Page 5
BLOWER DATA
SL280DF090V60C BLOWER PERFORMANCE (less filter)
0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
Settings
First Stage Heating Speed - cfm
Second Stage Heating Speed - cfm
+24%
1540
1695
+18%
1465
1615
+12%
1390
1530
+6%
1320
1450
Factory Default
1245
1365
–6%
1170
1285
–12%
1095
1205
–18%
1020
1120
COOLING
1
Cooling Speed
DIP Switch
Settings
First Stage Cooling Speed - cfm
Second Stage Cooling Speed - cfm
Low
Medium-Low Medium-High
2
High
Low
Medium-Low Medium-High
2
High
+
1125
1250
1400
1590
1585
1770
2000
2275
Factory Default
1020
1135
1285
1445
1420
1610
1845
2,050
–
900
1005
1155
1280
1305
1395
1645
1875
1
Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specific DIP Switch Settings.
2
Factory default setting.
NOTES - The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT.
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is selectable at 28% and 38% of the selected second stage cooling speed - minimum 450 cfm.
Lennox iHarmony
®
Zoning System Applications - Minimum blower speed is 450 cfm.
SL280DF090V60C BLOWER MOTOR WATTS (COOLING)
1
Cooling Speed
DIP Switch
Settings
Motor Watts @ Various External Static Pressures - in. wg.
First Stage
Second Stage
0
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
0
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
+ Setting
Cooling
Speed
Low
81
109 135 154 190 215 243 269 291 197 229 269 314 351 403 424 465 503 542 572
Med-Low 117 142 175 204 227 252 285 308 340 299 329 388 432 466 495 549 586 645 669 705
Med-High 143 183
208
247 283 312 352 385 423 451 501 521 587 633 664 705 765 794 848 879
High
209 246 291 329 370 402 447 490 525 689 720 783 826 890 938 995 1032 1072 1104 1131
Factory Default
Cooling
Speed
Low
63
92 114 139 162 186 216 242 270 144 183 217 248 286 307 354 386 421 459 498
Med-Low
82 111
141 159 195 223 247 274 308
211
245 294 331 369 401 445 486 523 559 604
Med-High
121
148
181 211
241 279 304 331 356 331 366 411 468 497 546 588 629 664 707 748
High
155 194 216 260 296 334 363 393 434 481 535 574 604 655 714 762 816 851 877 942
– Setting
Cooling
Speed
Low
53
76
101 121
139 166 184 209 238 117 149
180
203 235 269 294 327 349 387 421
Med-Low 68
94
120
137 166 193 219 239 266 154 187 219 258 291 319 365 386 424 458 492
Med-High
88
117 144 169 204 227 251
282
313 225 254 298 355 382 427 459 503 542 580 604
High
124 156 183
208
239 267 304 326 359 362 395 436 484 520 568 614 643 686 721 746