Page 55
SGH/SCH036, 060, 120, 240
TABLE 34
ECONOMIZER OPERATION - Zone Sensor Mode
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
DEMAND
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
DAMPER POSITION
UNOCC.
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
DAMPER POSITION
OCCUPIED
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
MECHANICAL COOLING
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
OUTDOOR AIR IS
NOT SUITABLE
FOR FREE COOLING
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
OFF
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
CLOSED
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
CLOSED
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
NO
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
G
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
CLOSED
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
MINIMUM
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
NO
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
Cooling Stage 1
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
CLOSED
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
MINIMUM
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
COMPRESSOR 1
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
Cooling Stage 2
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
CLOSED
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
MINIMUM
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
COMPRESSOR 1 & 2
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
Cooling Stage 3
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
CLOSED
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
MINIMUM
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
COMPRESSOR 1, 2, & 3
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
Cooling Stage 4
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
CLOSED
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
MINIMUM
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
COMPRESSOR 1, 2, 3, & 4
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
OUTDOOR AIR IS
SUITABLE
FOR FREE COOLING
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
OFF
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
CLOSED
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
CLOSED
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
NO
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
G
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
CLOSED
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
MINIMUM
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
NO
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
Cooling Stage 1
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
MODULATING
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
MODULATING
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
NO
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
Cooling Stage 2
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
FULL OPEN*
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
FULL OPEN*
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
COMPRESSOR 1
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
Cooling Stage 3
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
FULL OPEN*
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
FULL OPEN*
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
COMPRESSORS 1 & 2
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
Cooling Stage 4
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
FULL OPEN*
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
FULL OPEN*
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
COMPRESSORS 1, 2, 3, & 4
*Damper will modulate to maintain 55
_
F supply air when parameter 164 is changed to setting “0”. Note - Modulating dampers adjust to control supply air
(RT6) to 55
_
F (13
_
C).
Service
To maintain efficiency and longevity, your equipment must
be serviced yearly by a qualified service technician. Failure
to provide proof of service can void warranty.
A-Lubrication
All motor bearings are prelubricated. No further lubrication
is required.
B-Filters
Units are equipped with filters as shown in table 35. Units
will accept 4” filters. Filters should be checked monthly and
replaced when necessary with filters of like kind and size.
Take note of air flow direction marking on filter frame when
reinstalling filters.
NOTE-Filters must be U.L.C. certified or equivalent for use
in Canada.
TABLE 35
Number and Size of Filter By Unit
SG/SC Unit
Qty
Filter Size - inches (mm)
036, 060
4
16 X 20 X 2 (406 X 508 X 51)
120
4
20 X 25 X 2 (508 X 635 X 51)
240
12
20 X 20 X 2 (508 X 508 X 51)
WARNING
Label all wires prior to disconnection
when servicing controls. Wiring errors
can cause improper and dangerous op
eration. Verify proper operation after
servicing.
WARNING
Electric shock hazard and danger of
explosion. Can cause injury, death or
product or property damage. Turn off
gas and electrical power to unit before
performing any maintenance or
servicing operations on the unit. Follow
lighting instructions attached to unit
when putting unit back into operation
and after service or maintenance.
C-Burners (SG Units)
Periodically examine burner flames for proper appearance
during the heating season. Before each heating season
examine the burners for any deposits or blockage which may
have occurred.
1- Turn off both electrical power and gas supply to unit.
2- Open burner compartment access panel.
3- Remove and retain screws securing burner box top cap.
4- Remove and retain two screws securing burners to
burner support and lift the individual burners or the
entire burner assembly from the orifices. See figure 39
for 036 & 060 units and figure 40 for 120, 240 units.
Clean burners as necessary.
5- Locate the ignitor under the right burner for 036 and
060 units. See figure 41. Locate the ignitor under the
left burner for 120 and 240 units. See figure 43 and
table 36. Use appropriately sized twist drills or feeler
gauges to check the spark gap as shown in figure 42.
6- Replace burners and secure with retained screws.
7- Replace access panel.