background image

Page 15

TSA*H4 SERIES

Start−Up and Charging Procedures

IMPORTANT

If unit is equipped with a crankcase heater, it should
be energized 24 hours before unit start−up to
prevent compressor damage as a result of slugging.

1. Rotate fan to check for binding.

2. Inspect all factory− and field−installed wiring for loose

connections.

3. After evacuation is complete, open both the liquid and

suction line service valves to release the refrigerant
charge contained in the outdoor unit into the system.

4. Replace the stem caps and tighten to the value listed

in table 1.

5. Check voltage supply at the disconnect switch. The

voltage must be within the range listed on the unit’s
nameplate. If not, do not start the equipment until you
have consulted with the power company and the
voltage condition has been corrected.

6. Set the thermostat for a cooling demand. Turn on

power to the indoor indoor unit and close the outdoor
unit disconnect switch to start the unit.

7. Recheck voltage while the unit is running. Power must

be within range shown on the nameplate.

8. Check system for sufficient refrigerate by using the

procedures listed under 

Testing and Charging

System

.

SETTING UP TO CHECK CHARGE

1. Close manifold gauge set valves. Connect the center

manifold hose to an upright cylinder of HFC−410A.

2. Connect the manifold gauge set to the unit’s service

ports as illustrated in figure 1.

low pressure gauge to suction line service port.

high pressure gauge to liquid line service port.

INDOOR COIL AIRFLOW CHECK

Check indoor coil airflow using the Delta−T (

D

T)

 process

as illustration in figure 27.

DETERMINING CHARGE METHOD

To determine the correct charging method, use the
illustration in figure 27.

1. Determine the desired 

D

T

Measure entering air temperature

using dry bulb (

A

) and wet bulb (

B

). 

D

T

 is the intersecting value of 

A

and

 B

 in the table (see triangle).

2. Find temperature drop across coil

Measure the coil’s dry bulb

entering and leaving air temperatures (

A

 and 

C

). Temperature Drop

Formula: (

T

Drop

) = 

A

 minus 

C

.

3. Determine if fan needs adjustment

If the difference between

the measured 

T

Drop

 and the desired 

D

T

 

(T

Drop

D

T) 

is 3º, no

adjustment is needed. See examples: Assume 

D

T

 = 15 and 

A

 temp.

= 72º, these 

temperatures would necessitate stated actions:

Cº T

Drop

D

T

=

ºF

ACTION

53º

 19

15

=

4

Increase the airflow

58º

14

15

=

−1

(3º range) no change

62º

10

15

=

−5

Decrease the airflow

4. Adjust the fan speed

See indoor unit instructions to increase/

decrease fan speed.

Changing air flow affects all temperatures; recheck temperatures to
confirm that the temperature drop and 

D

T are 3º.

D

T

80

24 24 24 23 23 22 22 22 20 19 18 17 16 15

78

23 23 23 22 22 21 21 20 19 18 17 16 15 14

76

22 22 22 21 21 20 19 19 18 17 16 15 14 13

74

21 21 21 20 19 19 18 17 16 16 15 14 13 12

72

20 20 19 18 17 17 16 15 15 14 13 12 11 10

70

19 19 18 18 17 17 16 15 15 14 13 12 11 10

57 58 59 60 61 62 63 64 65 66 67 68 69 70

Temp.
of air
entering
indoor
coil ºF

INDOOR
COIL

DRY

BULB

DRY

BULB

WET

BULB

B

T

Drop

19º

A

Dry−bulb

Wet−bulb ºF

A

72º

B

64º

C

53º

air flow

air flow

All temperatures are
expressed in ºF

Figure 27. Checking Indoor Coil Airflow Guide

Summary of Contents for TSA036H4N41

Page 1: ...41 TSA048H4N41 and TSA060H4N41 AIR CONDITIONER 506083 01 03 08 Table of Contents Shipping and Packing List 1 TSA H4 Air Conditioners 1 Unit Dimensions 2 General Information 2 Recovering Refrigerant fr...

Page 2: ...ble 1 shows torque values for fasteners Table 1 Torque Requirements Parts Recommended Torque Service valve cap 8 ft lb 11 NM Sheet metal screws 16 in lb 2 NM Machine screws 10 28 in lb 3 NM Compressor...

Page 3: ...nd use an appropriately sized wrench to turn an additional 1 6 turn clockwise as illustrated in figure 2 To Open and Close Angle Type Service Valve A valve stem cap protects the valve stem from contam...

Page 4: ...as follows With Torque Wrench Finger tighten and then tighten per table 1 Without Torque Wrench Finger tighten and use an appropriately sized wrench to turn an additional 1 12 turn clockwise as illus...

Page 5: ...CONSIDERATIONS Consider the following when positioning the unit Some localities are adopting sound ordinances based on the unit s sound level registered from the adjacent property not from the install...

Page 6: ...ne that ran from condenser to evaporator coil Refrigerant was metered into the evaporator by utilizing temperature pressure evaporation effects on refrigerant in the small RFC line The length and bore...

Page 7: ...caps or service valve stub caps until you are ready to make connections WARNING Danger of fire Bleeding the refrigerant charge from only the high side may result in the low side shell and suction tubi...

Page 8: ...nnect manifold gauge set from service ports cool down piping with wet rag and remove all wrappings Do not reinstall cores until after evacuation procedure Reinstall service caps if desired to close of...

Page 9: ...ushing Existing System IMPORTANT The line set and indoor unit coil must be flushed with at least the same amount of clean refrigerant that previously charged the system Check the charge in the flushin...

Page 10: ...gerant to flow into the system through the suction line valve Allow the refrigerant to pass from the cylinder and through the line set and the indoor unit coil before it enters the recovery machine 4...

Page 11: ...aining Teflon washer around the other end of the TXV Lightly lubricate connector threads and expose surface of the Teflon ring with refrigerant oil 5 Attach the liquid line assembly to the TXV Finger...

Page 12: ...or unit 6 After a few minutes open a refrigerant port to ensure the refrigerant you added is adequate to be detected NOTE Amounts of refrigerant will vary with line lengths 7 Check all joints for leak...

Page 13: ...to break the vacuum and install a new filter drier in the system 4 Evacuate the system again Then weigh the appropriate amount of HFC 410A refrigerant as listed on unit nameplate into the system 5 Mo...

Page 14: ...e only with copper conductors NOTE A complete unit wiring diagram is located inside the unit control box cover NOTE See unit wiring diagram for power supply connections If indoor unit is not equipped...

Page 15: ...ine service port INDOOR COIL AIRFLOW CHECK Check indoor coil airflow using the Delta T DT process as illustration in figure 27 DETERMINING CHARGE METHOD To determine the correct charging method use th...

Page 16: ...utdoor ambient temperature 64 F and BELOW 1 Check Liquid and suction line pressures 2 Compare unit pressures with Table 27 Normal Operating Pressures 3 Conduct leak check evacuate as previously outlin...

Page 17: ...erant If refrigerant is added or removed verify charge using the Approach Method 64 F and BELOW 65 F and ABOVE ABOVE or BELOW F C 036 042 048 060 65 18 13 7 2 10 5 6 8 4 4 8 4 4 75 24 9 5 0 7 3 9 8 4...

Page 18: ...7 190 9 83 246 5 98 308 2 114 385 4 129 469 5 145 572 8 37 111 4 53 150 1 68 194 1 84 250 3 99 312 7 115 390 7 130 475 6 146 579 8 38 113 6 54 152 8 69 197 3 85 254 1 100 317 2 116 396 0 131 481 6 147...

Page 19: ...ineering Handbook for optional accessories that may apply to this unit The following may or may not apply Timed Off Control Sound Cover Suction Line Drier Stand Off Kit Low Ambient Kit Homeowner Infor...

Page 20: ...vides temporary heat supplied by the auxiliary heat Indicating Light Most heat pump thermostats have an amber light which indicates when the heat pump is operating in the emergency heat mode Temperatu...

Reviews: