QUANTUM WATERSIDE FAN COIL SPECIFICATION

2

Casings

The casings shall consist  of durable 1.2mm 
galvanised sheet steel  reinforced where
required to form a rigid structure.

Discharged Plenum

The discharge plenum shall be lined
with class 0  acoustic insulation.  The plenum
shall be provided with spigots for duct 
connection.

Drip Tray

The drip tray shall be manufactured such  that
when the unit is mounted level there shall  be a
positive fall for the condensate water to the
drain connection from all areas of the drip  tray.
There shall be no areas where water can col-
lect in pools. The drip tray shall be 
insulated with 3mm closed cell foam to 
Class 0  specification.

Fans

Double inlet  double width fans shall be used
driven by a motor using cradle type resilient
mountings. The fans impellers shall be at  least
160mm  diameter and of  ‘Tablock’  construction
to ensure good performance and low noise.
Each 
balanced.

impeller shall be statically & dynamically 

Motors

Motors shall be single speed permanent  split
capacitor type. The motors used shall  comply
with BS 5000  Part11  1973  (revised 1989).
Speed control shall be achieved by applying  a
variable voltage to the motor winding. Motors
are to have maintenance free sealed for life
bearings and built  in thermal overload protec -
tion.

Insulation

Dual function thermal and acoustic 
insulation shall be used and shall be to
Class 0  specification.

Heat Exchangers

All heat exchangers shall be tested  at a mini-
mum of 25  bar pressure. The coils shall be
manufactured using solid drawn copper tubes
and aluminium fins.  Each coil shall be fitted
with an air vent.

Filters

Standard filters  shall be of the washable type. 
They shall have a performance classification 
of G2 in accordance with EN779 (EU2) and a
flame resistance to DIN 53438:Class  F1.

Connections

All are to be to BS 2871  Part 1:1971  and suit-
able for brazed or compression fittings.  Coil
connections shall be at 40mm  centres to
enable easy fitment  of standard water control
valves.

Controls

All units  shall be fitted  with illuminated ON/Off
switch, three speed selector switch and include
+5v /  +10v  trimmer switches to aid 
commissioning and be complete with 24  Volt
AC transformer output to drive controllers and
actuators.

Packaging

Units shall be supplied with suitable packaging
to prevent damage and dust contamination.
Units shall be clearly marked with the model
identification  and site  reference and supplied
with installation  instructions.

Certification

Units  shall be supplied with a CE label desig-
nating that  they comply with CE requirements
for safety.

Summary of Contents for Quantum Waterside LQWFC 150

Page 1: ......

Page 2: ...ns 4 Controls 4 Fan Speed Settings 5 Periodic Maintenance 6 Fancoil Maintenance 7 Coil Water Content 8 Weights 8 Minimum No Spigots 8 Coil Connections 8 Wiring Diagram 9 Fault Finding 10 Spares List 1...

Page 3: ...s are to have maintenance free sealed for life bearings and built in thermal overload protec tion Insulation Dual function thermal and acoustic insulation shall be used and shall be to Class 0 specifi...

Page 4: ...el PIPEWORK CONNECTIONS 1 Water flow and return connection Plain pipe connection tails are all to BS 2871 Part 1 1971 and are suitable for brazed or compression fittings Connection sizes are 15mm or 2...

Page 5: ...acitor type and have a capacitor fixed to the outside of the motor All motors have thermal overload protection as standard Access to the fan tray is via removable panels on the bottom face of the unit...

Page 6: ...ign speed EL 120 150 I 0 1 130 L 120 150 II 0 1 145 ML 135 165 II 0 1 160 M 150 180 II 0 1 175 H 165 195 III 0 0 195 Main tapping Fan speed switches Output Volts 150 W Y R 5 V 10 V design speed EL 120...

Page 7: ...ace if necessary Ensureallelectricalconnectionsaresecure Check functions of controls according to operating procedures 6 Fan Motor and Fan A regular check on the fan motor assembly is advisable to asc...

Page 8: ...ECK ACTUATOR EXAMINE VALVES ACTUATORS EXAMINE WATER FLOW TEMPERATURE CHECK CONTROLLER CHECK MOTOR CAPACITOR ADD LINK BETWEEN TERM 8 9 IF FCU WORKS CONTROL LER IS FAULTY CONTACT SPARES DEPT CONTACT SPA...

Page 9: ...0 61 0 74 262 1 16 1 40 244 1 04 1 26 220 0 97 1 17 197 0 87 1 05 155 0 67 0 81 FAN MODEL SPEED Volts H 200 LQWFC M 170 150 ML 150 L 130 EL 120 H 170 LQWFC M 150 190 ML 140 L 130 EL 120 H 200 LQWFC M...

Page 10: ...R LENN X 9 WIRING DIAGRAM...

Page 11: ...R EMENT CALIBRATED CORRECTION FACTOR CHECK SOURCE OF CONTROLLER EXAMINE SWITCH WIRING CRIMP CONNECTIONS CONTINUITY TEST WIRES 24V AND MAINS OUTPUT OK BUT NEW FANCOIL FAULT FINDING CHECK QUANTITY LOCAT...

Page 12: ...igh Temp 9 14 deg C Flow X Z303793 Cooling Coil 4 row High Temp 9 14 deg C Flow X Z303834 Cooling Coil 4 row High Temp 9 14 deg C Flow X Z303878 Cooling Coil 4 row High Temp 9 14 deg C Flow X Z301771...

Page 13: ......

Reviews: