Page 15
Continuous Fan
When the thermostat is set for Continuous Fan" operation
and there is no demand for heating or cooling, the blower
control will provide 50% of the
COOL
CFM selected.
OFF
CALL
50%
G
g
G − Fan switch ON
g − Fan switch OFF
NOTE − With the proper thermostat and subbase, continu-
ous blower operation is possible by closing the R to G cir-
cuit.
Dehumidification
The A54 blower control board (see figure 17) includes a
HUM terminal which provides for connection of a humidis-
tat. The JW1 jumper on the blower control board must be
cut to activate the HUM terminal. The humidistat must be
wired to open on humidity rise. When the dehumidification
circuit is used, the variable speed motor will reduce the se-
lected air flow rate by 18% when humidity levels are high.
An LED (D1) lights when the blower is operating in the de-
humidification mode.
Humidification
Terminals are provided on the A15 control board for 120
volt output to operate a humidifier. The HUM" terminal is
energized when there is a call for heat. See figure 18.
Electronic Air Cleaner
Terminals are provided on A15 control board for 120 volt
output to an electronic air cleaner. The EAC" terminal is
energized when there is a call for heat, cool, or continuous
blower. See figure 18.
Table 6
Blower Performance
{0 through 0.80 in. w.g. (0 through 200 Pa) External Static Pressure Range}
ADJUST"
Jumper
Setting
HEAT" Jumper Speed Position [kBtuh heat input]
COOL" Jumper Speed Position
A
B
C
D
A
B
C
D
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
Model O23V2/3−70/90 Units
Do not use
Do not use
[−90]
[−70]
(+)
N/A
N/A
N/A
N/A
Same as NORM
1380
650
1150
545
920
435
690
325
NORM
N/A
N/A
N/A
N/A
1000
470
750
355
1200
565
1000
470
800
380
600
285
(–)
N/A
N/A
N/A
N/A
Same as NORM
1020
480
850
400
680
320
510
240
Model O23V3/4−105/120 Units
Do not use
Do not use
[−120]
[−105]
(+)
N/A
N/A
N/A
N/A
Same as NORM
1610
760
1380
650
1150
540
920
435
NORM
N/A
N/A
N/A
N/A
1300
615
1200
565
1400
660
1200
565
1000
470
800
380
(–)
N/A
N/A
N/A
N/A
Same as NORM
1190
560
1020
480
850
400
680
320
Model O23V5−140/154 Units
Do not use
[−154]
Do not use
[−140]
(+)
N/A
N/A
Same as
NORM
N/A
N/A
Same as
NORM
2300
1085
2070
975
1840
870
1380
650
NORM
N/A
N/A
1730
816
N/A
N/A
1400
660
2000
945
1800
850
1600
755
1200
565
(–)
N/A
N/A
Same as
NORM
N/A
N/A
Same as
NORM
1700
800
1530
720
1360
640
1020
480
NOTE − Continuous Fan air volume is 50% of COOL speed.
Downloaded from