background image

7

Unit Installation Instructions

1.  Make sure that the structural ceiling or slab is able 

to support the weight of the indoor unit. It may be 

necessary to add extra support. 

2.  Install suspension rods in the structural 

ceiling or concrete slab in a suitable location. 

 

If  the  structural  ceiling  is  constructed  of  concrete, 

install  anchors  to  accept  four  ⅜”  threaded  rods  to 

suspend the indoor unit. If the structural ceiling 

includes  wooden  joists,  use  angle  iron  or  Unistrut 

channel  fixed  securely  in  place  to  accept  the  ⅜” 

threaded rods. 

NOTE - 

Threaded rod (requirement 

of Lennox warranty program) is the ONLY acceptable 

method of suspending the unit; do not use chains or 

straps.  

See Figure 2.

3.  Slide one nut and one washer onto each threaded rod. 

Use electrical tape to keep the washer from failing off. 

Position the nuts slightly above the final resting place 

of the four suspension brackets. See Figure 3.

Figure 2. Suspending Methods

ANGLE IRON

BOLTED IN

PLACE ACROSS

WOODEN JOISTS

WOODEN JOIST

⅜”  THREADE

D

ROD

ANGLE IRON

ACROSS

WOODEN JOISTS

ANCHOR

CONCRETE CEILING

USING ANCHORS

⅜”  THREADE

D

ROD

4. 

Use either a mechanical lifting device or a minimum 

of two people to raise the unit and insert the threaded 

rods into the suspension brackets on the cassette 

base. Slide a washer and then a nut onto each rod 

below each suspension bracket. Use the leveling nut 

(beneath suspension bracket) to adjust the unit to the 

correct height. Remove the electrical tape holding the 

upper washers and nuts in place and tighten each 

of the four nuts above the brackets down onto the 

brackets. This will ensure that the unit remains level.

5. 

It is recommended to install a field-provided isolation 

grommet as shown in Figure 4 to prevent transmission 

of vibration from unit to structural ceiling.

INDOOR UNIT

LEVELING

NUT

” THREADED

ROD

SUSPENSION

BRACKET

SUPPLY AIR

OPENING

FRONT VIEW

When unit is

level, tighten

nut to secure

position of

suspension

bracket on

rod.

Figure 3. Suspension Hardware

Figure 4. Isolation Grommet

LEVELING

NUT

” THREADED

ROD

SUSPENSION

BRACKET

FIELD-PROVIDED

ISOLATION GROMMET

WASHER

6.  If the unit is being installed in an application that includes 

a sheet rock (plasterboard) ceiling, it is required that 

an access panel be installed in a suitable location. 

This will also allow access for future maintenance 

(requirement  of  Lennox  warranty  program).

 

Access is required during the commissioning process 

to test the condensate disposal system (See Figure 

20) and to check the local disconnect.

7. 

The unit is factory-configured for the supply air to be 

delivered from the front and the return air filter at the 

rear  of  the  unit. The  return  air  filter  location  can  be 

relocated in the field for bottom return air filter access, 

if more convenient. See Figure 10.

Summary of Contents for VRF VMDB Series

Page 1: ...sed professional HVAC installer service agency or the gas supplier Failure to follow safety warnings and these instruc tions exactly could result in property damage dan gerous operation serious injury...

Page 2: ...ce a fuse with a fuse of a different rating Do not use a jumper wire to replace a fuse Do not insert your hands tools or any other item into the air intake or air outlet at either the indoor or outdoo...

Page 3: ...UNIT REAR OF UNIT SECTION A A SECTION D D SECTION B B SECTION C C SECTION B B SECTION C C SECTION A A SECTION D D TOP OF UNIT NOTE Unit orientation reversed to show alternative filter location and re...

Page 4: ...2 13 1 25 1 3 4 44 1 7 8 48 CONDENSATE LIFT PUMP Size A B C D E F G H J in mm in mm in mm in mm in mm in mm in mm in mm in mm 012 36 1 4 921 10 5 8 270 25 3 8 645 22 1 2 572 39 3 4 1010 2 5 8 67 28 71...

Page 5: ...in any form Minimum clearances must be observed at all times NOTE Horizontal installation only 20 508 mm Minimum Service Clearance 24 610 mm Air Flow 24 610 mm Minimum Service Clearance TOP VIEW DUCT...

Page 6: ...te support for the weight of the duct system Duct system must not be supported by the indoor unit It is recommended that you use flexible joints canvas at the point where the duct connects to the unit...

Page 7: ...d then a nut onto each rod below each suspension bracket Use the leveling nut beneath suspension bracket to adjust the unit to the correct height Remove the electrical tape holding the upper washers a...

Page 8: ...es the filter retaining bracket and slide the bracket away from the unit 3 Grasp the filter removal tab and slide the filter out Figure 7 Loosen Filter Retaining Bracket Filter removal tab Figure 8 Sl...

Page 9: ...pplied foam insulating tape to the return air opening on the bottom of the unit See Figure 11 Figure 11 Apply Foam Insulating Tape Field supplied foam insulating tape 5 Use the existing screws to re i...

Page 10: ...PORTANT Support ALL piping within 12 in 305 mm of any mechanical fitting such as a flared connection WARNING Danger of fire Bleeding the refrigerant charge from only the high side may result in pressu...

Page 11: ...on conditions 4 All refrigerant piping shall be free of defects debris and oil 5 Connect the liquid and gas lines to the evaporator coil 6 Always use an appropriate heat absorption compound to protect...

Page 12: ...rnal drain pump Suspension Rods Drain line Structural Ceiling 3 ft 1 m Support straps NOTE Drain line should be sloped 1 4 inch per foot 18 mm per m AWAY from unit and should be supported as needed to...

Page 13: ...system in the cooling mode If the internal pump is being used ensure that the pump is operating and the water in the pan is draining freely If the internal pump is not being used pour the water into t...

Page 14: ...ions Clamp cables securely and make sure that connections are tight to avoid strain on wiring Insecure wiring connections may result in equipment failure and risk of fire Wiring must be installed so t...

Page 15: ...gure 21 Typical Power Wiring Diagram VRF Heat Recovery System Shown L2 L3 L1 L2 L1 208 230V 3Ph 60Hz or 460V 3Ph 60Hz Power supply 208 230V 1Ph 60Hz Power supply Mode Selection Box Indoor unit Indoor...

Page 16: ...PQ PQ H1 H2 H1 H2 H1 H2 Outdoor Unit Communication Terminal Block P Q H1 H2 X Y O A K1 K2 MS Box Communication Terminal Block P Q Indoor Unit Communication Terminal Block HA HB 12V COM P Q Ground drai...

Page 17: ...ler Signal transmission wire X2M 0 58 0 72 Terminal base of power supply X1M 0 87 1 06 Grounding terminal M4 1 06 1 43 PQ PQ Outdoor unit mainunit Outdoor unit sub1unit Outdoor unit sub2 unit Install...

Page 18: ...E F8 No address Outdoor unit fault Water level alarm Emergency stop Remote OFF E6 DC fan motor error E7 EEPROM failure error 5V GND 12V ONLY USED FOR TESTING CN30 RED BLACK HA HB 12V COM Q P Magnet Ri...

Page 19: ...6 Locate the return air thermistor to the conditioned area of which the indoor unit serves Figure 29 Sensor Thermistor Relocate the unit return air sensing from inside the unit to a location within th...

Page 20: ...K WHITE RED XS4 XS3 XS2 XS1 XS6 XP7 XS7 CN12 NOTE 1 Refer to manual for communication wiring 2 Please use the 2 conductor shielded twisted cable for communication NOTE Component in dash line is option...

Page 21: ...l indoor temperature T1 6 The middle coil temperature T2 7 The coil inlet temperature T2A 8 The coil outlet temperature T2B 9 The actual superheat temperature 10 The actual subcool temperature 11 Erro...

Page 22: ...it Fault EE High Water Alarm A0 Emergency stop D8 Remote off U4 MS self inspection error F8 MS error Table 8 Fault Code Display on Controller Error Code Description F0 Communication Address error betw...

Page 23: ...23...

Page 24: ...m Reference and adhere to the latest revision of the installation instructions Installation instructions can be downloaded from www lennoxvrf com www lennoxcommercial com www lennoxpros com and the Le...

Reviews: