 34 100 4 2 57 3 60 6 VVCB030H4 Description Input Blower Motor Full Load Amps 2 Minimum Circuit Ampacity 3 Maximum Overcurr...

Page 23: ...3 4 40 220 6 3 21 500 4 2 41 3 45 230 6 9 23 500 4 2 42 3 45 240 7 5 25 600 4 2 44 3 45 10 kW V8EH0100P 1P 13P64 208 7 5 25 600 4 2 50 3 60 220 8 4 28 700 4 2 53 3 60 230 9 2 31 400 4 2 55 3 60 240 10...

Page 24: ...2 4 45 220 6 3 21 500 5 7 43 2 45 230 6 9 23 500 5 7 44 2 45 240 7 5 25 600 5 7 46 2 50 10 kW V8EH0100P 1P 13P64 208 7 5 25 600 5 7 52 3 60 220 8 4 28 700 5 7 55 3 60 230 9 2 31 400 5 7 57 3 60 240 10...

Page 25: ...000 6 0 55 6 24 1 60 4 30 79 7 80 6 230 13 8 47 000 6 0 57 6 25 1 60 4 30 82 7 90 6 240 15 0 51 000 6 0 59 6 26 1 60 30 85 7 90 6 20 kW V8EH0200P 1P 13P76 208 15 0 51 200 6 0 52 6 45 1 60 4 50 97 7 10...

Page 26: ...4 112 130 149 169 192 214 235 30 2 5 Ton L 750 54 70 87 103 118 136 157 171 191 M 870 83 103 121 142 159 182 195 217 239 H 1000 119 142 164 185 212 233 257 286 304 36 3 Ton L 900 52 73 92 119 157 184...

Page 27: ...screws remove filter cabinet cover See Figure 19 2 Remove air filter 3 Clean the air filter using vacuum or water For heavy accumulations use soft brush and mild detergent See Figure 20 4 Dry filter c...

Page 28: ...lectrical control box 1 Remove receiver from accessories package 2 Insert the two fixed plastic mounting brackets on the back of the receiver into the two slots inside of the electrical control box an...

Page 29: ...r temperature T1 6 The middle coil temperature T2 7 The coil inlet temperature T2A 8 The coil outlet temperature T2B 9 The actual superheat temperature 10 The actual subcool temperature 11 Error Code...

Page 30: ...er power has been broken and restored at the disconnect switch or circuit breaker call VRF Technical Support 1 844 438 8731 Figure 23 Receiver Display Error Code Description FE No address E0 Mode conf...

Page 31: ...31 Technical Support 1 844 GET VRF1 1 844 438 8731 vrftechsupport lennoxind com www LennoxVRF com Download the app from the Apple App Store or the Google Play store...

Reviews: