Lennox LRP16GE Series Installation Instructions Manual Download Page 18

Page 18 

Maintenance – LRP16GE

Periodic inspection and maintenance normally consists of 

changing or cleaning the filters and cleaning the evaporator 

coil. On occasion, other components of the furnace may 

also require cleaning.

Shut off all electrical power to the unit before conducting 

any maintenance procedures. Failure to do so could 

cause personal injury.

WARNING

Filters

Filters are not supplied with the unit. Inspect once a month. 

Replace disposable or clean permanent type as necessary. 

Do not replace permanent type with disposable.

Motors

Indoor and outdoor fan and vent motors are permanently 

lubricated and require no maintenance.

Evaporator Coil

Dirt and debris should not be allowed to accumulate on 

the evaporator coil surface or other parts in the air circuit. 

Cleaning should be as often as necessary to keep coil 

clean. Use a brush, vacuum cleaner attachment, or other 

suitable means. If water is used to clean the coil, be sure 

the power to unit is shut off prior to cleaning. 

Care should 

be used when cleaning the coil so that the coil fins are 

not damaged.

Do not permit the hot condenser air discharge to be 

obstructed by overhanging structures or shrubs.

Condenser Coil

Clean condenser coil annually with water and inspect 

monthly during the cooling season.

Condenser coil may need to be cleaned at startup in 

case oil from the manufacturing process is found on the 

condenser coil.

Burners

To clean the burners, first remove them from the furnace 

as explained in Burner Instructions on Page 15. Vacuum 

and/or brush as required.

Vent Outlet 

Visually inspect vent outlet periodically to make sure that 

there is no buildup of soot or dirt. If necessary, clean to 

maintain adequate opening to discharge flue products.

Heat Exchanger

With proper combustion adjustment, the heat exchanger 

of a gas-fired furnace will seldom need cleaning. Sooting 

of a gas appliance is highly irregular and once cleaned, 

the cause of the sooting must be determined. If the heat 

exchanger should become sooted, it can be cleaned as 

follows:
1.  Remove the burner assembly as outlined in Burner 

Instructions on Page 15.

2.  Remove the combustion blower.
3.  At the bottom of the heating section, remove the screws 

holding the flue collector box. Carefully remove the flue 

collector box without ripping the adjacent insulation.

4. 

Using a wire brush on a flexible wand, brush out the 

inside of each heat exchanger from the burner inlet 

and flue outlet ends.

5. 

Brush out the inside of the flue collector box.

6.  Run the wire brush down the heat exchanger tubes 

from the flue collector end.

7.  If soot buildup is excessive, remove the vent motor and 

clean the wheel and housing. Run the wire brush down 

the flue extension at the outlet of the vent housing.

8.  After brushing is complete, blow all brushed areas with 

air. Vacuum as needed.

9.  Replace parts in the reverse order they were removed 

in Steps 1 through 3.

10. 

When replacing the flue collector box, be careful so as 

not to tear the adjoining insulation.

11.  Assure that all joints on the vent side of the combustion 

system are air tight. Apply a high temperature (+500°F) 

sealing compound where needed.

Flame Sensor

If the ignition control does not receive a signal from the 

flame sensor indicating that the burners have established 

flame,  the  gas  valve  closes  after  the  10-second  trial  for 

ignition period. 

Rollout Switch

The switch is located on the top of burner box. In the event 

of a sustained main burner rollout, the rollout switch shuts 

off the ignition control and closes the main gas valve. To 

reset, push the button on top of the switch.

Secure Owner’s Approval

When the system is functioning properly, secure the owner’s 

approval. Show the owner the location of all disconnect 

switches and the thermostat. Instruct the owner on how 

to start and stop the unit and how to adjust temperature 

settings within the limitations of the system.

Summary of Contents for LRP16GE Series

Page 1: ...stries Inc Dallas Texas USA THIS MANUAL MUST BE LEFT FOR FUTURE REFERENCE WARNING Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss o...

Page 2: ...17 07 13 44 13 44 14 32 16 06 6 20 40 89 21 63 13 21 TYPICAL DRAIN LOCATION CONDENSATE DRAIN 3 4 NPT 5 75 3 55 4 12 TYPICAL VENT HOOD SIDE VIEWS 11 49 2 33 47 66 1 98 16 77 2 48 14 02 47 66 POWER ENT...

Page 3: ...AGE ENTRY 7 8 DIA KNOCKOUT GAS SUPPLY 44 89 21 63 13 21 TYPICAL DRAIN LOCATION CONDENSATE DRAIN 3 4 NPT 5 75 3 55 4 12 TYPICAL VENT HOOD SIDE VIEWS TOP VIEW POWER ENTRY GAS ENTRY RETURN AIR 2 11 19 49...

Page 4: ...44 3 8 1127 44 3 8 1127 16 7 8 429 13 7 8 352 2 1 8 54 11 1 2 287 SUPPLY OPENING RETURN OPENING 8 203 14 356 18 457 24 610 3 4 19 1 25 5 1 2 140 5 3 4 146 11 1 2 287 17 1 4 438 1 3 8 35 3 3 4 95 13 3...

Page 5: ...13 in 76 x 330 mm 52 7 8 1343 44 3 8 1127 19 1 2 380 11 1 2 287 19 1 2 380 2 1 8 54 11 1 2 287 SUPPLY OPENING RETURN OPENING 8 203 14 356 18 457 24 610 3 3 4 95 22 7 8 581 7 178 3 4 19 1 25 NOTE If bo...

Page 6: ...8 203 SIDES AND BACK FLANGE 6 152 UNIT BASE RAIL CLIPS 4 NOTE Minimum Height 4 102 UNIT BASE RAIL CLIPS 4 Usage A B C in mm in mm in mm 24 36 42 7 8 1089 13 7 8 352 16 7 8 429 48 60 51 3 8 1305 19 1 2...

Page 7: ...nits are not suitable for use with conventional venting systems Inspection As soon as the unit is received it should be inspected for possible damage during transit If damage is evident the extent of...

Page 8: ...s may be installed on combustible floors Units must be installed outdoors Clearance to combustibles below the unit flue is 10 inches since the flue points down Do not permit overhanging structures or...

Page 9: ...truction bag see Figure 2 Vent Hood Attach with Screws Figure 2 Installing the Vent Cover Rigging Unit Exercise care when moving the unit Do not remove any packaging until the unit is near the place o...

Page 10: ...ilter rack kit If an existing gas furnace is being removed from a common venting system when this packaged unit is installed then read and follow the instructions in the Removal of Unit from Common Ve...

Page 11: ...rating plate Gas Piping Recommendations A drip leg and a ground joint union must be installed in the gas piping A ground joint union is recommended by the manifold valve When required by local codes a...

Page 12: ...he National Electrical Code ANSI NFPA No 70 latest edition Canadian Electrical Code Part 1 CSA C22 1 latest edition or local codes where they prevail Use wiring with a temperature limitation of 75 C m...

Page 13: ...d insulated wires 18 AWG should be used to connect the thermostat to the unit Compressor Units are shipped with compressor mountings factory adjusted and ready for operation Do not loosen compressor m...

Page 14: ...as valve and connecting a water manometer or gauge Under no circumstances should the final manifold pressure vary more than 0 3 w c from the above specified pressures To adjust the regulator turn the...

Page 15: ...roughout the external static range A particular CFM can be obtained by positioning jumpers COOL HEAT and ADJUST on the blower control The HEAT and COOL jumpers are labeled A B C and D Each of the numb...

Page 16: ...duce the selected air flow rate by 25 percent when humidity levels are high An LED D1 lights when the blower is operating in the dehumidification mode Cooling System The cooling system is a factory ch...

Page 17: ...nds of the ignition trial If the flame is established within 10 seconds the control de energizes the spark If flame is not established within 10 seconds the gas valve and spark are de energized and th...

Page 18: ...need cleaning Sooting of a gas appliance is highly irregular and once cleaned the cause of the sooting must be determined If the heat exchanger should become sooted it can be cleaned as follows 1 Remo...

Page 19: ...eration Call for heat 2 Flash Two flashes in second with 1 second pause System lockout Failed to detect or sustain flame 3 Flash Three flashes in 1 5 seconds with 1 second pause Pressure switch senses...

Page 20: ...00 400 1260 1080 900 720 1400 1200 1100 975 630 540 450 360 048 Blower Performance 0 through 0 80 in w g External Static Pressure Range 1980 1760 1540 1320 1350 1200 1100 1000 990 880 770 660 NORM 180...

Page 21: ...Page 21 Figure 9 Wiring Diagram Single Phase Wiring Diagram LRP16GE...

Page 22: ...being pulled through the condensate line will prevent positive drainage without a proper trap The condensate drain line must be properly trapped routed to a suitable drain and primed prior to unit com...

Page 23: ...JUST jumper is labeled Test and Norm The and pin settings are used to add or subtract a percentage of the CFM selected The Test jumper is used to operate the motor in the test mode Figure 12 shows the...

Page 24: ...e is no demand for heating or cooling the blower control will provide 50 percent of the COOL CFM selected DEHUMIDIFICATION The blower control includes an HUM terminal which provides for connection of...

Page 25: ...l Board 24V TERMINAL STRIP CONNECTIONS DIAGNOSTIC LEDS HIGH PRESSURE SWITCH TEST PINS DEFROST TIMING PINS P1 REVERSING VALVE DEFROST THERMOSTAT S6 LOW PRESSURE SWITCH COMPRESSOR DELAY PINS S4 S87 SERV...

Page 26: ...he compressor delay jumper is removed NOTE The 30 second off cycle is not functional when jumpering the TEST pins Time Delay The defrost control includes a compressor timer which ensures the compresso...

Page 27: ...ance normally consists of changing or cleaning the filters and cleaning the evaporator coil On occasion other components may also require cleaning Filters Filters are not supplied with the unit Inspec...

Page 28: ...49 150 36 132 134 136 137 138 139 140 142 144 145 147 148 48 136 138 140 142 143 144 145 147 148 149 150 151 60 134 135 137 138 139 140 141 142 144 145 147 148 24 Liquid 237 257 278 298 306 320 343 36...

Page 29: ...36 26 33 40 50 54 61 68 75 83 95 103 117 131 48 28 36 43 53 57 65 72 79 89 102 107 116 125 60 31 39 46 56 60 68 75 82 89 99 106 117 128 24 Liquid 264 271 279 289 294 301 309 316 324 335 340 348 357 36...

Page 30: ...Page 30 Wiring Diagram LRP16HP Figure 14 HP Wiring Diagram...

Reviews: