Page 79
Corp. 1244-L9
N
N
Check the outdoor wiring connections
for both the reactor (choke) line and
power factor correction capacitor
Start
Any damage or
short circuit?
Replace damage
component
Is fault corrected?
Restart unit
Restart
unit
Replace
reactor
(choke)
If capacitor is
short-circuited,
then replace
Is resistances
near zero?
Remove power factor
correction capacitor
(CBB65) and check for
open or shorted condition
between terminals.
Replace outdoor
control
Is component
damage or
short-circuited?
Disconnect the reactor (choke)
terminals and measure
resistances between both using
ohm gauge.
Y
Y
Y
Y
Y
N
N
N
N
End
Is fault corrected?
Is fault corrected?
Y
OUTDOOR POWER FACTOR CORRECTION FAULT
APPLICABLE UNIT SIZE(S): All
APPLICABLE ERROR CODE(S): HC
FIGURE 88