background image

Page 8

506083−01 03/08

2

3

4

5

6

OUTDOOR

UNIT

LIQUID LINE

SUCTION LINE

SERVICE

VALVE

SERVICE

VALVE

CUT AND DEBUR

ATTACH

GAUGES

WRAP

SERVICE

VALVE

FLOW NITROGEN

NITROGEN

BRAZE LINE SET

 

1

INSTALL CORE ONLY FOR

BOTH SERVICE PORTS AFTER

THEY HAVE COOLED.

7

INDOOR UNIT

REMOVE CAP AND CORE FROM

BOTH LIQUID AND SUCTION

SERVICE PORTS

SERVICE PORT MUST BE

OPEN TO ALLOW EXIT
POINT FOR NITROGEN

Figure 14. Brazing Connections

5. Flow regulated nitrogen (at 1 to 2 psig) through the

refrigeration gauge set into the valve stem port
connection on the liquid line service valve and out of
the valve stem port connection on the suction service
valve.

NOTE − The RFCIV or TXV metering device at the indoor
unit will allow low pressure nitrogen to flow through the
system.)

NOTE − Use silver alloy brazing rods with five or six percent
minimum silver alloy for copper−to−copper brazing or 45
percent silver alloy for copper−to−brass or copper−to−steel
brazing.

6. Braze the liquid line to the liquid line service valve.

Turn off nitrogen flow. Repeat procedure starting at
paragraph 4 for brazing the suction line to service
valve.

7. After all connections have been brazed, disconnect

manifold gauge set from service ports, cool down
piping with wet rag and remove all wrappings. Do not
reinstall cores until after evacuation procedure.
Reinstall service caps if desired to close off refrigerant
ports.

Removing Indoor Unit Metering Device

Remove the existing HCFC−22 fixed orifice or thermal
expansion valve from the indoor coil. The existing indoor
unit HCFC−22 metering device is not approved for use with
HFC−410A refrigerant and may prevent proper flushing.

REPLACEMENT PARTS

If replacement parts are necessary for the indoor unit,
order kit 69J46. The kit includes the following:

TEFLON RINGS (20)

BRASS NUTS (10)

LIQUID LINE ASSEMBLIES

(INCLUDES STRAINER) (10)

LIQUID LINE ORIFICE HOUSINGS (10)

LIQUID LINE

ASSEMBLY

COPPER
TUBE

PISTON
RETAINER

STRAINER

Figure 15. 69J46 Kit Components

TYPICAL FIXED ORIFICE REMOVAL PROCEDURE

1. On fully cased coils, remove the coil access and

plumbing panels.

2. Remove any shipping clamps holding the liquid line

and distributor assembly.

3. Using two wrenches, disconnect liquid line from liquid

line orifice housing. Take care not to twist or damage
distributor tubes during this process.

4. Remove and discard Teflon ring, orifice, and valve

stem assembly if present as illustrated in figure 16.

5. Use a field−provided fitting to temporary reconnect the

liquid line to the indoor unit’s liquid line orifice housing.

Summary of Contents for TSA036H4N41

Page 1: ...41 TSA048H4N41 and TSA060H4N41 AIR CONDITIONER 506083 01 03 08 Table of Contents Shipping and Packing List 1 TSA H4 Air Conditioners 1 Unit Dimensions 2 General Information 2 Recovering Refrigerant fr...

Page 2: ...ble 1 shows torque values for fasteners Table 1 Torque Requirements Parts Recommended Torque Service valve cap 8 ft lb 11 NM Sheet metal screws 16 in lb 2 NM Machine screws 10 28 in lb 3 NM Compressor...

Page 3: ...nd use an appropriately sized wrench to turn an additional 1 6 turn clockwise as illustrated in figure 2 To Open and Close Angle Type Service Valve A valve stem cap protects the valve stem from contam...

Page 4: ...as follows With Torque Wrench Finger tighten and then tighten per table 1 Without Torque Wrench Finger tighten and use an appropriately sized wrench to turn an additional 1 12 turn clockwise as illus...

Page 5: ...CONSIDERATIONS Consider the following when positioning the unit Some localities are adopting sound ordinances based on the unit s sound level registered from the adjacent property not from the install...

Page 6: ...ne that ran from condenser to evaporator coil Refrigerant was metered into the evaporator by utilizing temperature pressure evaporation effects on refrigerant in the small RFC line The length and bore...

Page 7: ...caps or service valve stub caps until you are ready to make connections WARNING Danger of fire Bleeding the refrigerant charge from only the high side may result in the low side shell and suction tubi...

Page 8: ...nnect manifold gauge set from service ports cool down piping with wet rag and remove all wrappings Do not reinstall cores until after evacuation procedure Reinstall service caps if desired to close of...

Page 9: ...ushing Existing System IMPORTANT The line set and indoor unit coil must be flushed with at least the same amount of clean refrigerant that previously charged the system Check the charge in the flushin...

Page 10: ...gerant to flow into the system through the suction line valve Allow the refrigerant to pass from the cylinder and through the line set and the indoor unit coil before it enters the recovery machine 4...

Page 11: ...aining Teflon washer around the other end of the TXV Lightly lubricate connector threads and expose surface of the Teflon ring with refrigerant oil 5 Attach the liquid line assembly to the TXV Finger...

Page 12: ...or unit 6 After a few minutes open a refrigerant port to ensure the refrigerant you added is adequate to be detected NOTE Amounts of refrigerant will vary with line lengths 7 Check all joints for leak...

Page 13: ...to break the vacuum and install a new filter drier in the system 4 Evacuate the system again Then weigh the appropriate amount of HFC 410A refrigerant as listed on unit nameplate into the system 5 Mo...

Page 14: ...e only with copper conductors NOTE A complete unit wiring diagram is located inside the unit control box cover NOTE See unit wiring diagram for power supply connections If indoor unit is not equipped...

Page 15: ...ine service port INDOOR COIL AIRFLOW CHECK Check indoor coil airflow using the Delta T DT process as illustration in figure 27 DETERMINING CHARGE METHOD To determine the correct charging method use th...

Page 16: ...utdoor ambient temperature 64 F and BELOW 1 Check Liquid and suction line pressures 2 Compare unit pressures with Table 27 Normal Operating Pressures 3 Conduct leak check evacuate as previously outlin...

Page 17: ...erant If refrigerant is added or removed verify charge using the Approach Method 64 F and BELOW 65 F and ABOVE ABOVE or BELOW F C 036 042 048 060 65 18 13 7 2 10 5 6 8 4 4 8 4 4 75 24 9 5 0 7 3 9 8 4...

Page 18: ...7 190 9 83 246 5 98 308 2 114 385 4 129 469 5 145 572 8 37 111 4 53 150 1 68 194 1 84 250 3 99 312 7 115 390 7 130 475 6 146 579 8 38 113 6 54 152 8 69 197 3 85 254 1 100 317 2 116 396 0 131 481 6 147...

Page 19: ...ineering Handbook for optional accessories that may apply to this unit The following may or may not apply Timed Off Control Sound Cover Suction Line Drier Stand Off Kit Low Ambient Kit Homeowner Infor...

Page 20: ...vides temporary heat supplied by the auxiliary heat Indicating Light Most heat pump thermostats have an amber light which indicates when the heat pump is operating in the emergency heat mode Temperatu...

Reviews: