background image

Page 7 

Improper installation, adjustment, alteration, service, or 

maintenance can cause injury or property damage. Refer 

to this manual. For assistance or additional information, 

consult a licensed professional (or equivalent), HVAC 

installer, service agency, or the gas supplier.

WARNING

Installation

These instructions must be saved for future reference.

These units are single package air conditioners with gas 

heat designed for outdoor installation on a rooftop or a 

slab.

The units are completely assembled. All piping, refrigerant 

charge, and electrical wiring are factory installed and 

tested. The units require only electric power, gas piping, 

condensate drain, and duct connections, plus installation 

of the vent cover at the point of installation.

If components are to be added to a unit to meet local codes, 

they are to be installed at the dealer’s and/or customer’s 

expense.

The size of unit for the proposed installation should be 

based on heat loss/heat gain calculation made according 

to the methods of Air Conditioning Contractors of America 

(ACCA).

In the State of Massachusetts:

This product must be installed by a licensed Plumber 

or Gas Fitter. When flexible connectors are used, the 

maximum length shall not exceed 36”. When lever-type 

gas shutoffs are used, they shall be T-handle type.

WARNING

These installation instructions are intended as a 

general guide only, for use by an experienced, qualified 

contractor.

These  units  are  certified  by  E.T.L.  Testing  Laboratories, 

Inc.:

•  For use as a forced air furnace with cooling unit.
•  For outdoor installation only.
•  For installation on combustible material.
•  For use with natural gas or propane gas. (Conversion 

kit required for propane gas application.)

These units are not suitable for use with conventional 

venting systems.

Inspection

As soon as the unit is received, it should be inspected 

for possible damage during transit. If damage is evident, 

the extent of the damage should be noted on the carrier’s 

freight bill. A separate request for inspection by the carrier’s 

agent should be made in writing.

Location

Use the following guidelines to select a suitable location 

for these units.

1.  Unit is designed for outdoor installation only. Unit must 

be installed so all electrical components are protected 

from water.

2.  Condenser coils must have an unlimited supply of air.
3.  For ground level installation, use a level prefabricated 

pad or use a level concrete slab. Do not tie the slab to 

the building foundation.

4.  Maintain level within a tolerance of 1/4” maximum 

across the entire length or width of the unit.

Unit levelness is critical for proper float switch operation.

CAUTION

5.  Do not locate the unit where the combustion air supply 

will be exposed to any of the following substances:

•  Permanent wave solutions
•  Chlorinated waxes and cleaners
•  Chlorine-based swimming pool chemicals
•  Water softening chemicals
•  Deicing salts or chemicals
•  Carbon tetrachloride
•  Halogen-type refrigerants
•  Cleaning solvents (such as perchloroethylene)
•  Printing inks, paint removers, varnishes, etc.
•  Cements and glues
•  Antistatic fabric softeners for clothes dryers
•  Masonry acid washing materials
•  Chlorinated laundry products
•  Hydrochloric acid

Use of Unit During Construction

Use of this unit as a construction heater or air conditioner is 

not recommended during any phase of construction. Very 

low return air temperatures, harmful vapors and operation 

of  the  unit  with  clogged  or  misplaced  filters  will  damage 

the unit.

If this unit has been used for heating or cooling of buildings 

or structures under construction, the following conditions 

must be met or the warranty will be void:

Summary of Contents for LRP16GE Series

Page 1: ...stries Inc Dallas Texas USA THIS MANUAL MUST BE LEFT FOR FUTURE REFERENCE WARNING Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss o...

Page 2: ...17 07 13 44 13 44 14 32 16 06 6 20 40 89 21 63 13 21 TYPICAL DRAIN LOCATION CONDENSATE DRAIN 3 4 NPT 5 75 3 55 4 12 TYPICAL VENT HOOD SIDE VIEWS 11 49 2 33 47 66 1 98 16 77 2 48 14 02 47 66 POWER ENT...

Page 3: ...AGE ENTRY 7 8 DIA KNOCKOUT GAS SUPPLY 44 89 21 63 13 21 TYPICAL DRAIN LOCATION CONDENSATE DRAIN 3 4 NPT 5 75 3 55 4 12 TYPICAL VENT HOOD SIDE VIEWS TOP VIEW POWER ENTRY GAS ENTRY RETURN AIR 2 11 19 49...

Page 4: ...44 3 8 1127 44 3 8 1127 16 7 8 429 13 7 8 352 2 1 8 54 11 1 2 287 SUPPLY OPENING RETURN OPENING 8 203 14 356 18 457 24 610 3 4 19 1 25 5 1 2 140 5 3 4 146 11 1 2 287 17 1 4 438 1 3 8 35 3 3 4 95 13 3...

Page 5: ...13 in 76 x 330 mm 52 7 8 1343 44 3 8 1127 19 1 2 380 11 1 2 287 19 1 2 380 2 1 8 54 11 1 2 287 SUPPLY OPENING RETURN OPENING 8 203 14 356 18 457 24 610 3 3 4 95 22 7 8 581 7 178 3 4 19 1 25 NOTE If bo...

Page 6: ...8 203 SIDES AND BACK FLANGE 6 152 UNIT BASE RAIL CLIPS 4 NOTE Minimum Height 4 102 UNIT BASE RAIL CLIPS 4 Usage A B C in mm in mm in mm 24 36 42 7 8 1089 13 7 8 352 16 7 8 429 48 60 51 3 8 1305 19 1 2...

Page 7: ...nits are not suitable for use with conventional venting systems Inspection As soon as the unit is received it should be inspected for possible damage during transit If damage is evident the extent of...

Page 8: ...s may be installed on combustible floors Units must be installed outdoors Clearance to combustibles below the unit flue is 10 inches since the flue points down Do not permit overhanging structures or...

Page 9: ...truction bag see Figure 2 Vent Hood Attach with Screws Figure 2 Installing the Vent Cover Rigging Unit Exercise care when moving the unit Do not remove any packaging until the unit is near the place o...

Page 10: ...ilter rack kit If an existing gas furnace is being removed from a common venting system when this packaged unit is installed then read and follow the instructions in the Removal of Unit from Common Ve...

Page 11: ...rating plate Gas Piping Recommendations A drip leg and a ground joint union must be installed in the gas piping A ground joint union is recommended by the manifold valve When required by local codes a...

Page 12: ...he National Electrical Code ANSI NFPA No 70 latest edition Canadian Electrical Code Part 1 CSA C22 1 latest edition or local codes where they prevail Use wiring with a temperature limitation of 75 C m...

Page 13: ...d insulated wires 18 AWG should be used to connect the thermostat to the unit Compressor Units are shipped with compressor mountings factory adjusted and ready for operation Do not loosen compressor m...

Page 14: ...as valve and connecting a water manometer or gauge Under no circumstances should the final manifold pressure vary more than 0 3 w c from the above specified pressures To adjust the regulator turn the...

Page 15: ...roughout the external static range A particular CFM can be obtained by positioning jumpers COOL HEAT and ADJUST on the blower control The HEAT and COOL jumpers are labeled A B C and D Each of the numb...

Page 16: ...duce the selected air flow rate by 25 percent when humidity levels are high An LED D1 lights when the blower is operating in the dehumidification mode Cooling System The cooling system is a factory ch...

Page 17: ...nds of the ignition trial If the flame is established within 10 seconds the control de energizes the spark If flame is not established within 10 seconds the gas valve and spark are de energized and th...

Page 18: ...need cleaning Sooting of a gas appliance is highly irregular and once cleaned the cause of the sooting must be determined If the heat exchanger should become sooted it can be cleaned as follows 1 Remo...

Page 19: ...eration Call for heat 2 Flash Two flashes in second with 1 second pause System lockout Failed to detect or sustain flame 3 Flash Three flashes in 1 5 seconds with 1 second pause Pressure switch senses...

Page 20: ...00 400 1260 1080 900 720 1400 1200 1100 975 630 540 450 360 048 Blower Performance 0 through 0 80 in w g External Static Pressure Range 1980 1760 1540 1320 1350 1200 1100 1000 990 880 770 660 NORM 180...

Page 21: ...Page 21 Figure 9 Wiring Diagram Single Phase Wiring Diagram LRP16GE...

Page 22: ...being pulled through the condensate line will prevent positive drainage without a proper trap The condensate drain line must be properly trapped routed to a suitable drain and primed prior to unit com...

Page 23: ...JUST jumper is labeled Test and Norm The and pin settings are used to add or subtract a percentage of the CFM selected The Test jumper is used to operate the motor in the test mode Figure 12 shows the...

Page 24: ...e is no demand for heating or cooling the blower control will provide 50 percent of the COOL CFM selected DEHUMIDIFICATION The blower control includes an HUM terminal which provides for connection of...

Page 25: ...l Board 24V TERMINAL STRIP CONNECTIONS DIAGNOSTIC LEDS HIGH PRESSURE SWITCH TEST PINS DEFROST TIMING PINS P1 REVERSING VALVE DEFROST THERMOSTAT S6 LOW PRESSURE SWITCH COMPRESSOR DELAY PINS S4 S87 SERV...

Page 26: ...he compressor delay jumper is removed NOTE The 30 second off cycle is not functional when jumpering the TEST pins Time Delay The defrost control includes a compressor timer which ensures the compresso...

Page 27: ...ance normally consists of changing or cleaning the filters and cleaning the evaporator coil On occasion other components may also require cleaning Filters Filters are not supplied with the unit Inspec...

Page 28: ...49 150 36 132 134 136 137 138 139 140 142 144 145 147 148 48 136 138 140 142 143 144 145 147 148 149 150 151 60 134 135 137 138 139 140 141 142 144 145 147 148 24 Liquid 237 257 278 298 306 320 343 36...

Page 29: ...36 26 33 40 50 54 61 68 75 83 95 103 117 131 48 28 36 43 53 57 65 72 79 89 102 107 116 125 60 31 39 46 56 60 68 75 82 89 99 106 117 128 24 Liquid 264 271 279 289 294 301 309 316 324 335 340 348 357 36...

Page 30: ...Page 30 Wiring Diagram LRP16HP Figure 14 HP Wiring Diagram...

Reviews: