Page 48
MS8C / MS8H (208-230V)
DISCHARGE LINE TEMPERATURE SENSOR (RT5)
High compressor discharge temperature can result from either of the following conditions:
*
Low refrigerant charge
*
Restricted refrigerant flow
When the discharge line temperature drops below 194°F (90°C) and the compressor has been
OFF
for more than 3 minutes,
the system will resume normal operation.The discharge line sensor continuously monitors the discharge temperature and
communicates this to the microprocessor. The microprocessor takes these measurements and changes the frequency of the
compressor to meet the system load. If the discharge temperature increases to the ranges noted in the above chart, the
microprocessor will adjust the frequency or cycle the compressor
OFF
(table 14).
DISCHARGE LINE TEMPERATURE PROTECTION SEQUENCE (RT5)
FIGURE 62
TABLE 14
MONITORING OF OUTDOOR DISCHARGE (RT5) LINE TEMPERATURE
Condition
Action
If outdoor discharge line temperature is greater than 208.ºF (98ºC)
Change in compressor speed is not allowed.
If outdoor discharge line temperature is greater than 217ºF (103ºC)
Compressor will run at reduced speed.
If outdoor discharge line temperature is greater than 230ºF (110ºC)
Compressor will stop.
If outdoor discharge line temperature is less than 194ºF (90ºC)
After anti-short cycle (3 minutes) delay, the compressor and outdoor fan
will resume operation.
Indoor Fan Operation
When compressor is cycled ”OFF”, the indoor fan will continue to run at a preset speed in air conditioning or in heating it will
cycle ”OFF” 60 seconds after compressor.
TEMPERATURE SENSOR FAULTS
Refer to the error code tables for details concerning fault conditions and equipment behavior.
TESTING TEMPERATURE SENSOR RESISTANCES
Sensors are connected to the indoor and outdoor controls through field-replaceable harnesses. These sensors provide
indoor ambient air (RT1), outdoor ambient air (RT4), indoor coil (RT2), outdoor coil (RT3) and outdoor discharge line (RT5)
temperatures to the indoor and outdoor controls to identify fault conditions. As the temperature changes, the resistance
across these sensor changes. Tables 15 through 17 indicates how the resistance varies as the temperature changes for all
reference temperature sensors.