background image

13

Brazing Refrigerant Lines

Refrigerant lines must be connected by a qualified 

technician in accordance with established procedures.

1.  The seal on the unit refrigerant piping connections 

should remain in place until the last possible moment. 

This will prevent dust or moisture from getting into the 

refrigerant piping before it is connected.

2.  To avoid damaging the rubber grommets in the 

cabinet while brazing, slide the rubber grommets over 

the refrigerant lines until they are away from the heat 

source.

3.  Remove rubber plug from both liquid and gas lines or 

cut pipework tails to suit field installation conditions

4.  Connect the liquid and gas lines to the evaporator coil.
5.  Place a wet rag against piping plate and around the 

line connections. 

Take care to protect the cabinet 

and internal components.

6. 

Ensure  nitrogen  is  flowing  at  all  times  during  the 

brazing process.

7.  Braze connections. Allow pipe to cool before removing 

wet rag.

8.  Reinstall the rubber grommets into the refrigerant 

piping panel.

9.  Insulate both pipes individually.

Sealing the Unit

Seal the unit so that warm air is not allowed into the 

cabinet. Warm air introduces moisture, which results in 

water blow-off problems.

This is especially important when the unit is installed in an 

unconditioned area.
If installed in an unconditioned space, sealant should be 

applied around the electrical wires, refrigerant tubing, and 

condensate lines where they enter the cabinet.

 WARNING

Danger  of  fire.  Bleeding  the  refrigerant 

charge from only the high side may result 

in pressurization of the low side shell and 

suction tubing. Application of a brazing torch 

to a pressurized system may result in ignition 

of the refrigerant and oil mixture. Check the 

high and low pressures before applying heat.

 CAUTION

Brazing  alloys  and  flux  contain  materials  which  are 

hazardous to your health.
Avoid breathing vapors or fumes from brazing operations. 

Perform operations only in well-ventilated areas.
Wear gloves and protective goggles or face shield to 

protect against burns.
Wash hands with soap and water after handling brazing 

alloys and flux.

 IMPORTANT

Refrigerant lines must be clean, dry, refrigerant-grade 

copper lines. Air handler coils should be installed 

only  with  specified  line  sizes  for  approved  system 

combinations.

Handle  refrigerant  lines  gently  during  the  installation 

process. Sharp bends or kinks in teh lines will cause 

restrictions.

 IMPORTANT

Only use brazing rods/sticks which are suitable/

recommended for air conditioning pipework installations 

- Do Not Use Soft Solder.

 WARNING

There must be an air-tight seal between the bottom of 

the air handler and the return air plenum. Use fiberglass 

sealing strips, caulking, or equivalent sealing method 

between the plenum and the air handler cabinet to 

ensure a tight seal. Return air must not be drawn from a 

room where this air handler or any gas-fueled appliance 

(i.e. water heater) or carbon monoxide-producing device 

(i.e. wood fireplace) is installed.

 CAUTION

Purge low pressure nitrogen [1 to 2 psig (6.0 to 12.8 

kPA)] through the refrigerant piping during brazing. This 

will help to prevent oxidation and the introduction of 

moisture into a system.

To prevent the build-up of high levels of nitrogen when 

purging be sure it is done in a well ventilated area.

Summary of Contents for VVCB

Page 1: ...h flanges for connecting the supply plenum VRF VRF SYSTEMS Air Handler 507895 02 01 2019 WARNING Improper installation adjustment alteration ser vice or maintenance can cause property damage personal...

Page 2: ...voided Note Only Lennox VRF indoor units will work with Lennox VRF outdoor units and associated mechanical equipment Lennox Mini Split indoor units are similar in appearance but must not be connected...

Page 3: ...8 549 10 1 4 260 SUPPLY AIR 17 7 8 454 SUPPLY AIR 1 1 4 32 SUCTION LINE LIQUID LINE RETURN AIR RETURN AIR RETURN AIR SUPPLY AIR 20 3 4 527 18 1 2 470 19 3 4 502 45 3 4 1162 3 4 19 3 76 13 3 4 349 1 5...

Page 4: ...365 B 22 560 C 19 1 2 495 D 24 610 E 19 1 2 495 F 20 3 8 518 G 22 3 4 578 F A G E LINE VOLTAGE INLETS Top and Either Side LOW VOLTAGE INLETS Top and Either Side 10 1 4 260 SUPPLY AIR 1 1 4 32 SUCTION...

Page 5: ...RTICAL INSTALLATION 39 3 8 39 3 8 39 3 8 7 7 8 7 7 8 7 7 8 NOTE All dimensions shown in inches 1000 mm 1000 mm 200 mm 200 mm 1000 mm 200 mm Model No 012 030 036 060 Cabinet 0 inch 0 mm 0 inch 0 mm To...

Page 6: ...ine Connection Liquid Line Connection Electronic Expansion Valve EEV Strainer Primary Drain Connection Vertical Drain Pan Auxiliary Horizontal Auxiliary Upflow Straps Drip Shield Baffle Drain Connecti...

Page 7: ...blower motor support is tight 3 motor mount bolts then check to see if wheel is secured to motor shaft before operating unit Motor mounting bolt IMPORTANT This unit is approved for installation cleara...

Page 8: ...rty damage injury or death Install the unit in a location that meets the following requirements Allow adequate space for installation service clearance piping and electrical connections and necessary...

Page 9: ...is shown in Figure 5 5 If the unit is suspended the entire length of the cabinet must be supported If you use threaded rod use a piece of angle iron or Unistrut channel attached to the unit either abo...

Page 10: ...rtical Upflow and Horizontal Right Configuration Shown T 1 T 2B T 2 Sensor Description T1 Return Air room Sensor T2 Middle of Coil Sensor T2A Entering Coil inlet Sensor T2B Leaving Coil outlet Sensor...

Page 11: ...r temperature 16 Secure T 1 sensor to top of coil See Figure 10 17 Re secure the wiring harness using clips and wire ties Do not pinch or bind wires 18 Reconnect the T2 and T2B sensors 19 Reconnect th...

Page 12: ...l with any other type of refrigerant oil Refrigerant leaks are unlikely however if a refrigerant leak occurs open a door or windows to dilute the refrigerant in the room Turn off the unit and all othe...

Page 13: ...n pressurization of the low side shell and suction tubing Application of a brazing torch to a pressurized system may result in ignition of the refrigerant and oil mixture Check the high and low pressu...

Page 14: ...ry drain The condensate drain is on the negative pressure side of the blower therefore air being pulled through the condensate line will not allow positive drainage without a proper trap 6 Route the d...

Page 15: ...ect supply air duct to the flange on top of the air handler If an isolation connector is used it must be nonflammable When sizing the return air filter grille a minimum surface area of 200 sq in per t...

Page 16: ...R84 IMPORTANT DO NOT adjust DIP switch settings Settings may only be adjusted by a trained technician as part of the com missioning procedures CAUTION This unit must be properly grounded and protected...

Page 17: ...from the outdoor unit Always follow NEC CEC and Local Codes Outdoor unit main unit L1 L2 L3 Outdoor unit sub1 unit L1 L2 L3 Outdoor unit sub2 unit L1 L2 L3 L2 L3 L1 L2 L1 208 230V 3Ph 60Hz or 460V 3Ph...

Page 18: ...wire polarity sensitive Typical Wiring Diagram NEC CEC and Local Codes apply Outdoor unit Outdoor unit sub1 unit Outdoor unit sub2 unit PQ main unit PQ MS Box PQ PQ MS Box PQ PQ H1 H2 H1 H2 H1 H2 Out...

Page 19: ...eat Pump System Tightening torque for the terminal screws Use the correct screwdriver for fighting the terminal screws If the screwdriver blade is too small the head of the screw might be damaged and...

Page 20: ...XP2 XP3 1 S X 2 S X 3 S X T2 Middle of evaporator Sensor YELLOW GRAY WHITE BLUE RED BLACK CN17 CN30 To wired controller comm bus To outdoor indoor MS units comm bus XT2 HA HB 12V COM Q P To wired cont...

Page 21: ...0 28 8 30 240 5 0 17 100 3 0 29 8 30 7 5 kW V8EH0080P 1P 13P63 208 5 6 19 200 3 0 37 8 4 40 5 220 6 3 21 500 3 0 39 8 4 40 5 230 6 9 23 500 3 0 41 8 45 5 240 7 5 25 600 3 0 42 8 45 5 VVCB024H4 Descri...

Page 22: ...50 3 60 6 220 8 4 28 700 4 2 53 3 60 6 230 9 2 31 400 4 2 55 3 60 6 240 10 0 34 100 4 2 57 3 60 6 VVCB030H4 Description Input Blower Motor Full Load Amps 2 Minimum Circuit Ampacity 3 Maximum Overcurr...

Page 23: ...3 4 40 220 6 3 21 500 4 2 41 3 45 230 6 9 23 500 4 2 42 3 45 240 7 5 25 600 4 2 44 3 45 10 kW V8EH0100P 1P 13P64 208 7 5 25 600 4 2 50 3 60 220 8 4 28 700 4 2 53 3 60 230 9 2 31 400 4 2 55 3 60 240 10...

Page 24: ...2 4 45 220 6 3 21 500 5 7 43 2 45 230 6 9 23 500 5 7 44 2 45 240 7 5 25 600 5 7 46 2 50 10 kW V8EH0100P 1P 13P64 208 7 5 25 600 5 7 52 3 60 220 8 4 28 700 5 7 55 3 60 230 9 2 31 400 5 7 57 3 60 240 10...

Page 25: ...000 6 0 55 6 24 1 60 4 30 79 7 80 6 230 13 8 47 000 6 0 57 6 25 1 60 4 30 82 7 90 6 240 15 0 51 000 6 0 59 6 26 1 60 30 85 7 90 6 20 kW V8EH0200P 1P 13P76 208 15 0 51 200 6 0 52 6 45 1 60 4 50 97 7 10...

Page 26: ...4 112 130 149 169 192 214 235 30 2 5 Ton L 750 54 70 87 103 118 136 157 171 191 M 870 83 103 121 142 159 182 195 217 239 H 1000 119 142 164 185 212 233 257 286 304 36 3 Ton L 900 52 73 92 119 157 184...

Page 27: ...screws remove filter cabinet cover See Figure 19 2 Remove air filter 3 Clean the air filter using vacuum or water For heavy accumulations use soft brush and mild detergent See Figure 20 4 Dry filter c...

Page 28: ...lectrical control box 1 Remove receiver from accessories package 2 Insert the two fixed plastic mounting brackets on the back of the receiver into the two slots inside of the electrical control box an...

Page 29: ...r temperature T1 6 The middle coil temperature T2 7 The coil inlet temperature T2A 8 The coil outlet temperature T2B 9 The actual superheat temperature 10 The actual subcool temperature 11 Error Code...

Page 30: ...er power has been broken and restored at the disconnect switch or circuit breaker call VRF Technical Support 1 844 438 8731 Figure 23 Receiver Display Error Code Description FE No address E0 Mode conf...

Page 31: ...31 Technical Support 1 844 GET VRF1 1 844 438 8731 vrftechsupport lennoxind com www LennoxVRF com Download the app from the Apple App Store or the Google Play store...

Reviews: