background image

Page 5

Unit Adjustments

Neither the nozzle setting nor the air adjustments are fac-
tory set. The furnace is fire tested and the limit control is
checked to make sure it functions properly; no factory set-
tings are made. During installation, the furnace must be
set up." The installing dealer/contractor must have and
use proper test equipment in order to correctly set up the
oil furnace. Proper testing equipment is required to ensure
correct operation of the unit. The use of test equipment is
now more critical than ever due to tighter tolerances need-
ed to keep the furnace operating efficiently.

Among the test equipment for an oil furnace, the proper
combustion test kit should contain the following:

S

Draft gauge

S

CO

2

 or O

2

 analyzer

S

Smoke tester

S

Pressure gauge

S

High temperature thermometer

S

Beckett T−500 gauge

S

Oil vacuum gauge

S

Knowledge of proper test equipment operation

CAUTION

Improper nozzle and/or air adjustment of this unit
may result in sooting problems. Refer to the follow-
ing section for correct adjustment procedures.

Adjusting the Nozzle

Proper adjustment of the nozzle assembly is critical be-
cause alignment may have changed during shipping. Be-
fore the furnace and oil lines are installed, the nozzle as-
sembly must be checked. To check the nozzle assembly,
remove the entire burner assembly (not just the nozzle)
from the furnace. The lower firing nozzle is factory
installed. This should be verified by the installer. Inspect
the spark transformer leads also to ensure they are still at-
tached to the electrodes.

The burner assembly is attached to the vestibule panel by
three nuts. Slots are provided in the mounting flange for re-
moving the burner assembly from the vestibule. By loosen-
ing the nuts and by turning the whole burner assembly
counterclockwise (figure 4), the entire burner assembly
will come out of the furnace. There is adequate wire to re-
move the burner without disconnecting wires. Once re-
moved, turn the burner around in the vest panel area.

Figure 4

O23V Series Burner Removal

Loosen three nuts which at-
tach burner to vest panel.

Rotate burner counterclockwise on
slots then pull toward you.

To correctly adjust the nozzle, use a Beckett #T−500 gauge

Insert the small end of the gauge into the end of the cone
and measure from the flat of the end cone to the tip of the
nozzle. When nozzle depth is correct, the tip of the nozzle
should just touch the end of the gauge. Refer to the illustra-
tion sheet provided with the gauge. Note that the scale side
of the gauge is not used for this purpose. Make corrections
by sliding the nozzle assembly forward or backward within
the blast tube (figure 5). At the same time, check the
nozzle alignment.

Figure 5

Beckett Oil Burner Nozzle Adjustment

Burner must be removed from furnace for this procedure.

GAUGE

TO ADJUST NOZZLE:

1−Loosen screw.
2−Slide entire nozzle/electrode assembly back and forth until nozzle
just touches the gauge.

1

2

To check nozzle alignment, again insert the small end into
the end cone and measure the nozzle and electrode align-
ment against the center lines marked on the gauge (again
refer to enclosed illustration sheet). If the nozzle is not cen-
tered, but found to be too far left or right, a new nozzle as-
sembly will need to be ordered. Do not attempt to adjust by
bending the 90 degree elbow in the oil line.

Venting

WARNING

Combustion air openings in front of the furnace
must be kept free of obstructions. Any obstruction
will cause improper burner operation and may re-
sult in a fire hazard.

Downloaded from 

ManualsNet.com

 search engine

Summary of Contents for O23V Series

Page 1: ...sedes 10 2005 Table of Contents General 1 Shipping Packing List 1 O23V Unit Dimensions 2 O23V Unit Parts Arrangement 3 O23V Oil Burner Parts Arrangement 3 Requirements 4 Locate Level the Unit 4 Unit A...

Page 2: ...OW TOP VIEW RETURN AIR SIDE VIEW E RETURN AIR FRONT VIEW Figure 1 O23V Unit Dimensions Inches mm O23V Model A B C D E Q2 3 70 90 Q3 4 105 120 19 1 2 495 30 5 8 778 18 457 19 5 8 498 16 406 Q5 140 154...

Page 3: ...0 8 Figure 3 AIR TUBE SCREWS ELECTRONIC IGNITION TRANSFORMER FLANGE GASKET RETAIN ING CLIP IGNITOR PRIMARY CONTROL REAR ACCESS DOOR GASKET MAIN HOUSING ASSY AIR ADJUST DIAL 4X4 BOX BLOWER WHEEL INLET...

Page 4: ...i mum free area one half square inch per 1 000 Btu per hour input This combustion air should be brought into the area containing the furnace below the level of the furnace burner Table 2 O23V Installa...

Page 5: ...rner assembly from the vestibule By loosen ing the nuts and by turning the whole burner assembly counterclockwise figure 4 the entire burner assembly will come out of the furnace There is adequate wir...

Page 6: ...n outside or through any unconditioned space 6 Chimney should extend 3 feet 0 9 m above highest point where the vent passes through the roof and 2 feet 0 6 m higher than any portion of a building with...

Page 7: ...OR DEATH A living space which provides insufficient combustion air to the furnace can result in headaches nausea dizziness or asphyxiation CAUTION Insufficient combustion air to the furnace can cause...

Page 8: ...space shall be provided with two perma nent openings One opening shall be within 12 305 mm of the top of the enclosure and one within 12 305 mm of the bottom These openings must communicate directly o...

Page 9: ...from Common Venting System In the event that an existing furnace is removed from a venting system commonly run with separate appliances the venting system is likely to be too large to properly vent t...

Page 10: ...of the cabinet See unit dimensions on page 2 Using it as the center point cut a 6 inch 152 mm round hole in the cabinet s side Install the barometric draft control within 18 inches of the furnace flue...

Page 11: ...bing or steel pipe for oil supply pipe Install oil supply pipe under floor or near walls to protect it from damage Avoid running pipes along joists or reverberating surfaces Always use flare fittings...

Page 12: ...de the building between the tank shut off valve and the burn er Locate filter close to burner for easy maintenance Table 5 lists the filters for the O23V furnace Table 5 Installation Clearances inches...

Page 13: ...ted The Test jumper is used to operate the motor in the test mode See figure 17 Factory settings for the blower speed jumpers are given in the wiring diagram in figure 18 Figure 17 shows the blower co...

Page 14: ...age cooling closes the R to Y1 circuit on the A54 blower control board The blower motor runs at 57 CFM for the first 7 1 2 minutes of the 1st stage cooling demand After 7 1 2 minutes the blower motor...

Page 15: ...output to an electronic air cleaner The EAC terminal is energized when there is a call for heat cool or continuous blower See figure 18 Table 6 Blower Performance 0 through 0 80 in w g 0 through 200 P...

Page 16: ...Page 16 Figure 18 O23V Wiring Diagram P535277W Downloaded from ManualsNet com search engine...

Page 17: ...s above the range shown in the table check for high static pres sure Table 7 O23V Unit Nozzle Size Spray Angle Pattern Pump PSIG Input Rating BTU Hr Output Rating BTU Hr Head Temp Rise F 70 50GPH 80 A...

Page 18: ...ive Cleaning the Heat Exchanger 1 Remove the vent pipe from the furnace 2 Remove the locking screws and the caps from the clean out tubes Remove flue access elbow 3 Using a long spiral wire brush swee...

Page 19: ...rt Source Procedure Causes Correction Thermostat Check thermostat settings Thermostat in OFF or COOL Switch to HEAT Thermostat is set too low Turn thermostat to higher temperature Safety Overloads Che...

Page 20: ...flame is established Source Procedure Causes Correction Oil Supply Check tank gauge or use dip stick No oil in tank Fill tank Coat dip stick with litmus paste and insert into bottom of tank Water in o...

Page 21: ...ause of overloading Faulty motor Replace motor Troubleshooting Burner starts and fires but lock out on safety Source Procedure Causes Correction Poor Fire After burner fires immediately jumper across...

Page 22: ...ocedure Causes Correction Poor Fire After burner fires immediately jumper across flame detector terminals at the primary control SIf burner continues to run does not lock out of safety fault may be po...

Page 23: ...n air Air leaks into heat exchanger around inspection door etc Correct cause of air leak Excessive draft Adjust barometric draft control for correct draft Incorrect burner head adjustment Correct burn...

Page 24: ...nk Lift D Filter Type Inspect Change E Pressure Test F All fittings checked for tightness Thermostat A Type Heating Cooling B Anticipator Set C Wires New Old Air Filter A Filter Type Permanent Disposa...

Reviews: