Lennox LRP16GE Series Installation Instructions Manual Download Page 15

Page 15 

To check this pressure:
1.  Slide the gas valve switch to the “OFF” position (see 

Figure 7).

2.  Remove plug on valve marked “OUTLET PRESSURE.”
3.  Install a water manometer.
4.  Slide the gas valve switch to the “ON” position and 

initiate a call for heat. If manifold pressure must be 

adjusted, the gas valve has separate adjusting screws 

for first stage (LO) and second stage (HI) (see Figure 

7). Turn the adjusting screws clockwise to increase 

pressure and input; turn counterclockwise to decrease 

pressure and input. The pressure regulator adjustment 

is sensitive. One turn of the adjusting screw results in 

a large change in manifold pressure. Final first-stage 

and second-stage manifold pressures must be within 

the allowable ranges for the gas being used.

5. 

After  checking  pressure,  turn  gas  off,  remove 

manometer fitting, and replace pipe plug and regulator 

cap.

6.  Put furnace in operation and check plug for leaks 

using soapy solution.

Burner and Burner Orifice Instructions

To check or change burners or burner orifices:

1. 

Close the main manual gas shutoff valve and turn off 

all power to unit.

2.  Remove the burner access panel.  
3.  Disconnect the union in the gas supply line upstream 

of the gas valve and downstream of the manual shutoff 

valve.

4.  Label wires going to the gas valve, then disconnect 

the wires.

5. 

To change orifice:

a.  Remove screws that fasten the manifold to the 

burner box assembly and remove the manifold.

b. 

Remove  the  orifices,  then  install  replacement 

orifices.

c.  To reassemble: Reverse above steps, making 

sure orifices are inserted into the orifice holders 

on the back end of the burners, and that burners 

are level and centered on each burner opening in 

the vest panel.

6.  To remove or service burners:

a.  Label and disconnect the wires to the rollout switch 

and disconnect the igniter and flame sensor leads 

at the ignition control.

b.  Remove the screws that secure the burner box 

assembly to the vest panel and remove the 

assembly from the unit.

c.  Remove the screws that fasten the burner rack 

and bottom shield assembly to the burner box. 

Burners are now accessible for removal.

Operation

Blower Control 

Units are equipped with a variable speed motor that is 

capable  of  maintaining  a  specified  CFM  throughout  the 

external static range. A particular CFM can be obtained by 

positioning jumpers (COOL, HEAT, and ADJUST) on the 

blower control. The HEAT and COOL jumpers are labeled 

A, B, C and D. Each of the numbers corresponds with an 

air volume (CFM) setting. The ADJUST jumper is labeled 

Test, -, +, and Norm. The + and - pin settings are used to 

add or subtract a percentage of the CFM selected. The 

Test jumper is used to operate the motor in the test mode. 

Figure 8 shows the blower control.

The CFM LED located on the blower control flashes one 

time per 100 cfm to indicate selected blower speed. For 

example, if the unit is operating at 1200 CFM, CFM LED 

will flash 12 times. If the CFM is 1150, CFM LED will flash 

11 full times plus one fast or half flash. At times the light may 

appear to flicker or glow. This takes place when the control 

is communicating with the motor between cycles. This is 

normal operation.Read through the jumper settings section 

before adjusting the jumper to obtain the appropriate blower 

speed.To change jumper positions, gently pull the jumper 

off  the  pins  and  place  it  on  the  desired  set  of  pins. The 

following  section  outlines  the  different  jumper  selections 

available and conditions associated with each one. Refer 

to Figure 8.

From  the  engineering  handbook  and/or  specification 

sheet, determine which row most closely matches the 

desired  CFM.  Once  a  specific  row  has  been  chosen  (+, 

NORMAL, or -), CFM volumes from other rows cannot be 

used. Below are descriptions of the jumper selections. 

The variable speed motor slowly ramps up to and down 

from the selected air flow during both cooling and heating 

demand. This minimizes noise and eliminates the initial 

blast of air when the blower is initially energized.

ADJUST

The ADJUST pins allow the motor to run at normal speed, 

approximately 15 percent higher, or approximately 15 

percent lower than normal speed. 

The TEST pin is available to bypass the blower control 

and run the motor at approximately 70 percent to make 

sure that the motor is operational. This is used mainly in 

troubleshooting. The G terminal must be energized for the 

motor to run.

d.  To Reassemble: Reverse above steps.

7.  After reassembly of all parts is complete and all wires 

are reconnected, open the main manual gas shutoff 

valve; check for and correct any gas leaks. Turn 

electrical power on, initiate a call for heat, and check 

for proper burner operation.

8.  Install burner access panel.

Summary of Contents for LRP16GE Series

Page 1: ...stries Inc Dallas Texas USA THIS MANUAL MUST BE LEFT FOR FUTURE REFERENCE WARNING Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss o...

Page 2: ...17 07 13 44 13 44 14 32 16 06 6 20 40 89 21 63 13 21 TYPICAL DRAIN LOCATION CONDENSATE DRAIN 3 4 NPT 5 75 3 55 4 12 TYPICAL VENT HOOD SIDE VIEWS 11 49 2 33 47 66 1 98 16 77 2 48 14 02 47 66 POWER ENT...

Page 3: ...AGE ENTRY 7 8 DIA KNOCKOUT GAS SUPPLY 44 89 21 63 13 21 TYPICAL DRAIN LOCATION CONDENSATE DRAIN 3 4 NPT 5 75 3 55 4 12 TYPICAL VENT HOOD SIDE VIEWS TOP VIEW POWER ENTRY GAS ENTRY RETURN AIR 2 11 19 49...

Page 4: ...44 3 8 1127 44 3 8 1127 16 7 8 429 13 7 8 352 2 1 8 54 11 1 2 287 SUPPLY OPENING RETURN OPENING 8 203 14 356 18 457 24 610 3 4 19 1 25 5 1 2 140 5 3 4 146 11 1 2 287 17 1 4 438 1 3 8 35 3 3 4 95 13 3...

Page 5: ...13 in 76 x 330 mm 52 7 8 1343 44 3 8 1127 19 1 2 380 11 1 2 287 19 1 2 380 2 1 8 54 11 1 2 287 SUPPLY OPENING RETURN OPENING 8 203 14 356 18 457 24 610 3 3 4 95 22 7 8 581 7 178 3 4 19 1 25 NOTE If bo...

Page 6: ...8 203 SIDES AND BACK FLANGE 6 152 UNIT BASE RAIL CLIPS 4 NOTE Minimum Height 4 102 UNIT BASE RAIL CLIPS 4 Usage A B C in mm in mm in mm 24 36 42 7 8 1089 13 7 8 352 16 7 8 429 48 60 51 3 8 1305 19 1 2...

Page 7: ...nits are not suitable for use with conventional venting systems Inspection As soon as the unit is received it should be inspected for possible damage during transit If damage is evident the extent of...

Page 8: ...s may be installed on combustible floors Units must be installed outdoors Clearance to combustibles below the unit flue is 10 inches since the flue points down Do not permit overhanging structures or...

Page 9: ...truction bag see Figure 2 Vent Hood Attach with Screws Figure 2 Installing the Vent Cover Rigging Unit Exercise care when moving the unit Do not remove any packaging until the unit is near the place o...

Page 10: ...ilter rack kit If an existing gas furnace is being removed from a common venting system when this packaged unit is installed then read and follow the instructions in the Removal of Unit from Common Ve...

Page 11: ...rating plate Gas Piping Recommendations A drip leg and a ground joint union must be installed in the gas piping A ground joint union is recommended by the manifold valve When required by local codes a...

Page 12: ...he National Electrical Code ANSI NFPA No 70 latest edition Canadian Electrical Code Part 1 CSA C22 1 latest edition or local codes where they prevail Use wiring with a temperature limitation of 75 C m...

Page 13: ...d insulated wires 18 AWG should be used to connect the thermostat to the unit Compressor Units are shipped with compressor mountings factory adjusted and ready for operation Do not loosen compressor m...

Page 14: ...as valve and connecting a water manometer or gauge Under no circumstances should the final manifold pressure vary more than 0 3 w c from the above specified pressures To adjust the regulator turn the...

Page 15: ...roughout the external static range A particular CFM can be obtained by positioning jumpers COOL HEAT and ADJUST on the blower control The HEAT and COOL jumpers are labeled A B C and D Each of the numb...

Page 16: ...duce the selected air flow rate by 25 percent when humidity levels are high An LED D1 lights when the blower is operating in the dehumidification mode Cooling System The cooling system is a factory ch...

Page 17: ...nds of the ignition trial If the flame is established within 10 seconds the control de energizes the spark If flame is not established within 10 seconds the gas valve and spark are de energized and th...

Page 18: ...need cleaning Sooting of a gas appliance is highly irregular and once cleaned the cause of the sooting must be determined If the heat exchanger should become sooted it can be cleaned as follows 1 Remo...

Page 19: ...eration Call for heat 2 Flash Two flashes in second with 1 second pause System lockout Failed to detect or sustain flame 3 Flash Three flashes in 1 5 seconds with 1 second pause Pressure switch senses...

Page 20: ...00 400 1260 1080 900 720 1400 1200 1100 975 630 540 450 360 048 Blower Performance 0 through 0 80 in w g External Static Pressure Range 1980 1760 1540 1320 1350 1200 1100 1000 990 880 770 660 NORM 180...

Page 21: ...Page 21 Figure 9 Wiring Diagram Single Phase Wiring Diagram LRP16GE...

Page 22: ...being pulled through the condensate line will prevent positive drainage without a proper trap The condensate drain line must be properly trapped routed to a suitable drain and primed prior to unit com...

Page 23: ...JUST jumper is labeled Test and Norm The and pin settings are used to add or subtract a percentage of the CFM selected The Test jumper is used to operate the motor in the test mode Figure 12 shows the...

Page 24: ...e is no demand for heating or cooling the blower control will provide 50 percent of the COOL CFM selected DEHUMIDIFICATION The blower control includes an HUM terminal which provides for connection of...

Page 25: ...l Board 24V TERMINAL STRIP CONNECTIONS DIAGNOSTIC LEDS HIGH PRESSURE SWITCH TEST PINS DEFROST TIMING PINS P1 REVERSING VALVE DEFROST THERMOSTAT S6 LOW PRESSURE SWITCH COMPRESSOR DELAY PINS S4 S87 SERV...

Page 26: ...he compressor delay jumper is removed NOTE The 30 second off cycle is not functional when jumpering the TEST pins Time Delay The defrost control includes a compressor timer which ensures the compresso...

Page 27: ...ance normally consists of changing or cleaning the filters and cleaning the evaporator coil On occasion other components may also require cleaning Filters Filters are not supplied with the unit Inspec...

Page 28: ...49 150 36 132 134 136 137 138 139 140 142 144 145 147 148 48 136 138 140 142 143 144 145 147 148 149 150 151 60 134 135 137 138 139 140 141 142 144 145 147 148 24 Liquid 237 257 278 298 306 320 343 36...

Page 29: ...36 26 33 40 50 54 61 68 75 83 95 103 117 131 48 28 36 43 53 57 65 72 79 89 102 107 116 125 60 31 39 46 56 60 68 75 82 89 99 106 117 128 24 Liquid 264 271 279 289 294 301 309 316 324 335 340 348 357 36...

Page 30: ...Page 30 Wiring Diagram LRP16HP Figure 14 HP Wiring Diagram...

Reviews: