background image

Single-Stage Deluxe

Induced-Combustion

4-Way Multipoise Furnace

Installation, Start-up, Operating, and

Service and Maintenance Instructions

Series 120/C

NOTE:

Read the entire instruction manual before starting the

installation.

This symbol

indicates a change since the last issue.

Portions of the text and tables are reprinted from NFPA 54/ANSI Z223.1-2002©,

with permission of National Fire Protection Association, Quincy, MA 02269 and
American Gas Association, Washington DC 20001. This reprinted material is not the
complete and official position of the NFPA or ANSI on the referenced subject, which
is represented only by the standard in its entirety.

TABLE OF CONTENTS

SAFETY CONSIDERATIONS .....................................................2

INTRODUCTION ..........................................................................3

CODES AND STANDARDS........................................................3

Safety.........................................................................................3
General Installation...................................................................5
Combustion and Ventilation Air ..............................................5
Duct Systems ............................................................................5
Acoustical Lining and Fibrous Glass Duct..............................5
Gas Piping and Gas Pipe Pressure Testing..............................5
Electrical Connections ..............................................................5

ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
PROCEDURE ................................................................................5

LOCATION....................................................................................5

General ......................................................................................5
Location Relative to Cooling Equipment ................................7

AIR FOR COMBUSTION AND VENTILATION ......................7

INSTALLATION .........................................................................10

Upflow Installation .................................................................10

Bottom Return Air Inlet ....................................................10
Side Return Air Inlet.........................................................10
Leveling Legs (If Desired)................................................10

Downflow Installation ............................................................10

Bottom Return Air Inlet ....................................................11

Horizontal Installation ............................................................12

Suspended Unit Support....................................................12
Platform Unit Support .......................................................12
Roll-Out Protection............................................................12
Bottom Return Air Inlet ....................................................13
Side Return Air Inlet.........................................................13

Filter Arrangement..................................................................13
Air Ducts.................................................................................13

General Requirements .......................................................13
Ductwork Acoustical Treatment .......................................13
Supply Air Connections ....................................................13
Return Air Connections.....................................................14

Gas Piping...............................................................................17
Electrical Connections ............................................................19

115-V Wiring.....................................................................19
J-Box Relocation ...............................................................20
Electrical Connection to J-Box .........................................20
Power Cord Installation.....................................................21

BX Cable Installation ........................................................21
24-V Wiring.......................................................................21
Accessories ........................................................................21

Venting ....................................................................................21

General Venting Requirements .........................................23
Masonry Chimney Requirements......................................23
Appliance Application Requirements ...............................27
Additional Venting Requirements.....................................29
Sidewall Venting ...............................................................29

START-UP, ADJUSTMENT, AND SAFETY CHECK ............33

General ....................................................................................33
Start-Up Procedures ................................................................33
Adjustments.............................................................................34
Check Safety Controls ............................................................36
Checklist..................................................................................37

SERVICE AND MAINTENANCE PROCEDURES..................40

Introduction .............................................................................40

General...............................................................................40
Electrical Controls and Wiring .........................................40

Care and Maintenance ............................................................44

Cleaning and/or Replacing Air Filter ...............................44
Blower Motor and Wheel..................................................44
Cleaning Heat Exchanger..................................................45

Sequence of Operation............................................................48
Wiring Diagrams.....................................................................50
Troubleshooting ......................................................................50

Cancels: II 311A-45-5

II 311A-45-6

4-06

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book 1

4

Tab

6a 8a

PC 101

Printed in U.S.A.

Pg 1

4-06

Summary of Contents for 120/C Series

Page 1: ...gs If Desired 10 Downflow Installation 10 Bottom Return Air Inlet 11 Horizontal Installation 12 Suspended Unit Support 12 Platform Unit Support 12 Roll Out Protection 12 Bottom Return Air Inlet 13 Side Return Air Inlet 13 Filter Arrangement 13 Air Ducts 13 General Requirements 13 Ductwork Acoustical Treatment 13 Supply Air Connections 13 Return Air Connections 14 Gas Piping 17 Electrical Connectio...

Page 2: ... service calls This is the safety alert symbol When you see this symbol on the furnace and in instructions or manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING and CAU TION These words are used with the safety alert symbol DAN GER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies a hazard which ...

Page 3: ...esign certified A Category I fan assisted furnace is an appliance equipped with an integral mechanical means to either draw or force products of combustion through the combustion chamber and or heat exchanger The furnace is factory shipped for use with natural gas This furnace is not approved for installation in mobile homes recreational vehicles or outdoors This furnace is designed for minimum co...

Page 4: ...onduit ommun d autres appareils à gaz MINIMUM INCHES CLEARANCE TO COMBUSTIBLE CONSTRUCTION Installation on non combusibible floors only For Installation on combustible flooring only when installed on special base Part No KGASB0201ALL Coil Assembly Part No CD5 or CK5 or Coil Casing Part No KCAKC 18 inches front clearance required for alcove Indicates supply or return sides when furnace is in the ho...

Page 5: ...precautions will help to avoid exposing the control to electrostatic discharge by putting the furnace the control and the person at the same electrostatic potential 1 Disconnect all power to the furnace Multiple disconnects may be required DO NOT TOUCH THE CONTROL OR ANY WIRE CONNECTED TO THE CONTROL PRIOR TO DIS CHARGING YOUR BODY S ELECTROSTATIC CHARGE TO GROUND 2 Firmly touch the clean unpainte...

Page 6: ...such as perchloroethylene Printing inks paint removers varnishes etc Hydrochloric acid Cements and glues Antistatic fabric softeners for clothes dryers Masonry acid washing materials All fuel burning equipment must be supplied with air for fuel combustion Sufficient air must be provided to avoid negative pressure in the equipment room or space A positive seal must be made between the furnace cabin...

Page 7: ...oil must be installed parallel with or on the downstream side of the unit to avoid condensation in the heat exchangers When installed parallel with the furnace dampers or other flow control must prevent chilled air from entering the furnace If the dampers are manually operated they must be equipped with means to prevent operation of either unit unless the damper is in the full heat or full cool po...

Page 8: ...ustion air supply must be provided in accordance with this instruction manual The Standard Method 1 The space has no less volume than 50 cubic feet per 1 000 Btuh of the maximum input ratings for all gas appliances installed in the space and 2 The air infiltration rate is not known to be less than 0 40 air changes per hour ACH Table 2 Minimum Free Area Required for Each Combustion Air Opening or D...

Page 9: ...thin 12 300 mm of the floor The minimum dimension of air openings shall be at least 3 in 80 mm See Fig 8 c Combining space on different floor levels The volumes of spaces on different floor levels shall be considered as communicating spaces if connected by one or more perma nent openings in doors or floors having free area of at least 2 in 2 1 000 Btuh 4 400 mm2 kW of total input rating of all gas...

Page 10: ...om closure panel perform the following 1 Tilt or raise furnace and remove 2 screws holding bottom filler panel See Fig 9 2 Rotate bottom filler panel downward to release holding tabs 3 Remove bottom closure panel 4 Reinstall bottom filler panel and screws Side Return Air Inlet These furnaces are shipped with bottom closure panel installed in bottom return air opening This panel MUST be in place wh...

Page 11: ...alled in bottom return air opening Remove and discard this panel when bottom return air is used To remove bottom closure panel perform the following 1 Tilt or raise furnace and remove 2 screws holding bottom filler panel See Fig 9 2 Rotate bottom filler panel downward to release holding tabs 3 Remove bottom closure panel PLENUM OPENING C A B D FLOOR OPENING A96283 Fig 11 Floor and Plenum Opening D...

Page 12: ...sts The sheet metal MUST extend underneath the furnace casing by 1 in with the door removed The bottom closure panel on furnaces of widths 17 1 2 in and larger may be used for flame roll out protection when bottom of furnace is used for return air connection See Fig 17 for proper orientation of roll out shield Table 4 Opening Dimensions In FURNACE CASING WIDTH APPLICATION PLENUM OPENING FLOOR OPEN...

Page 13: ...design external static pressure The furnace airflow rates are provided in Table 5 AIR DELIVERY CFM With Filter When a furnace is installed so that the supply ducts carry air circulated by the furnace to areas outside the space containing the furnace the return air shall also be handled by duct s sealed to the furnace casing and terminating outside the space containing the furnace Secure ductwork w...

Page 14: ...ide air duct humidifier or other accesso ries All accessories MUST be connected to duct external to furnace casing Return Air Connections FIRE HAZARD Failure to follow this warning could cause personal injury death and or property damage Never connect return air ducts to the back of the furnace Follow instructions below Downflow Furnaces The return air duct must be connected to return air opening ...

Page 15: ...SCREWS IN SIDE AND 2 SCREWS IN BOTTOM Fig 17 Typical Attic Installation A03177 30 IN MIN WORK AREA 6 MIN TYPE B VENT 17 3 4 22 SHEET METAL SEDIMENT TRAP EQUIPMENT MANUAL SHUT OFF GAS VALVE LINE CONTACT ONLY PERMISSIBLE BETWEEN LINES FORMED BY INTERSECTIONS OF THE TOP AND TWO SIDES OF THE FURNACE JACKET AND BUILDING JOISTS STUDS OR FRAMING GAS ENTRY 17 3 4 OVER ALL 4 3 4 UNDER DOOR 1 UNDER FURNACE ...

Page 16: ...1880 1715 2130 1995 1805 1645 2025 1895 1730 1565 1920 1785 1630 1480 1790 1675 1535 1390 1660 1565 1420 1280 1530 1420 1275 1145 1350 1260 1135 1005 Both Sides or 1 Side Bottom High Med High Med Low Low 2530 2285 1995 1770 2450 2215 1945 1740 2365 2150 1900 1700 2270 2075 1840 1645 2165 1985 1770 1575 2065 1890 1685 1505 1940 1780 1600 1415 1805 1660 1480 1325 1670 1525 1350 1190 1505 1360 1180 1...

Page 17: ... upstream of gas supply connection to furnace and downstream of manual equipment shutoff valve NOTE The furnace gas control valve inlet pressure tap connec tion is suitable to use as test gauge connection providing test pressure DOES NOT exceed maximum 0 5 psig 14 in wc stated on gas control valve See Fig 52 Some installations require gas entry on right side of furnace as viewed in upflow See Fig ...

Page 18: ...A02075 Fig 18 Upflow Return Air Configurations and Restrictions A02163 Fig 19 Downflow Return Air Configurations and Restrictions A02162 Fig 20 Horizontal Return Air Configurations and Restrictions 18 ...

Page 19: ...ower cord where permitted by local code when installed in accordance with existing electrical codes Refer to the power cord manufacturer s ratings for proper wire gauge Do not use gas piping as an electrical ground FURNACE MAY NOT OPERATE Failure to follow this caution may result in intermitent furnace operation Furnace control must be grounded for proper operation or else control will lock out Co...

Page 20: ... Box Do not pinch wires between cover and bracket Electrical Box on Furnace Casing Side See Fig 23 FIRE OR ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury death or property damage If field supplied manual disconnect switch is to be mounted on furnace casing side select a location where a drill or fastener cannot damage electrical or gas components 1 Select an...

Page 21: ...es between cover and bracket 24 V WIRING Make field 24 v connections at the 24 v terminal strip See Fig 23 Connect terminal Y Y2 as shown in Fig 24 for proper cooling operation Use only AWG No 18 color coded copper thermostat wire The 24 v circuit contains an automotive type 3 amp fuse located on the control Any direct shorts during installation service or maintenance could cause this fuse to blow...

Page 22: ...INAL 24 VAC 0 5 AMP MAX TWINNING AND OR COMPONENT TEST TERMINAL BLOWER OFF DELAY Fig 25 Heating and Cooling Application Wiring Diagram with 1 Stage Thermostat A99440 115 V FIELD SUPPLIED DISCONNECT AUXILIARY J BOX 24 V TERMINAL BLOCK THREE WIRE HEATING ONLY FIVE WIRE NOTE 1 NOTE 2 FIELD SUPPLIED DISCONNECT CONDENSING UNIT TWO WIRE FURNACE C O N T R O L R G COM W C R G Y GND GND FIELD 24 V WIRING F...

Page 23: ...essure to minimize the potential for vent gas leakage Category I furnaces operate with a flue loss not less than 17 percent to minimize the potential for condensation in the venting system These furnaces are approved for common venting and multistory venting with other fan assisted or draft hood equipped appliances in accordance with the NFGC or the NSCNGPIC the local building codes and furnace an...

Page 24: ...eed Air Conditioner A04216 See notes 2 5 8 and 10 on the page following these figures See notes 1 2 4 6 7 9 10 and 12 on the page following these figures A04217 Fig 28 Single Stage Furnace with Single Speed Heat Pump Dual Fuel See notes 1 2 3 4 6 8 9 10 and 12 on the page following these figures A04218 Fig 29 Single Stage Furnace with Two Speed Heat Pump Dual Fuel 24 ...

Page 25: ...Single Speed Heat Pump HUMIDFIER 24VAC See notes 1 2 3 4 11 12 and 14 on the page following these figures A04220 Fig 31 Dual Fuel Thermostat with Single Stage Furnace and Two Speed Heat Pump HUMIDFIER 24VAC See note 2 on the page following these figures A04221 Fig 32 Two Stage Thermostat with Single Stage Furnace and Two Speed Air Conditioner 25 ...

Page 26: ...y default 7 Dip switch No 2 on Thermidistat should be set in ON position for two speed compressor operation 8 Configuration Option No 10 Dual Fuel Selection must be turned ON in all dual fuel applications 9 NO connection should be made to the furnace HUM terminal when using a Thermidistat 10 The RVS Sensing terminal L should not be connected This is internally used to sense defrost operation 11 DO...

Page 27: ...tween the chimney and the metal liner APPLIANCE APPLICATION REQUIREMENTS Appliance operation has a significant impact on the performance of the venting system If the appliances are sized installed adjusted and operated properly the venting system and or the appliances should not suffer from condensation and corrosion The venting system and all appliances shall be installed in accordance with appli...

Page 28: ...lignment missing sections gaps Debris in cleanout Mortar tile metal vent fuel oil residue Is liner and top seal in good condition Is chimney property lined with clay tile liner Crown condition Missing mortar or brick Rebuild crown Yes Yes No No No Reline Yes Repair Yes Yes Yes No No Remove mortar and tile debris Remove metal vent or liner No No No No Yes Yes Suitable Suitable Not Suitable Line chi...

Page 29: ...ue extension is used fasten the flue extension to the vent elbow with at least two field supplied corrosion resistant sheet metal screws located 180 apart Fasten the vent connector to the flue extension with at least two field supplied corrosion resistant sheet metal screws located 180 apart 2 Vent the furnace with the appropriate connector as shown in Fig 34 46 CUT HAZARD Failure to follow this c...

Page 30: ...he page following these figures A03210 Fig 36 Downflow Application Vent Elbow Up then Left SEE NOTES 1 2 4 5 7 8 9 on the page following these figures A03211 Fig 37 Downflow Application Vent Elbow Up SEE NOTES 1 2 4 5 6 7 8 9 10 on the page following these figures A03207 Fig 38 Downflow Application Vent Elbow Left then Up SEE NOTES 1 2 3 4 5 7 8 9 on the page following these figures A03212 Fig 39 ...

Page 31: ... 8 9 on the page following these figures A03215 Fig 42 Horizontal Left Application Vent Elbow Up SEE NOTES 1 2 4 5 7 8 9 on the page following these figures A03216 Fig 43 Horizontal Left Application Vent Elbow Right SEE NOTES 1 2 4 7 8 9 on the page following these figures A03218 Fig 44 Horizontal Right Application Vent Elbow Right SEE NOTES 1 2 4 5 7 8 9 on the page following these figures A03219...

Page 32: ...nal to the furnace 6 Accessory Downflow Vent Guard Kit KGAVG0101DFG required in downflow installations with lower vent configuration 7 Chimney Adapter Kit may be required for exterior masonry chimney applications Refer to Chimney Adapter Kit KGACA02014FC or KGACA02015FC for sizing and complete application details 8 Secure vent connector to furnace elbow with 2 corrosion resistant sheet metal screw...

Page 33: ...tion 2 Make thermostat wire connections at the 24 v terminal block on the furnace control Failure to make proper connections will result in improper operation See Fig 25 3 Gas supply pressure to the furnace must be greater than 4 5 in wc 0 16 psig but not exceed 14 in wc 0 5 psig 4 Check all manual reset switches for continuity 5 Install blower compartment door Door must be in place to operate fur...

Page 34: ...ifices Improper drilling burrs out of round holes etc can cause excessive burner noise and misdirection of burner flames This can result in flame impingement of heat exchangers causing failures See Fig 53 Furnace gas input rate on rating plate is for installations at altitudes up to 2000 ft Furnace input rate must be within 2 percent of furnace rating plate input For altitudes above 5500 ft a fiel...

Page 35: ...rilled check orifice hole with a numbered drill bit of correct size Never redrill an orifice A burr free and squarely aligned orifice hole is essential for proper flame characteristics 4 Verify natural gas input rate by clocking meter NOTE Gas valve regulator adjustment cap must be in place for proper input to be clocked a Turn off all other gas appliances and pilots served by the meter b Run furn...

Page 36: ...on is at the mid point of rise range or slightly above 6 Set thermostat heat anticipator a Mechanical thermostat Set thermostat heat anticipator to match the amp draw of the electrical components in the R W circuit Accurate amp draw readings can be obtained at the wires normally connected to thermostat subbase terminals R and W The thermostat anticipator should NOT be in the circuit while measurin...

Page 37: ...ning the call for heat again i Furnace should ignite normally Step 5 Checklist 1 Put away tools and instruments Clean up debris 2 Verify that blower OFF DELAY time is selected as desired 3 Verify that blower and burner access doors are properly installed 4 Cycle test furnace with room thermostat 5 Check operation of accessories per manufacturer s instruc tions 6 Review User s Guide with owner 7 At...

Page 38: ...50 43 3 7 43 3 8 42 3 2 42 3 3 875 43 3 5 43 3 6 43 3 7 43 3 8 900 43 3 3 43 3 4 43 3 5 43 3 6 925 43 3 1 43 3 2 43 3 3 43 3 4 950 43 2 9 43 3 0 43 3 1 43 3 2 975 43 2 8 43 2 9 43 3 0 43 3 1 1000 43 2 6 43 2 7 43 2 8 43 2 9 ALTITUDE RANGE FT AVG GAS HEAT VALUE BTU CU FT SPECIFIC GRAVITY OF NATURAL GAS 0 58 0 60 0 62 0 64 Orifice No Manifold Pressure Orifice No Manifold Pressure Orifice No Manifold...

Page 39: ...43 3 0 43 3 1 43 3 2 750 43 2 7 43 2 8 43 2 9 43 3 0 775 43 2 6 43 2 7 43 2 7 43 2 8 800 43 2 4 43 2 5 43 2 6 43 2 7 825 43 2 3 43 2 3 43 2 4 43 2 5 850 43 2 1 43 2 2 43 2 3 43 2 4 ALTITUDE RANGE FT AVG GAS HEAT VALUE AT ALTITUDE BTU CU FT SPECIFIC GRAVITY OF NATURAL GAS 0 58 0 60 0 62 0 64 Orifice No Manifold Pressure Orifice No Manifold Pressure Orifice No Manifold Pressure Orifice No Manifold P...

Page 40: ...ensing electrode The 24 v circuit contains an automotive type 3 amp fuse located on the control See Fig 24 Any shorts of the 24 v wiring during installation service or maintenance will cause this fuse to blow If fuse replacement is required use ONLY a 3 amp fuse The control LED will display status code 24 when fuse needs to be replaced Proper instrumentation is required to service electrical contr...

Page 41: ...50 43 3 3 43 3 5 43 3 6 43 3 7 875 43 3 2 43 3 3 43 3 4 43 3 5 900 43 3 0 43 3 1 43 3 2 43 3 3 925 43 2 8 43 2 9 43 3 0 43 3 1 950 43 2 7 43 2 8 43 2 9 43 2 9 975 43 2 5 43 2 6 43 2 7 43 2 8 1000 43 2 4 43 2 5 43 2 6 43 2 7 ALTITUDE RANGE FT AVG GAS HEAT VALUE BTU CU FT SPECIFIC GRAVITY OF NATURAL GAS 0 58 0 60 0 62 0 64 Orifice No Manifold Pressure Orifice No Manifold Pressure Orifice No Manifold...

Page 42: ...1 43 3 2 725 43 2 7 43 2 8 43 2 9 43 2 9 750 43 2 5 43 2 6 43 2 7 43 2 8 775 43 2 3 43 2 4 43 2 5 43 2 6 800 43 2 2 43 2 3 43 2 3 43 2 4 825 43 2 1 43 2 1 43 2 2 43 2 3 850 48 3 7 43 2 0 43 2 1 43 2 1 ALTITUDE RANGE FT AVG GAS HEAT VALUE AT ALTITUDE BTU CU FT SPECIFIC GRAVITY OF NATURAL GAS 0 58 0 60 0 62 0 64 Orifice No Manifold Pressure Orifice No Manifold Pressure Orifice No Manifold Pressure O...

Page 43: ...trol valve relay 22 ABNORMAL FLAME PROVING SIGNAL Flame is proved while gas valve is de energized Inducer will run until fault is cleared Check for Leaky gas valve Stuck open gas valve 23 PRESSURE SWITCH DID NOT OPEN Check for Obstructed pressure tubing Pressure switch stuck closed 24 SECONDARY VOLTAGE FUSE IS OPEN Check for Short circuit in secondary voltage 24VAC wiring If status code recall is ...

Page 44: ...pes or broken fittings Have vent pipes vent system serviced by a qualified service agency 6 Inspect any accessories attached to the furnace such as a humidifier or electronic air cleaner Perform any service or maintenance to the accessories as recommended in the acces sory instructions CLEANING AND OR REPLACING AIR FILTER The air filter arrangement will vary depending on the application The filter...

Page 45: ...by hand to verify that the wheel does not rub on the housing 15 Reinstall blower assembly in furnace 16 Reinstall control box assembly in furnace UNIT DAMAGE HAZARD Failure to follow this caution may result in shortened heat exchanger life Heating fan speed s MUST be adjusted to provide proper air temperature rise as specified on the rating plate Recom mended operation is at the midpoint of the ri...

Page 46: ...n optimum speed selection 10 Factory connected when BVSS Chimney Adapter Accessory Kit is not installed 11 Factory connected when LGPS is not used 12 Ignition lockout will occur after four consecutive unsuccessful trials for ignition Control will auto reset after three hours 13 Blower on delay gas heating 25 seconds cooling or heat pump 2 seconds 14 Blower off delay gas heating selections are 90 1...

Page 47: ... at local hardware stores 1 Attach variable speed reversible drill to the end of spring cable end opposite brush 2 Insert brush end of cable into the outlet opening of cell and slowly rotate with drill DO NOT force cable Gradually insert cable into upper pass of cell See Fig 59 3 Work cable in and out of cell 3 or 4 times to obtain sufficient cleaning DO NOT pull cable with great force Reverse dri...

Page 48: ... At the end of the prepurge period the Hot Surface igniter HSI is energized for a 17 second igniter warm up period c Trial for Ignition Sequence When the igniter warm up period is completed the main gas valve relay contacts GVR close to energize the gas valve GV the gas valve opens and 24 vac power is supplied for a field installed humidi fier at the HUM terminal The gas valve GV permits gas flow ...

Page 49: ...g is satisfied and there is a demand for dehumidification the cooling blower off delay is decreased from 90 seconds to 5 seconds 4 Continuous Blower Mode When the R to G circuit is closed by the thermostat the blower motor BLWM will operate on continuous blower speed can be adjusted to FAN HEAT or COOL speed at the thermostat Factory default is FAN speed Terminal EAC 1 is energized as long as the ...

Page 50: ... delay If the R to W and Y Y2 and G or R to W and Y1 and Y Y2 and G signals disappear at the same time the blower motor BLWM will remain on for the selected blower OFF delay period If the R to W and Y Y2 or R to W and Y1 and Y Y2 signals disappear leaving the G signal the blower motor BLWM will remain on for the selected blower OFF delay period then switch to continuous blower speed Step 4 Wiring ...

Page 51: ... go through a brief component test sequence The inducer will start and run for the entire component test The HSI blower motor FAN speed AMBER LED boards only HEAT speed and COOL speed will run for 10 15 seconds each Gas valve and humidifier will not be turned on Was there a previous status code other than 11 Is door switch closed Is there 115V going to switch Replace door switch Replace transforme...

Page 52: ...ING FAILURE If flame is not sensed during the trial for ignition period the control will repeat the ignition sequence 3 more times before lockout 14 occurs If flame signal is lost during the blower on delay period blower will come on for the selected blower off delay Check the following items first before proceeding to the next step Gas valve turned off Manual shut off valve Green Yellow wire MUST...

Reviews: