Page 4
BLOWER DATA
SL280DF090V48B BLOWER PERFORMANCE (less filter)
0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
Settings
First Stage Heating Speed - cfm
Second Stage Heating Speed - cfm
+24%
1360
1500
+18%
1285
1415
+12%
1220
1350
+6%
1135
1285
Factory Default
1075
1200
–6%
1030
1110
–12%
960
1050
–18%
890
975
COOLING
1
Cooling Speed
DIP Switch
Settings
First Stage Cooling Speed - cfm
Second Stage Cooling Speed - cfm
Low
Medium-Low Medium-High
2
High
Low
Medium-Low Medium-High
2
High
+
740
905
1040
1220
1085
1330
1545
1730
Factory Default
690
820
950
1110
990
1200
1400
1,595
–
610
745
855
1005
895
1075
1270
1460
1
Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specific DIP Switch Settings.
2
Factory default setting.
NOTES - The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT.
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is selectable at 28% and 38% of the selected second stage cooling speed - minimum 380 cfm.
Lennox iHarmony
®
Zoning System Applications - Minimum blower speed is 380 cfm.
SL280DF090V48B BLOWER MOTOR WATTS (COOLING)
1
Cooling Speed
DIP Switch
Settings
Motor Watts @ Various External Static Pressures - in. wg.
First Stage
Second Stage
0
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
0
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
+ Setting
Cooling
Speed
Low
33
59
77
98
122
142 166 192 214 97 129 150
188
217 247 267 302 323 365 394
Med-Low 64
91
118
139 167 193 215 246 272 156
188
230 269 313 346 377 429 452 491 529
Med-High 92 119 150 174 209 240 261 292 319
281
304 361 413 455 473 528 552 607 637 673
High
136 174
200
236 264 305 342 376 399 442 470 538 566 603 636 691 730 775 814 838
Factory Default
Cooling
Speed
Low
23
50
63
84 104 124 150 168 194 74 103 126 155 183
210
243 264 290 316 349
Med-Low 45
74
98 114 140 163 192 216 247
120
155 192 223 246 276 314 352 382 412 458
Med-High 62
93
122
143 173 195 232 260 290 206 236 285 324 369 401 437 483 514 551 590
High
112
142 168
202 220
253
282
306 346 323 336 400 445 489 523 558 595 643 660 689
– Setting
Cooling
Speed
Low
17
38
56
72
88
115 132 150 170 51
78 106 129 155 178 207 229 259 289 311
Med-Low 31
54
76
97 117 142 165 187 209 92
122
147 178 217 244 264 289 322 361 385
Med-High 51
76 104 125 153 175
202 222
258 135 177
208
233 272 311 349 386 417 452 491
High
78 107 137 155 184 215 246 268 301 247
282
313 365 398 445 483 521 558 582 620