18
IOM / MINIAIR-0507
11.5 Accessories technical data
11.5.1 Water coil for reheating
Section 1.03 Coil code
SKW 10
SKW 14
SKW 19
SKW 25
SKW 30
SKW 40
Geometry
25 22
25 22
25 22
25 22
25 22
25 22
Tubes per row
N °
14
14
16
17
17
21
Rows
N °
3
3
3
3
3
3
Fin pitch
mm
2.5
2.5
2.5
2.5
2.5
2.5
Capacity
KW
9.4
13.4
16.6
23.9
28.4
36.2
Outlet temp
° C
36
36.6
34.1
36.6
34.5
34.3
Air pressure drop
Pa
65
64
85
62
85
92
Water pressure drop
kPa
8
16
10
11
15
27
Size valued in the following hypothesis:
Water 70/60°C;
Air entrance temperature 8°C;
Nominal air volume.
11.5.2 Electrical reheating
Coil code
SKE 03
SKE 06
SKE 10
SKE 14
SKE 19
SKE 25
SKE 30
SKE 40
Electrical coil 1 stage
kW
2
4
4.5
6
9
12
12
12
Power supply
V
230
230
400
400
400
400
400
400
Phases
n°
1
1
3
3
3
3
3
3
Stage
n°
1
1
1
1
1
1
1
1
Absorbed current
A
8.7
17.4
6.5
8.7
13
17.3
17.3
17.3
Outlet Air Temp (+)
°C
28.4
27.8
21.3
20.7
22
22.2
19.5
17
(+) Size valued with Ting air = 8°C and nominal air capacity.