IOM / MINIAIR-0507
25
Model
03
06
10
14
19
25
30
Section 1.05 A
796
796
906
946
946
1276
1276
B
940
940
1100
1230
1380
1630
1630
C
700
700
810
830
830
1160
1160
D
1036
1036
1196
1346
1496
1746
1746
To aid the regular flow of the condensation, it is advised to install the apparatus with a 3 mm inclination towards the
condensation outlet.
13.6 Duct connection
The Ducts must be the correct dimension based on the functions of system and the air diffusion characteristics
of the unit fans. A mistaken calculation of the ducting will cause power loss or the intervention of any eventual
devices present on the system.
To prevent the formation of condensation and cut down the sound level it is advised to use internally lined
Ducts.
To avoid the transmission of machine vibrations into the environment, it is advised to fit an anti-vibration joint
between the fans and Ducts. The electrical continuity must be guaranteed between the Ducts and the apparatus
via an earth cable.
IMPORTANT: IT IS IMPORTANT NOT TO PLACE
IN OPERATION THE UNIT IF THE
MOUTHS OF THE FANS ARE NOT DUCTED OR
NOT PROTECTED BY A SAFETY NET
ADHERING WITH REGULATION UNI 9219 OR
SUCCESSIVE.