Page 60
507964-01
9/2019
START-UP REPORT
Job Name:___________________________________
Store No.___________Start-Up Date:______________
Address:_____________________________________
City:______________________________State:______
Start-Up Contractor:____________________________
Technician:___________________________________
Model No.:___________________________________
Serial No.:____________________________________
RTU No.:________ Catalog No.:__________________
Inspections and Checks
Damage?
Yes
No
R22
j
R410A
j
If yes, reported to:____________________________
Verify factory and field-installed accessories.
Check electrical connections. Tighten if necessary.
Supply voltage: L1-L2______L1-L3_____L2-L3_____
If unit contains a 208-230/240 volt transformer:
Check primary transformer tap
j
Transformer secondary voltage: __________
Cooling Checks
Compressor Rotation
j
Ambient Temp.________Return Air Temp.________ Supply Air Temp.________
Compressor Amps
Compressor Volts
Pressures
Condenser Fan Amps
CC Heater Amps
L1
L2
L3
L1-L2
L1-L3
L2-L3
Disch.
Suct.
L1
L2
L3
L1
1
2
3
4
Blower Checks
Pulley/Belt Alignment
j
Set Screws Tight
j
Blower Rotation
j
Belt Tension
j
Nameplate Amps:_________ Volts:_______________
Motor
Amps
L1_________
L2_________
L3_________
Volts
L1-L2_____________
L1-L3_____________
L2-L3_____________
Heating Checks - Gas
Fuel type: Nat.
j
LP
j
Inlet Pressure:_____in. w.c.
Return Air Temp.:______ Supply Air Temp.:_____
Altitude:____________ Primary Limits Operate:
j
Gas Valve
Manifold Pressure
Low Fire
High Fire
GV1
GV2
Control Type
Heating Checks - Electric
Return Air Temp.:______ Supply Air Temp.:______
Limits Operate:
j
Amps
L1
L2
L3
L1
L2
L3
1
10
2
11
3
12
4
13
5
14
6
15
7
16
8
17
9
18
Accessory Checks
Power Exhaust Amps
1 _____________ 2 ____________ None
j
Economizer Operation
Min. Pos.
j
Motor travel full open/close
j