background image

Page 9

Equipment in Confined Space

All Air From Outside

OUTLET AIR

INLET AIR

CHIMNEY OR OIL VENT

Figure 12

NOTE − Each air duct opening shall have a free area of at least
one square inch (6.4 square centimeters) per 2,000 Btu (586 W)
per hour of the total input rating of all equipment in the enclosure. If
the equipment room is located against an outside wall and the air
openings communicate directly with the outdoors, each opening
shall have a free area of at least one square inch (6.4 square
centimeters) per 4,000 Btu (1172 W) per hour of the total input
rating of all other equipment in the enclosure.

WATER
HEATER

OIL
FURNACE

When ducts are used, they shall be of the same cross−sec-
tional area as the free area of the openings to which they
connect. The minimum dimension of rectangular air ducts
shall be no less than 3" (76 mm). In calculating free area,
the blocking effect of louvers, grilles, or screens must be
considered. If the design and free area of protective cover-
ing is not known for calculating the size opening required, it
may be assumed that wood louvers will have 20 to 25%
free area and metal louvers and grilles will have 60 to 75%
free area. Louvers and grilles must be fixed in the open
position or interlocked with the equipment so that they are
opened automatically during equipment operation.

Direct Connection of Outdoor Air for Combus-
tion

The Beckett AFII burner was designed to allow for direct air
intake piping (4" [102 mm]). The maximum equivalent
length of pipe is 70 feet (21.3 m). A 90

_

 elbow equals 6feet

(1.8 m). The enclosed intake pipe ring may be used to facil-
itate direct air intake to the burner through the right side of
the cabinet.

To convert the AFII burner from confined space to outside
combustion air, simply remove the three screws attaching
the inlet air scoop to the burner and insert 4" (102 mm) di-
rect air intake piping.

The use of a barometric relief placed in the intake pipe is
recommended when outdoor combustion air is directly
connected to the burner. This will allow confined space air
to be used as combustion air in the event that the opening
to the outdoor air becomes blocked. Using a barometric re-
lief in the intake will reduce the chance of sooting.

CAUTION

DO NOT USE a barometric draft relief in exhaust
vent pipe if outdoor combustion air is connected di-
rectly to the burner. 

Removal of Unit from Common Venting System

In the event that an existing furnace is removed from a
venting system commonly run with separate appliances,
the venting system is likely to be too large to properly vent
the remaining attached appliances. The following test
should be conducted while each appliance is in operation
and the other appliances not in operation remain con-
nected to the common venting system. If venting system
has been installed improperly, the system must be cor-
rected as outlined in the previous section.

1. Seal any unused openings in the common venting sys-

tem.

2. Visually inspect venting system for proper size and

horizontal pitch and determine there is no blockage or
restriction, leakage, corrosion or other deficiencies
which could cause an unsafe condition.

3. Insofar as is practical, close all building doors and win-

dows and all doors between the space in which the ap-
pliances remaining connected to the common venting
system are located and other spaces of the building.
Turn on clothes dryers and any appliances not con-
nected to the common venting system. Turn on any
exhaust fans, such as range hoods and bathroom ex-
hausts, so they will operate at maximum speed. Do not
operate a summer exhaust fan. Close fireplace damp-
ers.

4. Following the lighting instruction on the unit, place the

appliance being inspected in operation. Adjust ther-
mostat so appliance will operate continuously.

5. Test for spillage using a draft gauge.
6. After it has been determined that each appliance re-

maining connected to the common venting system
properly vents when tested as outlined above, return
doors, windows, exhaust fans, fireplace dampers and
any other fuel burning appliance to their previous con-
dition of use.

7. If improper venting is observed during any of the

above tests, the common venting system must be cor-
rected.

Horizontal Venting

The O23V is approved for horizontal venting with the fol-
lowing mechanical vent systems:

S

Tjernlund (sideshot) #SS1C

S

Field Controls #SWG−5 with the CK−61 control kit

Refer to the manufacturers’ installation instructions for
installation procedures and service parts information.
Do not use the same vent with any other appliance when
using a sidewall vent system.
Maximum permissible vent length is 70 equivalent feet.
Minimum length is 15 equivalent feet. Calculate the equiv-
alent vent pipe footage from the furnace to the mechanical
vent system (Tjernlund or Field Controls) by adding the
straight vent pipe length and the equivalent elbow lengths
together.

Downloaded from 

ManualsNet.com

 search engine

Summary of Contents for O23V Series

Page 1: ...sedes 10 2005 Table of Contents General 1 Shipping Packing List 1 O23V Unit Dimensions 2 O23V Unit Parts Arrangement 3 O23V Oil Burner Parts Arrangement 3 Requirements 4 Locate Level the Unit 4 Unit A...

Page 2: ...OW TOP VIEW RETURN AIR SIDE VIEW E RETURN AIR FRONT VIEW Figure 1 O23V Unit Dimensions Inches mm O23V Model A B C D E Q2 3 70 90 Q3 4 105 120 19 1 2 495 30 5 8 778 18 457 19 5 8 498 16 406 Q5 140 154...

Page 3: ...0 8 Figure 3 AIR TUBE SCREWS ELECTRONIC IGNITION TRANSFORMER FLANGE GASKET RETAIN ING CLIP IGNITOR PRIMARY CONTROL REAR ACCESS DOOR GASKET MAIN HOUSING ASSY AIR ADJUST DIAL 4X4 BOX BLOWER WHEEL INLET...

Page 4: ...i mum free area one half square inch per 1 000 Btu per hour input This combustion air should be brought into the area containing the furnace below the level of the furnace burner Table 2 O23V Installa...

Page 5: ...rner assembly from the vestibule By loosen ing the nuts and by turning the whole burner assembly counterclockwise figure 4 the entire burner assembly will come out of the furnace There is adequate wir...

Page 6: ...n outside or through any unconditioned space 6 Chimney should extend 3 feet 0 9 m above highest point where the vent passes through the roof and 2 feet 0 6 m higher than any portion of a building with...

Page 7: ...OR DEATH A living space which provides insufficient combustion air to the furnace can result in headaches nausea dizziness or asphyxiation CAUTION Insufficient combustion air to the furnace can cause...

Page 8: ...space shall be provided with two perma nent openings One opening shall be within 12 305 mm of the top of the enclosure and one within 12 305 mm of the bottom These openings must communicate directly o...

Page 9: ...from Common Venting System In the event that an existing furnace is removed from a venting system commonly run with separate appliances the venting system is likely to be too large to properly vent t...

Page 10: ...of the cabinet See unit dimensions on page 2 Using it as the center point cut a 6 inch 152 mm round hole in the cabinet s side Install the barometric draft control within 18 inches of the furnace flue...

Page 11: ...bing or steel pipe for oil supply pipe Install oil supply pipe under floor or near walls to protect it from damage Avoid running pipes along joists or reverberating surfaces Always use flare fittings...

Page 12: ...de the building between the tank shut off valve and the burn er Locate filter close to burner for easy maintenance Table 5 lists the filters for the O23V furnace Table 5 Installation Clearances inches...

Page 13: ...ted The Test jumper is used to operate the motor in the test mode See figure 17 Factory settings for the blower speed jumpers are given in the wiring diagram in figure 18 Figure 17 shows the blower co...

Page 14: ...age cooling closes the R to Y1 circuit on the A54 blower control board The blower motor runs at 57 CFM for the first 7 1 2 minutes of the 1st stage cooling demand After 7 1 2 minutes the blower motor...

Page 15: ...output to an electronic air cleaner The EAC terminal is energized when there is a call for heat cool or continuous blower See figure 18 Table 6 Blower Performance 0 through 0 80 in w g 0 through 200 P...

Page 16: ...Page 16 Figure 18 O23V Wiring Diagram P535277W Downloaded from ManualsNet com search engine...

Page 17: ...s above the range shown in the table check for high static pres sure Table 7 O23V Unit Nozzle Size Spray Angle Pattern Pump PSIG Input Rating BTU Hr Output Rating BTU Hr Head Temp Rise F 70 50GPH 80 A...

Page 18: ...ive Cleaning the Heat Exchanger 1 Remove the vent pipe from the furnace 2 Remove the locking screws and the caps from the clean out tubes Remove flue access elbow 3 Using a long spiral wire brush swee...

Page 19: ...rt Source Procedure Causes Correction Thermostat Check thermostat settings Thermostat in OFF or COOL Switch to HEAT Thermostat is set too low Turn thermostat to higher temperature Safety Overloads Che...

Page 20: ...flame is established Source Procedure Causes Correction Oil Supply Check tank gauge or use dip stick No oil in tank Fill tank Coat dip stick with litmus paste and insert into bottom of tank Water in o...

Page 21: ...ause of overloading Faulty motor Replace motor Troubleshooting Burner starts and fires but lock out on safety Source Procedure Causes Correction Poor Fire After burner fires immediately jumper across...

Page 22: ...ocedure Causes Correction Poor Fire After burner fires immediately jumper across flame detector terminals at the primary control SIf burner continues to run does not lock out of safety fault may be po...

Page 23: ...n air Air leaks into heat exchanger around inspection door etc Correct cause of air leak Excessive draft Adjust barometric draft control for correct draft Incorrect burner head adjustment Correct burn...

Page 24: ...nk Lift D Filter Type Inspect Change E Pressure Test F All fittings checked for tightness Thermostat A Type Heating Cooling B Anticipator Set C Wires New Old Air Filter A Filter Type Permanent Disposa...

Reviews: